* Can default two telephone no., alarm SMS can be send to two users. * Build GSM mobile modem ( dual band ). * After the SMS command send by mobile phone, the confirm message will be send back to the...
* Intelligent application , innovation, wide range, no limitation. * Full line industrial 4-20 mA transmitters are available from LUTRON : ACV, ACA, DCV, DCA, Hz, WATT, VAR, Power Factor, Humidity, Temperature ( type K, Pt 100 ohm ), Pressure, Vibration, Sound Level, RPM, pH, Conductivity, Dissolved, TDS, ORP, RPM, Air velocity, Light, Clamp current, Load Cell, Potential, Angle, EMF, IR, UV light, Moisture…...
3. SPECIFICATIONS DISPLAY Dot-matrix LCD with back light 16 characters x 2 line. GSM Modem 900/1800 MHz, dual band. Switch inputs Number 8 inputs Reaction 200 mS, min. time Status Default open, Close will alarm Analog input Number 8 channels...
Page 6
Operating 0 to 50 ( 32 to 122 ℃ ℉ Temperature Operating Less than 80% RH. Humidity Power supply DC 9V. Power Less than 400 mA DC. consumption Size 193 x 149 x 46 cm ( 7.6 x 4.9 x 1.8 inch ). Weight 592 g ( 1.3 LB ).
To cancel the PIN code is the necessary procedures, otherwise your GSM system will be not working properly. 3) To guarantee flawless operation of your GSM Control System, ensure that adequate signal strength is permanently to and from your mobile telephone network. Check this with your mobile before installation.
( per 1 second On, 1 second Off ) if the CPU Circuit working properly. 6) GSM indicator ( 4-4, Fig. 1 ) a. If the GSM modem is not connecting the mobile network, the " GSM indicator " will flash per 0.6 second On and 0.6 second Off.
If the GSM modem connect to the mobile network properly, the " GSM indicator " will flash per 0.075 second On and 3 second Off. 0.075 second On 3 seconds Off 7. FUNCTION SETUP 7-1 AD ( 4-20 mA Analog input ) 1)Push the "...
Page 13
* Press " button " ( 4-12, Fig. 1 ) once, LCD will show ▲ CH1 20mA Value CH1 20 mA setting SCREEN xxxx : * Press the buttons ( 4-9, 4-10 , Fig. 1 ) to key in the desired channel 1 20 mA value ( 20 mA = real display value ).
Page 14
* Press " button " once again, LCD will show ▲ CH1 Unit : xxxx CH1 Unit setting SCREEN xx : * Use the buttons ( 4-9, Fig. 1 ) to key in the desired no. of display unit. The " DISPLAY UNIT LIST of ANALOG INPUT ", please refer chapter 12, page 38 For example, 01=C, 94=%RH, 17=dB..
Page 15
* Press " button " once again, display will return to ▲ CH1 4mA Value CH1 4 mA setting SCREEN xxxx : * Use " button " ( 4-13, Fig. 1 ) will move the LCD to ▼ Channel 2, Channel 3..Channel 8 setting SCREEN For example : CH2 4mA Value CH2 4 mA setting SCREEN...
Page 16
CHx Unit : xxxx CH1 Unit setting SCREEN xx : CHA : xxxxxxxx Channel alarm setting SCREEN Enable : CHx 4mA Value CHx 4 mA setting SCREEN xxxx : * In each channel, the procedures that to key in the desired value are same as above page 10, page 11, page 12.
7-2 IO ( Input, Output ) 1)Push the " SETUP Button " once, LCD will show 1:AD 2:IO 3: TEL SETUP SCREEN 4:RP 5:IM 6:SAVE * key in " 2 ", LCD will show :xxxxxxxx RELAY ON/OFF SETTING SCREEN Output : * Use the "...
Page 18
:xxxxxxxx IP ALARM enable/disble SETTING SCREEN Enable : @ It is to set if the input switch alarm enable/disable. 1= alarm enable 0= alarm disable @ For example, setting " Enable : 11100000 " will engage the Switch 1 to Switch 3 to alarm enable, Switch 4 to Switch 8 is alarm disable.
7-3 TEL ( Telephone ) Press the " SETUP Button " once, LCD will return to SETUP SCREEN 1:AD 2:IO 3: TEL SETUP SCREEN 4:RP 5:IM 6:SAVE * key in " 3 ", LCD will show Telephone Num 1 TEL 1 SETTING SCREEN * Use the "...
Page 20
Num1: Supervisor TEL 1 M/S SETTING SCREEN (0):M , (1):S @ Define the first mobile is the Supervisor or Monitor. @ 1 = Supervisor, 0 = Monitor @ Supervisor mobile can control & monitor the system. @ Monitor mobile only can monitor listen the alarm SMS message from the system only.
7-4 RP ( Ring period ) Press the " SETUP Button " once, LCD will show : 1:AD 2:IO 3: TEL SETUP SCREEN 4:RP 5:IM 6:SAVE * key in " 4 ", the screen will show RP old value : xx RP SETTING SCREEN RP new value : @ RP function is to set the duration period of alarm...
7-5 IM ( Switch input management ) Press the " SETUP Button " once, LCD will show : 1:AD 2:IO 3: TEL SETUP SCREEN 4:RP 5:IM 6:SAVE * key in " 5 ", LCD will show Alarm : Close ( Pulse ) IM SETTING SCREEN ( 0): P ,(1): C...
* Press the " Button " will show " Relay8 action " ▲ screen as : Relay8:Action (0):N , (1):Y @ It is to select if the Relay 8 will do action or no. @ Typically always select to 1 ( Yes ). * After finish to set the desired IM function., should press the "...
8. SMS COMMAND from MOBILE SMS CONFIRMATION from SYSTEM ERROR SMS COMMAND ALARM SMS from SYSTEM 8-1 SMS COMMAND from MOBILE SMS CONFIRMATION from SYSTEM There are 6 types of SMS would be send from the mobile are : SET-DOP xxxxxxxx SET-DIP-ALARM xxxxxxxx SET-CH-ALARM xxxxxxxx GET-CH...
Page 25
SET-DOP xxxxxxxx @ x= 1 or 0, 1 = Relay On, 0 = Relay Off @ SMS command from mobile to set the Relays' out to be On or Off @ The relay 8 is the alarm relay. Relay 8 will be On when alarm ( High value alarm.
Page 26
SET-DIP-ALARM xxxxxxxx @ SMS command from mobile to set alarm stattus is enable or disable of the the IP ( Switch input ). @ x = 1, Input switch alarm enable x = 0, Input switch alarm disable @ For example, SET-DIP-ALARM 11000000 The IP1, IP2 will be alarm enable, IP3 to IP8 will be alarm disable After mobile send the SMS ( SET-DIP-alarm xxxxxxxx )
Page 27
SET-CH-ALARM xxxxxxxx @ SMS command from mobile to set Analog ( 4-20 mA Analog input ) alarm status is enable or disable. @ x = 1 Analog alarm enable, x = 0 Analog alarm disable @ For example, SET-CH-ALARM 11000000 The CH1, CH2 will be alarm enable, CH3 to CH8 will be alarm disable After mobile send the SMS ( SET-DIP-alarm xxxxxxxx )
Page 28
GET-CH @ SMS command from mobile to get CH ( Channel, 4-20 mA Analog input ) information. After mobile send the SMS ( GET-CH ) to the system, The mobile will get the confirmation SMS from the system back as : For example : Channel H/L/N status H=Reading on High value...
Page 29
GET-STATE @ SMS command from mobile to get the follwoing information : OP : Relay On/Off IP : Switch input Close/Open CHAM : Channel alarm ( 4-20 mA input alarm ) enable/disable IPAM : Input switch alarm enable/disable After mobile send the SMS ( GET-STATE ) to the system, the mobile will get the SMS confirmation from the system back as : For example :...
Page 30
RESET @ SMS command from mobile to reset the system. @ After mobile send the " RESET " SMS command to the system, the system will not send any SMS confirmation to the mobile, it just to execute the reset function to the system only. 8-2 ERROR SMS COMMAND If the mobile send the wrong or illegal SMS command to the...
Page 31
8-3 ALARM SMS from SYSTEM Ther are two kind alarm ( Analog High/Low alarm, Input switch alarm ) SMS will send out from the system to the mobile if the alarm happned. a. Analog High/Low alarm ( CH ALARM ) The mobile will get the following alarm SMS from the system as example : Channel 1-8 H/L/N status...
Page 32
b. Input switch alarm ( IP ALARM ) The mobile will get the following alarm SMS from the system as example : Switch input 1-8 (1:Close) 2:Open 3:Open Switch 1 and Switch 6 4:Open are Closed 5:Open (6:Close) 7:Open 8:Open @ If the switch has been bracketed, it indicate that this switch alam send already.
9. IMPORTANT OPERATION PROCEDURES & CONSIDERATION 1)If system under normal operation, the LCD display should select to the Regular SCREEN, other wise the system can not accept SMS in or send the SMS out. Push the " SETUP Button " once again, the LCD will change to SETUP SCREEN to Regular SCREEN alternatively.
Page 34
CH8=>xxxxxx xxx Regular SCREEN ( CH8 ) LO:xxxx H:xxxx CH8 Analog input, High/Low/Normal value @ If the CHx => flashed, it indicate that the channel x already send the " Analog alarm " SMS out. CH=>12345678 Regular SCREEN ( Relay On/Off ) OP=>HHHHHHHL H=Relay On, L=Relay Off CH=>12345678...
Page 35
At the beginning, the GSM modem is not connecting the mobile network, the " GSM indicator " ( 4-4, Fig. 1 ) will flash per 0.6 second On and 0.6 second Off. After the GSM modem already connect to the mobile network properly, the "...
Page 36
4) Analog Channel, 4-20 mA input terminals Warning ! The max. input current for the " Analog Channel, 4-20 mA terminals " ( 4-18, Fig. 1 ). is DC 20 mA, do not input the current over the full range. 5) Relay Output terminals Warning ! For the long term operation, for each "...
Page 37
6) LCD Information between GSM modem and the CPU circuit LCD display Right up text Right down text Right up text " 2 " Receive SMS Right down text " 0 " Right up text " 2 " Read SMS Right down text "...
The system may possible not key in the right mobile telephone number? Please check and key in telephone no. again. 3)Power on the system, but the " GSM indicator " is not finished. Corrective action : May the GSM modem is not triggered.
Page 39
Check if the system set the alarm function to disable ? Setting the enable alarm function again. 5)After power On the system, the GSM modem do not connect to the mobile network ( GSM indicator just flash per 0.6 second On and 0.6 second Off ).
Need help?
Do you have a question about the GSM-888 and is the answer not in the manual?
Questions and answers