INSTALLATION
Continued
WARNING: Seal any fresh air vents or ash clean-
out doors located on floor or wall of fireplace. If not,
drafting may cause pilot outage or sooting. Use a
heat-resistant sealant. Do not seal chimney flue
damper.
WARNING: Never install the heater
• in a bedroom or bathroom unless installed as a
vented appliance (Variable Manually-Controlled
Models Only) (see page 10)
• in a recreational vehicle
• where curtains, furniture, clothing, or other flam-
mable objects are less than 42 inches from the
front, top, or sides of the heater
• in high traffic areas
• in windy or drafty areas
CAUTION: This heater creates warm air currents.
These currents move heat to wall surfaces next to
heater. Installing heater next to vinyl or cloth wall
coverings or operating heater where impurities (such
as, but not limited to, tobacco smoke, aromatic
candles, cleaning fluids, oil or kerosene lamps, etc.)
in the air exist, may discolor walls or cause odors.
IMPORTANT: Vent-free heaters add moisture to the air. Although
this is beneficial, installing heater in rooms without enough venti-
lation air may cause mildew to form from too much moisture. See
Air for Combustion and Ventilation, pages 4 through 6.

CHECK GAS TYPE

Use only the correct gas type (natural or propane/LP) for your unit.
If your gas supply is not correct, do not install heater. Call dealer where
you bought heater for proper type heater.
INSTALLATION AND CLEARANCES
(Vent-Free Operation Only)
WARNING: Maintain the minimum clearances. If
you can, provide greater clearances from floor, ceil-
ing, and adjoining wall.
For more information, visit www.desatech.com
For more information, visit www.desatech.com
107068-01E
Installation and Clearances
MINIMUM FIREPLACE
CLEARANCE TO

COMBUSTIBLE MATERIALS

Log Size
18", 24"
LOG SIZING REQUIREMENTS
Minimum Firebox Size
Log
Size Height Depth Width Width*
18"
17"
24"
17"
*Measured at 14" Depth
Carefully follow the instructions below. This will ensure safe
installation into a masonry, UL127-listed manufactured fireplace,
or certified vent-free firebox.
Minimum Clearances For Side Combustible
Material, Side Wall, and Ceiling
A. Clearances from the side of the fireplace cabinet to any com-
bustible material and wall should follow diagram in Figure 8.
Example: The face of a mantel, bookshelf, etc. is made of
combustible material and protrudes 3
combustible material must be 4" from the side of the fireplace
cabinet (see Figure 4).
Note: When installing your gas logs into a manufactured fire-
box, follow firebox manufacturer's instructions for minimum
clearances to combustible materials.
B. Clearances from the top of the fireplace opening to the ceiling
should not be less than 42 inches.
Example
FIREBOX
.5
1
2
*Minimum 16 inches from Side Wall
Figure 4 - Minimum Clearance for Combustible to Wall
INSTALLATION
Check Gas Type
Side Wall
Ceiling
16"
42"
Front
Rear
14"
24"
20"
14"
28"
21"
1
/
" from the wall. This
2
1
12
/
4
1
10
/
2
3
8
/
4
7
1
5
/
4
1
3
/
2
3
1
/
4
7/8
7/16
*
4
6
8 10 12 14 16
INCHES
7 7