107 W. Main Street Worthington, PA 16262 Phone: 724.297.3416 Fax: 724.297.5189 http://www.airtak.com INSTALLATION, OPERATION AND MAINTENANCE Instructions for Refrigerated Water Chillers Models C-25 through C-8000...
CONTENTS A. INTRODUCTION B. RECEIVING C. LOCATION D. FOUNDATION E. PIPING F. ELECTRICAL G. CHILLED FLUID CIRCUIT - 1. Fluid to Refrigerant Heat Exchanger. H. REFRIGERANT CIRCUIT 1. Refrigerant Compressor 2. Air Cooled Condenser and Condenser Fan Cycling control (Low Ambient) 3.
A. INTRODUCTION AIR/TAK Refrigerated Fluid Chillers are of the high-efficiency type, designed to effectively remove heat from process cooling fluids by means of a refrigeration process. The process fluid temperature is reduced to the temperature required by your machinery. AIR/TAK chillers are completely automatic in all respects. As with all AIR/TAK products, minimal maintenance is required.
D. FOUNDATION All chillers are completely free-standing units. Any reasonably level floor that has sufficient strength will serve as a foundation. E. PIPING When piping the main fluid lines to the chiller, the use of flexible connections are recommended to avoid piping stress and vibration.
G. CHILLED WATER CIRCUIT 1. Chilled Water-to-Refrigerant Heat Exchanger (Evaporator): This exchanger is of the brazed plate stainless steel design. The evaporator is engineered with maximum efficiency in mind. 2. Water pump: The water pump must be checked for proper direction of operation. Set GPM by amps compared to pump curve.
3. Evaporator: Water-to-Refrigerant Heat Exchanger: The evaporator is constructed of high quality copper tubing. Cold liquid refrigerant is efficiently fed by a venturi type distributor to each circuit. The circuiting within the evaporator is designed to insure adequate refrigerant velocity to eliminate the problem of oil return to the crankcase. 4.
9. Automatic Water Regulating Valve: This control is found only in chillers equipped with water cooled condensers. The purpose of the valve is to control the flow of water through the condenser at a rate that is factory set to maintain a constant condensing pressure.
ambients, high inlet fluid temperatures or high fluid flow rates. 16. Start Timer: Standard on C-1200 and larger chillers. This timing device is used in conjunction with the High Temperature Control in item 16. During start-up, this device will temporarily energize the compressors electrical circuit.
J. DESIGN CONDITIONS Each chiller is shipped complete and ready for installation. Every chiller is tested and preset at the factory for optimum service at the design conditions. The following are the standard design conditions for a refrigerated chiller operating at 60 HZ: 95°...
M. TROUBLESHOOTING GUIDE SYMPTOM PROBABLE CAUSE REMDY Chiller not running. (Power a. Disconnect open. a. Close disconnect. on light off, high temperature light off, analyzer gauge b. Fuse blown. b. Replace fuse. normal.) c. Wiring, improper or broken. c. Check wiring diagram or repair. d.
Page 11
M. TROUBLESHOOTING GUIDE CONTINUED SYMPTOM PROBABLE CAUSE REMDY Chiller running. (Power on a. Defective hot gas bypass valve. a. Replace. light on, high temperature light off, analyzer gauge b. Defective fan control (low b. Replace. pressure low) ambient control). c. Low ambient termperature. c.
Page 12
BLOWER PURGE REGENERATIVE AIR DRYERS * EXTERNALLY HEATED REGENERATIVE AIR DRYERS AIR CHILLERS * FLUID CHILLERS For an authorized distributor near you, contact Air/Tak at: Air/Tak Inc. 107 West Main Street, Worthington, PA 16262 Phone: 724.297.3416 Fax: 724.297-5189 URL: http://www.airtak.com e-mail: airtak@airtak.com...