Do you have a question about the Versapro and is the answer not in the manual?
Questions and answers
Summary of Contents for United Process Versapro
Page 1
Versapro Temperature Controller Installation and Operation Handbook Revision 1.11...
Page 2
United Process Controls Inc. DISCLAIMER: The VersaPro is to be used by the industrial operator under his/her direction. United Process Controls Inc. is not responsible or liable for any product, process, damage or injury incurred while using the VersaPro. United Process Controls Inc. makes no representations or warranties with respect to the contents hereof and specifically disclaim any implied warranties or merchantability or fitness for any particular purpose.
Where it is impractical to do this, use shielded cables with the shield grounded at one end. VersaPro Features The VersaPro is a single loop process controller / monitor has the following capabilities: 24 bit Sigma-Delta ADC for thermocouple with cold junction compensation.
Page 11 Installation The VersaPro instrument is designed for up to 1/8" panel mounting in a DIN standard opening of 3.62" square (adapter panels available by special order). Required rear clearance is 7.5” to allow for wiring. As with all solid state equipment, the controller should be located away from excessive heat, humidity, and vibration.
To mount the instrument in a control panel, a hole must be cut 3.62" square in the necessary location on the panel. The following procedure should be followed to mount the VersaPro in the panel. Insert the unit into previously cut out 3.62" square hole in panel.
VersaPro Temperature Controller Page 13 Process Control Options The Versapro is configured to perform as a single loop PID controller for a specific process. This instrument is setup as an oxygen controller. Table 1 Instrument Control Options Function Description Temperature Uses the temperature signals from a thermocouple to control to temperature setpoint.
ON when the first is control contact is OFF and vice versa. Direct Current Output The Versapro has two analog output channels that provide an isolated 4 to 20mA signal proportional to selectable process values. The analog outputs can be configured to control the process by driving actuators with a 4-20mA signal proportional to the calculated percent output of the PID loop.
Process Alarms The process alarms can be setup to activate either or both of the two alarm contacts provide on the VersaPro. Nine user selectable modes are available. The Full Scale HI, Full Scale LO, Fault, and Probe alarms are available in the monitor.
Page 20 Serial Interface The VersaPro has a single RS-485 half duplex (two wire) communications port. This port can be configured for either the Marathon protocol of Modbus RTU protocol. Baud rates and parities are selectable. The Modbus protocol only uses a parity of none. See the section on communications for details on both of these protocols.
When the controller is set to Automatic mode the “Auto” LED lights and the lower display indicates the process setpoint (default). When the controller is set to Remote mode the “Rem” LED lights and the VersaPro will accept a remote setpoint from a master on the host serial interface. The lower display indicates the process setpoint (default).
Page 23
ENTER key is pressed. A new menu can be select only when the menu heading is displayed. You can exit from the Setup mode by pressing the SETUP key at any time. The following tables outline the Setup menus available in the VersaPro Controller and Monitor when the operator presses the SETUP key.
Pressing the Setup key once at any point in the Setup menu will return the instrument to the normal process display. Dual Key Functions The VersaPro was four dual key functions as defined below: RIGHT arrow / Enter Start probe test sequence...
Page 32 Digital Input Event The VersaPro has a single digital input. This input is activated by making an isolated contact closure between terminals TB-B 11 and 12. This input is debounced for a momentary closure of at least 0.6 seconds.
Page 34 Timer Function The Versapro timer function is available on all process controller options. The timer can operate independently or it can be dependent on the process based on how either alarm contact is configured. The instrument has three possible functions; timer, guaranteed start timer, and guaranteed soak timer. These functions are set through the mode selection of alarm 1 or alarm 2 in the Setup menu.
Page 37
Alarm Contact = OFF Rem Light = Flash Figure 8 Versapro Timer State Diagram The timer has four states. The IDLE state is the inactive condition. The RUN state is the active state when the timer is counting down. The HOLD state is when counting is paused due to either Digital Event = HOLD or a configured alarm is active.
Timer SIO Operations The Versapro allocates a second host address if the timer function is enabled and the host port protocol is set to PRoP (Marathon) using the Marathon slave protocol. If the host port protocol is set to buss (Modbus) or the Marathon block protocol is used, then the timer information is accessed directly.
The input event configuration is in the lower byte of this word. Any configuration of the input event must be added to the timer function values when this word is written to the Versapro. In this example the event configuration is set to none (0).
(Rate) The Versapro uses the Proportional Band as a representation of the Proportion section of PID, the Reset as a representation of the Integral section of PID, and the Rate as a representation of the Derivative section of PID.
53.2mV. The process display can be configured to display either 100 or 100.0. This process value can then be retransmitted to other control devices are a recorder. The control model of the Versapro will be able to control to a setpoint for the new process value.
DACV1 or DACV2 registers. Calibration There are two analog inputs, a cold junction compensation sensor, and two analog outputs on the VersaPro. The input level is determined by which terminals are used for the input signal. There are two pairs of input terminals: TB-B 1, 2 for the thermocouple (T/C) input and TB-B 3, 4 for the probe millivolt input.
Change the copper wire with the correct thermocouple extension wire 2. Set the calibrator to a typical temperature level. 3. Use the Versapro Enter key to advance to the CJ Adjustment display. 4. Using the arrow keys, adjust the displayed value to equal the calibrator input.
Each device is assigned an address to distinguish it from all other connected devices. The VersaPro recognizes three Modbus RTU (Remote Terminal Unit) commands. These are: read single I registers (command 4), read a single H register (command 3), and preset a single H register (command 6) In the RTU protocol sends data in 8-bit binary characters.
PLC on the MODBUS industrial communications system. Command codes were established to manipulate PLC registers and coils. As far as the VersaPro is concerned, they are all just memory locations, but the response to each command is consistent with Modbus specifications.
‘U’ block protocol. The following command set applies to the ‘A’ command and is used for the Versapro and other 10PRO type instruments such as temperature controller slaves. The command set is sent by a master to a 10PRO slave instrument.
11 blocks or more. The Versapro, 10Pro-E, and Version 3.5 Carbpro have only table 0. The table value is assumed to be 0 and the parameter is addressed directly with the possible range of 0 to 71. These number correspond with the decimal numbers in the Versapro Memory Map table.
Block Commands Block transfer commands are used to read and write data in a group of 24 words. The Versapro has only three blocks in table zero. The block transfer command has to identify the table as well as the block.
Page 55
(bb) Block number (HEX) (tt) Table number (HEX) (*) Block Read command character (I) Instruement Prefix: U = Versapro instrument prefix. (A) Address of instrument. Figure 11 Block Read Response Format The following is an example is for a block request from the Host and a reply from the instrument. The Host sends the command: 1U*0000<00>N<04><06>...
MSI Error Codes The Marathon protocol for the Versapro has three error codes that can be generated by the instrument: E1 = Incorrect LRC detected on received message, E2 = Invalid command detected, and E3 = Invalid table or parameter address.
How come I have communications problems with an instrument address following a Versapro address setting. If the timer function has been enabled and the Versapro host protocol is set to ‘Prop’ for the Marathon protocol, the instrument will take the next host address setting to respond with the timer parameters. The problem can be corrected by turning of the timer function in the Control menu or setting to next instrument address to Versapro host address + 2.
EEPROM values. These parameters will include the thermocouple type, alarm functions, and probe care settings. For the controller version of the Versapro this will also include control and PID settings as well. Note the instrument calibration settings for the two analog output channels by going into the SETUP mode, selecting CAL OUT –...
"MONITOR MODE”, (about 5 seconds). The instrument will send a prompt to the HyperTerminal screen that should look like figure 1. If the Versapro is already in Monitor Mode it may only have the Power light on with no other display. Cycle power on the instrument while connected to see the “Marathon Monitors, Inc.”...
Exits Monitor mode Resets processor idle counter The Versapro is placed into Monitor mode when the <Enter> and <Rem> keys on the instrument are pressed simultaneously and held for about 5 seconds. The LCD display will display the prompt ‘MONITOR MODE’ and the LED display will be blank.
Page 79
VersaPro Temperature Controller Page 79 Reach us at www.group-upc.com United Process Controls brings together leading brands to the heat treating industry including Waukee Engineering, Furnace Control, Marathon Monitors and Process-Electronic. We provide prime control solutions through our worldwide sales and services network with easy-to- access local support.
Need help?
Do you have a question about the Versapro and is the answer not in the manual?
Questions and answers