1
Power the Gateway and
Sensor Pod(s)
Install (3) AA-size batteries in the battery
bay on the underside of the unit. It is recommended
that batteries are installed even if the Pod is
powered by the AC power cable. Turn the Pod on by
holding the on/off button located on the front of
the Pod for several seconds until both LEDs on the
Pod become lit.
Associate
Wireless Status
LED (red)
To power down the Pod, hold the On/Off switch for
several seconds until the red LEDs turns solid, then
release. No data is collected when the Pod is
powered off.
Power
Ethernet
Connection
On/Off Switch
Associate
Link LED
Activity LED
Plug the AC adapter power cable into the
back of the unit. Use the included Ethernet cable to
connect the Gateway to a broadband Internet
connection and then power using the on/off switch.
The Ethernet link LED will appear orange when a
physical link is established. The Ethernet activity
LED flashes when the Ethernet is sending data.
2
establishes communication between the devices.
To associate, hold the associate button on the Pod
for at least 5 seconds until the red LED on the Pod
flashes rapidly. Release the associate button on
the Pod and immediately push the red associate
button on the back of the Gateway for 1 second.
During the association process, LEDs on the Pod
On/Off Switch
and the Gateway will blink rapidly for up to 30
seconds. Each Sensor Pod should be associated to
Wireless Network
the Gateway separately.
Transmit LED
(yellow)
than 80 meters apart from at least one Sensor Pod.
This distance may be shorter if operating in an
environment with obstacles that interfere with
radio frequency transceivers. If multiple Sensor
Pods are associated in the network, the Pods
should be placed within 80 meters of one another in
order to form a mesh network and communicate
with the Gateway.
Associate Sensor Pod(s)
with the Gateway
Associating Sensor Pods to the Gateway
The Gateway must be located no further
3
Access Online Account
Log onto
http://www.accsense.com
enter using the "customer login" link. To access
your secure online account, use the MAC number
located on the back of the Gateway unit. The
default login name and password are both Admin
(case-sensitive). We recommend you change
your login and password using the Account
Options link at the top of the screen after your
first login. Use your online account to view data
and to set alarms.
# # # # # # # # #
Admin
•••••
Default Login and Password are
both Admin (case-sensitive)
In the event that a Pod loses connection
with the system, up to 256 data points can be
stored in the Pod. When the Pod regains
connection to the Gateway or another pod, the
data will be sent to your online account.