Mitsubishi Electric PKA-RP60FAL Service Manual page 29

Split-type, heat pump air conditioners split-type, air conditioners
Hide thumbs Also See for PKA-RP60FAL:
Table of Contents

Advertisement

9-8. FUNCTIONS OF DIP SWITCH AND JUMPER WIRE
Each function is controlled by the dip switch and the jumper wire on control p.c. board.
SW1 and SW2 are equipped only for service parts.
Model setting and capacity setting are memorized in the nonvolatile memory of the control p.c. board of
the unit.
Jumper wire
Functions
Model
SW1
settings
Capacity
SW2
settings
Pair number
setting with
J41
wireless
J42
remote
controller
Unit type
JP1
setting
Indoor
controller
JP3
board type
setting
Setting by the dip switch and jumper wire
For service board
1
2
3
4
5
ON
OFF
Models
Service board
PKA-RP60FAL
1
2
3
PKH-P60FALH
PKA-RP71FAL
1
2
3
PKH-P71FALH
PKA-RP100FAL
1
2
3
PKH-P100FALH
Control PCB setting
Wireless remote
controller setting
J41
0
1
2
3 ~ 9
Model
JP1
Without TH5
With TH5
Indoor controller board type
Factory shipment
Service parts
(Marks in the table below)
4
5
ON
OFF
4
5
ON
OFF
4
5
ON
OFF
<Settings at time of factory shipment>
Wireless remote controller: 0
Control PCB:
J42
Four pair number settings are supported.
The pair number settings of the wireless remote
controller and indoor control PCB (J41/J42) are
given in the table on the left.
(' ' in the table indicates the jumper line is disco-
nnected.)
There is no jumper (JP1) because these models
have the cond./eva. temperature thermistor (TH5).
JP3
29
Jumper wire (
: Short
Remarks
(for both J41 and J42)
: Open)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents