REFRIGERATED AIR DRYERS Operating Instructions Models SD-10 through SD-250 AIR/TAK 107 W. Main Street Worthington, PA 16262 724.297.3416 www.airtak.com 11/2013...
SPECIFICATIONS: Refrigerant: R134a Maximum Inlet Pressure: 250 psig Maximum Inlet Temperature: 120°F Minimum Ambient Temperature: 50°F Maximum Ambient Temperature 110°F OPERATION: Under normal conditions, the air dryer will run continuously when power is on. The dryer will provide a specified pressure dew point for the compressed air system with little maintenance or adjustments required.
Page 3
Ambient Conditions: A. Indoor installation is recommended. Dryers installed outdoors must be well protected from precipitation, dust, dirt, debris and animals. B. The unit should be installed in a well ventilated area. Ambient temperature must be in the temperature range of 50°F to 110°F. C.
Page 4
moisture removal and temperature variation demands on the refrigerated dryer. Between the compressed air receiver and dryer, a general purpose coalescing filter with an automatic drain is used to remove liquid water, liquid oil and solid particles from the airstream. Pre-filtering eases the load on the dryer and prevents an emulsion of water, oil and particulates from forming.
Page 5
AIR & REFRIGERANT CIRCUITS: Air Circuit Warm wet compressed air enters the refrigerant dryer at the inlet port. (On models 30 scfm through 250 scfm) It first passes through an air-to-air heat exchanger where its temperature is lowered by the cool air exiting the dryer. It then enters the evaporator or refrigerant-to-air heat exchanger where its temperature is lowered.
TROUBLESHOOTING GUIDE PROBLEM POSSIBLE CAUSE REPAIR Water in 1. Inlet and outlet connections are Check inlet and outlet connections. This system. reversed. dryer is designed for air flow in one direction only. Inlet and outlets are identified. 2. Drain trap is clogged or inoperative. Restore a free flow of water.
Page 7
TROUBLESHOOTING GUIDE continued 9. Shortage of refrigerant Fix the leak and add a charge of refrigerant. Loss of refrigerant will cause improper functioning. A qualified refrigerant specialist should perform the necessary repairs, or factory should be contacted if the unit is under warranty. 10.
Page 8
TROUBLESHOOTING GUIDE continued 3. Faulty refrigerant compressor or Determine the cause and make controls. Power on light will be on. corrections. Failure of compressor to run may be due to several factors. A qualified refrigeration specialist should check all electrical and refrigerant controls, or factory should be contacted if unit is in warranty.
Page 9