Unitary products group GY8S*UH Installation Manual

High efficiency tubular heat exchanger series
Table of Contents

Advertisement

Quick Links

INSTALLATION MANUAL
INSTALLATION MANUAL
INSTALLATION MANUAL
INSTALLATION MANUAL
HIGH EFFICIENCY
TUBULAR HEAT EXCHANGER SERIES
MODELS: GY8S*UH / GM8S*UH / GR8S*UH / LY8S*UH / LM8S*UH / LF8*UH
(Single Stage Upflow / Horizontal / Low NOx)
40 - 130 MBH INPUT
(11.72 - 38.10 KW) INPUT
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
DUCTWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
FILTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
GAS PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
ELECTRICAL POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Typical Attic Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Side Return Cutout Markings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Gas Valve - All Except GR Models . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Gas Valve - GR Models Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Upflow Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Horizontal Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Thermostat Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Accessory Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Typical Twinned Furnace Application . . . . . . . . . . . . . . . . . . . . . . . . 12
Single Stage Twinning Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . 13
Two-Stage Twinning Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . 13
Vent Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Vent Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Typical Sidewall Vent Application . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Unit Clearances to Combustibles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Minimum Duct Sizing For Proper Airflow . . . . . . . . . . . . . . . . . . . . . . . 4
Round Duct Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Cabinet and Duct Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Filter Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Nominal Manifold Pressure - High Fire . . . . . . . . . . . . . . . . . . . . . . . . 9
Roof Pitch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Estimated Free Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Free Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
SECTION I: SAFETY
SECTION I: SAFETY
SECTION I: SAFETY
SECTION I: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property dam-
age.
LIST OF SECTIONS
TWINNING AND STAGING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
VENT SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
SAFETY CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
START-UP AND ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . .20
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SAFETY 1
LIST OF FIGURES
Home Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Casing to the Burner Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Air Inlet, Outlet and Chimney Connections . . . . . . . . . . . . . . . . . . . . .17
Typical Chimney Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Outside and Ambient Combustion Air . . . . . . . . . . . . . . . . . . . . . . . . .18
Pressure Switch Tubing Routing . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Gas Valve - GR Models Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Reading Gas Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Typical Heat/Cool Speed Tap Connections . . . . . . . . . . . . . . . . . . . .24
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
LIST OF TABLES
Unconfined Space Minimum Area in Square Inch . . . . . . . . . . . . . . .18
Inlet Gas Pressure Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Nominal Manifold Pressure - GR Models . . . . . . . . . . . . . . . . . . . . . .23
Field Installed Accessories - Non Electrical . . . . . . . . . . . . . . . . . . . .25
Bottom Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Left Side Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or mainte-
nance can cause injury or property damage. Refer to this manual
for assistance or for additional information, consult a qualified con-
tractor, installer or service agency.
This product must be installed in strict compliance with the installa-
tion instructions and any applicable local, state, and national codes
including, but not limited to building, electrical, and mechanical
codes.
EFFICIENCY
RATING
CERTIFIED
ISO 9001
Certified Quality
Management System
166753-UIM-C-0706

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the GY8S*UH and is the answer not in the manual?

Questions and answers

Summary of Contents for Unitary products group GY8S*UH

  • Page 1: Table Of Contents

    HIGH EFFICIENCY EFFICIENCY RATING TUBULAR HEAT EXCHANGER SERIES CERTIFIED MODELS: GY8S*UH / GM8S*UH / GR8S*UH / LY8S*UH / LM8S*UH / LF8*UH (Single Stage Upflow / Horizontal / Low NOx) ISO 9001 Certified Quality Management System 40 - 130 MBH INPUT (11.72 - 38.10 KW) INPUT...
  • Page 2: Safety

    Never operate the furnace with the blower door removed. To • Furnaces for installation on combustible flooring shall not be do so could result in serious personal injury and/or equipment installed directly on carpeting, tile or other combustible material damage. other than wood flooring. Unitary Products Group...
  • Page 3: Ductwork

    Unitary Products Group...
  • Page 4: Minimum Duct Sizing For Proper Airflow

    To properly design the ductwork for the build- 12 (30) 113.1 (730) ing, refer to the ASHRAE Fundamentals Handbook, Chapter on “DUCT 13 (33) 132.7 (856) DESIGN” or a company that specializes in Residential and Modular Home duct designs. 14 (36) 153.9 (993) Unitary Products Group...
  • Page 5: Dimensions

    19 3/4 50.2 17 3/4 45.1 13 3/8 115/92 (33.7/27.0) 2000 (56.6) 53.3 19 3/4 50.2 17 3/4 45.1 13 3/8 130/104 (38.1/30.5) 2000 (56.6) 24 1/2 62.2 23 1/4 59.1 21 3/8 54.3 15 1/8 27.6 Unitary Products Group...
  • Page 6: Typical Attic Installation

    WORK AREA 12” Refer to the installation instructions supplied with the air conditioning coil for additional information. RETURN AIR SEDIMENT TRAP FIGURE 2: Typical Attic Installation Unitary Products Group...
  • Page 7: Filters

    IMPORTANT: Some accessories such as electronic air cleaners and pleated media may require a larger side opening. Follow the instruc- tions supplied with that accessory for side opening requirements. Do not cut the opening larger than the dimensions shown in Figure 1. Unitary Products Group...
  • Page 8: Gas Piping

    For altitudes above 8,000 feet (2,438 m), see Table 16 Field Installed Accessories - High Altitude Pressure Switch GROUNDED JOINT UNION DRIP MAY BE INSTALLED INSIDE OR OUTSIDE UNIT. FIGURE 7: Upflow Gas Piping Unitary Products Group...
  • Page 9: Electrical Power

    Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures. Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes. The furnace shall be installed so that the electrical components are protected from water. Unitary Products Group...
  • Page 10: Electrical Wiring

    Reposition on the left side of the furnace and fas- ten using holes provided. BLK/BLK WHT/WHT GRN/GRN JUNCTION BLOWER COMPARTMENT DOOR SWITCH TRANSFORMER CLASS 2 SYSTEM CONTROL WIRING IGNITION MODULE TO THERMOSTAT BURNER COMPARTMENT FIGURE 9: Electrical Wiring Unitary Products Group...
  • Page 11: Thermostat Chart

    166753-UIM-C-0706 FIGURE 10: Thermostat Chart Unitary Products Group...
  • Page 12: Accessory Connections

    The relay must not be installed in any location where it could be exposed to water. If the relay has been exposed to water in any way, it must not be used. Unitary Products Group...
  • Page 13: Single Stage Twinning Wiring Diagram

    G signal is removed. FURNACE 2 CONTROL BOARD FURNACE 1 CONTROL BOARD TO A/C WALL THERMOSTAT TWIN TWIN FIGURE 13: Single Stage Twinning Wiring Diagram ISOLATION RELAY TO A/C WALL THERMOSTAT FIGURE 14: Two-Stage Twinning Wiring Diagram Unitary Products Group...
  • Page 14: Vent Termination

    Over 14/12 to 16/12 1.83 The chimney must extend at least 5 ft (1.5 m) above the highest Over 16/12 to 18/12 2.13 equipment draft hood or flue collar. Over 18/12 to 20/12 2.27 Over 20/12 to 21/12 2.44 Unitary Products Group...
  • Page 15: Typical Sidewall Vent Application

    VENT CLEARANCES VENT CLEARANCES VENT CLEARANCES VENT CLEARANCES IMPORTANT: The vent must be installed with the following minimum clearances as shown in Figure 20, must comply with local codes and requirements. Unitary Products Group...
  • Page 16: Home Layout

    Horizontal portions of the vent system must slope upwards and be supported to prevent sagging. The vent system may be supported by the use of clamps or hangers secured to a permanent part of the structure every 4 ft. (1.22 m). Unitary Products Group...
  • Page 17: Estimated Free Area

    CHIMNEY OR GAS VENT OUTLET INLET ALTERNATE AIR INLET OPENING VENTILATION LOUVERS FOR UNHEATED CRAWL SPACE FIGURE 21: Alternate Air Intake, Air Outlet and Chimney Connections OPENING FIGURE 23: Typical Chimney Connections Unitary Products Group...
  • Page 18: Free Area

    4. The blocking effects of louvers, grilles and screens must be given INLET AIR (b) consideration in calculating free area. If the free area of a specific AIR (a) louver aor grille is not known. FIGURE 25: Outside and Ambient Combustion Air Unitary Products Group...
  • Page 19: Safety Controls

    Refer to Figure 27 for tubing connections. Blockage of vent piping or terminal. Failure of combustion air blower motor. Unitary Products Group...
  • Page 20: Start-Up And Adjustments

    • 1 - 5/16” (0.8 cm) tee Calculate the furnace input by using one of the following equa- • 1 – 5/16” (0.8 cm) x 1/8” (3.175 mm) reducing coupling tions. • 1 – 1/8” (0.3 cm) adapter Unitary Products Group...
  • Page 21 If the actual input is significantly higher than the furnace input specified on the rating plate then replace the gas orifice spuds with the gas ori- fice spuds of the proper size for the type of gas you are using. Unitary Products Group...
  • Page 22: Gas Valve

    Be sure that gas valve regulator cap is in place and burner box to to the negative side of the manometer, as it will reference atmospheric gas valve pressure reference hose is connected. pressure. Refer to Figure 30 for connection details. Unitary Products Group...
  • Page 23: Gas Valve - Gr Models Only

    The manifold pressure must be taken at the port marked Outlet sooting and eventual clogging of the heat exchanger could occur. Pressure Tap. Be sure that gas valve regulator cap is in place and burner box to gas valve pressure reference hose is connected. Unitary Products Group...
  • Page 24: Reading Gas Pressure

    380 0.0062 658 0.0108 0.19 0.0473 0.11 0.0274 0.18 0.0448 0.1 0.0249 0.3 0.0747 0.17 0.0423 2001 & Above 56.66 & Above 463 0.0076 658 0.0108 0.19 0.0473 0.11 0.0274 0.18 0.0448 0.1 0.0249 0.3 0.0747 0.17 0.0423 Unitary Products Group...
  • Page 25: Field Installed Accessories - Non Electrical

    1BR0221 BOTTOM RETURN FILTER KIT 1-4” FILTER 21” CABINETS 1BR0124 BOTTOM RETURN FILTER KIT 1” FILTER 24-1/2” CABINETS 1BR0224 BOTTOM RETURN FILTER KIT 1-4” FILTER 24-1/2” CABINETS 1HF0801 INTERNAL FILTER KIT WITH 1” FIBER FILTER ALL MODELS Unitary Products Group...
  • Page 26: Blower Performance Cfm - Upflow/Horizontal (Without Filter) - Bottom Return

    1. Airflow expressed in standard cubic feet per minute (CFM) and in cubic meters per minute (m /min). 2. Motor voltage at 115 V. * Input / CFM / Cabinet Width (A=14-1/2, B=17-1/2, C=21, D=24-1/2) † Indicates model available in LoNOx. Unitary Products Group...
  • Page 27: Blower Performance Cfm - Upflow/Horizontal (Without Filter) - Left Side Return

    3. Motor voltage at 115 V. 4. Airflow through motor side return (right side) maybe slightly less than shown above. * Input / CFM / Cabinet Width (A=14-1/2, B=17-1/2, C=21, D=24-1/2) † Indicates model available in LoNOx. Unitary Products Group...
  • Page 28: Wiring Diagram

    SECTION X: WIRING DIAGRAM SECTION X: WIRING DIAGRAM SECTION X: WIRING DIAGRAM SECTION X: WIRING DIAGRAM FIGURE 31: Wiring Diagram Subject to change without notice. Printed in U.S.A. 166753-UIM-C-0706 Copyright © by York International Corp. 2006. All rights reserved. Supersedes: 166753-UIM-B-0306 Unitary 5005 Norman...

This manual is also suitable for:

Gm8s*uhGr8s*uhLy8s*uhLm8s*uhLf8*uh

Table of Contents