HP COMPACT Sinewave Inverter with integrated Battery Charger and AC Transfer Switch & I PERATION NSTALLATION ANUAL SSC-12-2K5 ODELS SSC-24-4K0 SSC-48-5K0 SSC- TS-01 EMPERATURE SENSOR SSC- REM-01 EMOTE ISPLAY Serial No: _____________________ Model No: ______________________ OLAR NERGY USTRALIA 081 639 938 .
Page 2
ISABLING UNCTIONS AINTENANCE PECIFICATIONS INEWAVE UTPUT (THD) OTAL ARMONIC ISTORTION XTREMELY FFICIENCY ATTERY AVING TANDBY IRCUIT UILT APACITY ATTERY HARGER AC S CTING YNCHRONISED RANSFER WITCH VERLOAD ROTECTED OWER ACTOR ORRECTION Page 2 User Manual HP COMPACT Rev 0803 SSC-1602A...
SSC-REM-01 Any personnel who installs an HP COMPACT and/or works with it must be fully familiar with the contents of this man- ual and must follow exactly all the warnings and safety instructions. Installation of, or any work on the HP COMPACT must be carried out by a qualified and trained personnel.
These measures are put in place to ensure you have years of trouble free service from your Solar Energy Australia inverter. If you have any questions about this warranty please do not hesitate to contact us. LEASE COMPLETE AND RETURN YOUR WARRANTY CARD Page 4 User Manual HP COMPACT Rev 0803 SSC-1602A...
HP Compact Caution: Even when an HP COMPACT has been completely disconnected, there can still be deadly voltages pre- sent at the OUTPUT. To remove these voltages you must switch the COMPACT ON with the ON/OFF switch. Af- ter one minute the electronics are discharged and any work can now be safely carried out.
The Transfer system HP COMPACT can be connected to an AC input source, eg. a stand-by motor generator, AC grid, shore power or a caravan park. With the transfer system, on one side you have AC voltage which is used to run the load, on the other side the batter- ies are being charged.
Page 7
The HP COMPACT can be installed in any desired location but only vertically. Screw the fixing bracket to the wall, and hang the HP Compact onto this bracket, insert two screws at the bottom of the unit. In motor vehicles, the HP COMPACT must be fixed on vibration reducing mounts.
Page 8
AC Output Connecting terminal for AC-output Fuse Fuse Holder for Solar Charge regulator. (optional). Hole Pass through hole for remote display cables. 30A Protection 30A Protection switch for the Transfer system Page 8 User Manual HP COMPACT Rev 0803 SSC-1602A...
Page 9
Pre-installation settings Before you start with the wiring of the HP COMPACT you must set the type of battery. If sealed-gel batteries are used then you must set the small slide-switch ”Equalize“ which is on the front with the connecting terminals, to OFF position. In case of normal lead-acid batter- ies, these can handle a higher equalizing charge, the same slide switch can be set to the ON position.
Page 10
PERATING INAL CHECK ALL WIRING AND CONFIRM CORRECT BATTERY VOLTAGE AND POLARITY Caution: With a wrong battery voltage the COMPACT can be destroyed. ( For example: connecting a SSC-12-2K5 to a 48V Bat- tery). If the COMPACT has been connected with reverse battery polarity, it must be returned to Solar Energy Australia for repair.
Page 11
Displays the value of the output power in % of max MONITOR continuous power (in Inverter Mode) and the charge current in Amps. (in Charger Mode) In this mode the 200% LED indicate that power sharing is in use. Page 11 User Manual HP COMPACT Rev 0803 SSC-1602A...
AC Out LED is lit. If the Standby- Mode is not wanted, turn the “Standby” dial to the left, to the OFF position, this will keep the HP Compact running continuously, but will also discharge your batteries quicker.
Charging Cycle The fully automatic HP COMPACT Battery Charger is adjusted at the factory so that most lead-acid and lead-gel batteries can be charged to the maximum. As soon as the minimum AC voltage (as set with the “Transfer” adjustment dial) is avail- able at the AC input (“AC IN”...
Page 14
The Transfer system When an AC voltage is present at the AC IN of the HP COMPACT, the “AC IN” LED is lit. When this voltage matches the lowest adjusted value set by the “TRANSFER” dial, and the frequency is between 44Hz and 65Hz, then this power is transferred directly to the AC load and the battery charger section of the HP Compact.
Page 15
However, when the HP COMPACT is transferring power supplied from the a grid or a generator the voltage and quality of the power running the AC load will be the same as that coming from the grid or generator. The HP Compact cannot modify the incoming voltage.
Page 16
ISPLAY As an option, a Remote Display can be connected to the HP COMPACT. All operating controls and displays except for level adjustments are available on the Remote Display. The Remote Display is supplied with a 20m long cable. It can be lengthened up to a maximum of 40m.
Page 17
Active in case of fault or manual turn off with the ”OverTemp”, “Overload”, “Batt Low/High” and “OFF” LED Resetting Factory Settings When the HP COMPACT is to be reconnected to a battery or after an interruption (RESET), it will default back to the fac- tory settings..
Page 18
Programming Voltages and timing threshold. When programming your HP Compact, switches and LED’s perform different functions as they do when in the normal mode, the diagrams below shows the function of each when in the programming mode, the normal meanings are in brack- ets.
Page 19
Press the “Select” button until the all 4 Red LED’s are lit, then use the “Change Status” button to select the value you require as indicated on the 5 centre LED’s. Page 19 User Manual HP COMPACT Rev 0803 SSC-1602A...
Page 20
Press the “Select” button until the Red LED next to “Set Equalisation Voltage” is lit, then use the “Change Status” button to select the value you require as indicated on the 5 centre LED’s. Page 20 User Manual HP COMPACT Rev 0803 SSC-1602A...
Page 21
The programming of the Auxiliary Contact is carried out in the following Steps: Press the “Program” button for min. 2 seconds. The “Program” LED is lit to show the HP COMPACT is in program mode. A flashing LED indicates that condition has been programmed to activate the auxiliary contact. The HP Compact is factory programmed with “Over Temp”, “Overload”, “Battery Low High”...
Page 22
To change the type of programming press the “Reset Alarm” button until the LED corresponding to the desired function is lit, in to the table below. After 10 seconds the HP COMPACT will exit the programming mode and function with the new programming.