Diagnosis Methods Of A Malfunction Of A Compressor - Panasonic CS-C18KKS Service Manual

Hide thumbs Also See for CS-C18KKS:
Table of Contents

Advertisement

15.1.1
Relationship between the condition of the air conditioner and pressure and
electric current
Condition of the
air conditioner
Insufficient refrigerant
(gas leakage)
Clogged capillary tube or
strainer
Short circuit in the indoor unit
Heat radiation deficiency
of the outdoor unit
Inefficient compression
• Carry out the measurement of pressure, electric current, and temperature fifteen minutes after an operation is started.
15.1.2

Diagnosis methods of a malfunction of a compressor

Nature of fault
Insufficient compressing of a compressor
Locked compressor
Low Pressure
• Electric current during operation becomes approximately 20% lower than the normal value.
• The discharge tube of the compressor becomes abnormally hot (normally 70°C to 90°C).
• The different between high pressure and low pressure becomes almost zero.
• Electric current reaches a high level abnormally, and the value exceeds the limit of an
ammeter. In some cases, a breaker turns off.
• The compressor has a humming sound.
54
Cooling Mode
High Pressure
Electric current during operation
Symptom

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cs-c24kksCu-c24kksCu-c18kks

Table of Contents