Slide the cover back into place and secure captive screw.
13
Turn on the water supply and plug in the humidifier.
POWER
HUMIDIFYING
CLEAN TANK
SEE LABEL BELOW !
14
CALL SERVICE
PRESS RESET
PRESS EMPTY
RESET
EMPTY
M24763
Turn the control to a high setpoint (60% +). Be sure to turn this back down when test-
15
ing is complete. "Off" will turn the humidifier off.
Confirm that the furnace blower turns on to circulate air. This will take about 10–15
16
minutes upon call for humidity.
Important for Remote Installation:
After the humidifier has produced steam for 10–15 minutes, check the integrity of the
remote hose to ensure no sags have occurred. Add or adjust clamps if necessary to
ensure 2 in. per foot continuous slope.
The Press Reset light will blink when
power is applied.
Press/release the RESET button to
ready the humidifier. If not pushed,
the humidifier will automatically move
to ready after five minutes.
17
Humidification System
WIRIng
M24762
69-2307—01