Electronic Parts Troubleshooting Guide
5. When indoor Fan does not operate
• The pin of Micom, and the part for driving SSR
• Check the pattern
• Check the SSR
- SSR Open: Indoor Fan Motor never operate
- SSR short: Indoor Fan Motor always operates in case of ON or OFF.
56 Free Joint Multi Air Conditioner
Turn off Main power
Check the connection of CN-FAN or CN-MOTOR
Check the Fan Motor
Check the Fuse(AC250V/T2A)
Check the related circuit of indoor Fan Motor.
Turn ON Main Power
Check the SSR high speed operation by remote control.
(The Indoor Fan Motor is connected)
The voltage of PIN NO 1(blue) and 3(yellow) of CN-FAN or CN-MOTOR.
About AC 160V over
SSR is not damaged
About AC 50V over
SSR Check