Long-run UPS Series Quick Guide
1. Product Introduction
This UPS is a compact unit which combines both benefits of UPS and inverter for long-time
operation. It can accept wide input voltage range and provide stable and pure power source to
the connected devices such as personal computer, monitor and other precious 3C products.
2. Product Overview
Front View:
LCD panel
600 model
1K model
Back View:
600 model
Power Switch
Line mode indicator: green lighting
Battery mode indicator: yellow flashing
Fault indicator: red lighting
Version. 2.1
LCD Panel:
Input voltage
Output voltage
AC mode indicator
Battery mode indicator
Load level indicator,
flashing indicates overload
Battery capacity indicator,
flashing indicates low battery
1000 model
AC input
Output receptacles
Circuit breaker
External battery terminal
3. Important Safety Warning (SAVE THESE INSTRUCTIONS)
CAUTION! Careful to reduce the risk or dropping a metal tool on the batteries. It could spark
or short circuit the batteries and could cause an explosion.
CAUTION! Remove personal metal items such as rings, bracelets, necklaces, and watches
when working with batteries. Batteries can produce a short circuit current high enough to
make metal melt, and could cause severe burns.
CAUTION! Avoid touching eyes while working near batteries.
CAUTION! Have plenty of fresh water and soap nearby in case battery acid contacts skin,
clothing, or eyes.
CAUTION! NEVER smoke or allow a spark or flame in vicinity of a battery.
CAUTION! If a remote or automatic generator start system is used, disable the automatic
starting circuit or disconnect the generator to prevent accident during servicing.
CAUTION! The unit is designed for indoor use. Do not expose this unit to rain, snow or liquids
of any type.
CAUTION! To reduce risk of injury, only use qualified batteries from qualified distributors or
manufacturers. Any unqualified batteries may cause damage and injury. Do NOT use old or
overdue batteries. Please check the battery type and date code before installation to avoid
damage and injury.
WARNING! It's very important for system safety and efficient operation to use appropriate
external battery cable. To reduce risk of injury, external battery cables should be UL certified
and rated for 75° C or higher. And do not use copper cables less than 10AWG. Below is the
external battery cable reference according to system requirements.
Table 1 Minimum Recommended Battery Cable Size versus Length
Model
600
1K
CAUTION! Do not disassemble the unit Contact with the qualified service center when service
or repair is required.
WARNING! Provide ventilation to outdoors from the battery compartment. The battery
enclosure should be designed to prevent accumulation and concentration of hydrogen gas at
the top of the compartment.
CAUTION! Use insulated tools to reduce the chance of short-circuit when installing or working
with the inverter, the batteries, or other equipments attached to this unit.
CAUTION! For battery installation and maintenance, read the battery manufacturer's
installation and maintenance instructions prior to operating.
5. Installation
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is
damaged.
Checking Package Contents
You should receive the following items inside of the package:
UPS unit
User manual
Typical Amp.
1 meter (one-way)
40 A
AWG 10
59 A
AWG 8
Dia-mm
5.0
5.9

Advertisement

loading

Summary of Contents for Long-run UPS Series

  • Page 1 3. Important Safety Warning (SAVE THESE INSTRUCTIONS) Long-run UPS Series Quick Guide CAUTION! Careful to reduce the risk or dropping a metal tool on the batteries. It could spark or short circuit the batteries and could cause an explosion. Version. 2.1 CAUTION! Remove personal metal items such as rings, bracelets, necklaces, and watches 1.
  • Page 2 Connect External Battery Connect to Utility and Charge Step 1 - Install a DC Breaker in a positive battery line. The rating of the DC Breaker must be Plug in the AC input cord to the wall outlet. The unit will automatically charge the connected according to the inverter's battery current (50 Amp).