Meridian 5.24 Installation & Operating Instructions Manual page 39

Condensing gas – fired wall mounted stainless steel boiler, heating only or with external tank and solar system
Table of Contents

Advertisement

3.3.2 Measurement and adjustment of percentage of CO2 for MERIDIAN 3.15 (valve
system + mixer SIT)
hundreds and thousands and the two small digits on the right 53) indicate the units and
tenths. (see Figure 17).
♦ Place the combustion control sensor Fig 15 gas sampling connection and measure the
percentage of CO
♦ If necessary, adjust the value (see Table 6) by turning the Venturi screw (B) as shown
in Fig. 16 using a 4mm Allen key.
♦ Turn anti-clockwise to increase the percentage of CO2;
♦ Turn clockwise to decrease the percentage of CO2;
The adjustment of the gas valve and consequently of
the CO2 have to execute regulating before maximum
flow and then minimum flow
27
To set the CO
♦ Remove the front cover of the boiler;
♦ Turn the boiler control panel and unscrew the two
side screws that hold it in place.
max
♦ Move the boiler selector
sweep", a function which
the display with a "spanner" symbol and then set the
min
heating potentiometer to maximum.
♦ With the boiler burner on, reset the function
selector.
♦ Display the fan rpm by quickly turning the sanitary
knob. Behind the control panel, use a small slotted
screwdriver to adjust the number of fan rpm on
trimmer P4 as indicated in Table 5 on page 28.
Information appears on the front of the display where
the two large digits on the left 54) indicate the
;
2
B
A
value, do the following:
2
39
to
"Chimney
appears
on