Note:
If your air condition unit shuts down and the display reads 'HPF' or 'HI PF' it means
there is a high pressure fault in the cooling system. This is usually caused by air being
trapped in the line. There is a bleed valve located under the floor board in the salon that
enables you to bleed the system of any air. Turn off the A/C control, remove the small
square floorboard with the finger hole, remove the dust tray and now remove the larger
floorboard where the dust tray was taken from. Turn on the air condition, while the unit is
running, open the bleed valve and let it run until it coughs out all the air and a steady
stream of water flows. Close the bleed valve and the unit should run properly.
Floor board w/ dust tray
Bleed valve
In the event that a compressor trips out, there is a red reset button located
on each compressor. The compressor pictured below is located in the main
salon. There is another compressor located under the bunk in the aft cabin
just behind the battery switches and a bleed valve under the aft bunk fwd of
the house batteries. Turn off the A/C control, push the reset button on the
compressor, now turn on the air condition.