Mini Triple IR (IR3) Flame Detector Model 20/20MI User and Maintenance Manual TM 787100, Rev. D April 2011 ATEX (Cenelec) Approved Ex II 1 GD, EEx ia IIC T5 (+65ºC), T4 (+85ºC) 218 Little Falls Rd., Cedar Grove, NJ 07009 USA;...
Page 3
The SharpEye Optical Flame Detector described in this document is the property of Spectrex, Inc. No part of the hardware, software or documentation may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language or computer language, in any form or by any means, without prior written permission of Spectrex, Inc.
4.3.3. Detector Default Set Up ..............18 4.4 B .....................18 UILT 4.4.1. General ....................18 4.4.2. Principles ...................19 4.4.3. Automatic & Manual BIT ..............19 4.4.4. Manual BIT only.................19 5.Technical Specifications ................ 20 5.1 E ...............20 LECTRICAL PECIFICATIONS 5.2 M ..............21 ECHANICAL PECIFICATIONS 5.3 E...
Page 6
ONLY WHEN OPTIONAL LATCHING ALARM HAS BEEN SELECTED 7.4 F ...................31 UNCTIONAL TESTING 7.4.1 Manual BIT Test .................32 7.4.2 Testing with Fire Simulator Model 20/20-310 (see Appendix B) ..32 7.5 S .................33 AFETY RECAUTIONS 8. Maintenance Instructions ..............34 8.1 S ......................34...
Page 7
Figure 12: 4-20mA Wiring (Source Option)..............40 Figure 13: Typical Wiring For 4 Wire Controllers ............41 Figure 14: 4-20 mA (sink) connection for Intrinsically Safe installation......44 Figure 15: RS-485 connection for Intrinsically Safe installation........45 Figure 16: Fire Simulator....................46 Figure 17: Mini IR3 Detector Target Point..............
Page 8
Spectrex Inc. - SharpEye Mini IR3 Flame Detector Manual – TM 787100, Rev. D April 2011...
Manual – TM 787100, Rev. D April 2011 1. Scope 1.1 Product Overview The Spectrex Model 20/20MI is a new version of the triple IR spectrum flame detector designed to provide maximum fire protection. It uses innovative technology of advanced digital signal processing to analyze the dynamic characteristics of fire.
Maintenance Instructions and support procedures. Appendix A. Typical Wiring Configurations - wiring diagrams for installation. Appendix B. Intrinsically Safe Wiring Configurations For 20/20MI-XX-X-C Appendix C. Long Range IR3 Fire Simulator Appendix D. FM Report for 20/20 MI-3 Appendix E. Ordering information...
Spectrex Inc. - SharpEye Mini IR3 Flame Detector Manual – TM 787100, Rev. D April 2011 2. Technical Description • Detection Range: up to 132 ft (40m) for a 1 ft (0.1m ) fire. • Ultra High Immunity to False Alarms (see section. 3.3).
2.1.5 Modbus RS-485 For more advanced communication 20/20MI has a RS 485 modbus Compatible output that provides Data communication from a network (up to 247 detectors) to a host computer on universal controller for central monitoring.
C - ATEX certified Per EX II 1GD, EEx ia IIC T4 or T5 (this model is available with 4-20mA and RS-485 outputs only) F- FM – functional test only - model 20/20 MI-3. * Cable for connection to junction box...
The detection distance, for the WARNING level, is approximately 10% higher than the ALARM distance. Alarm response times for a “standard fire” at a specified range are shown hereunder. Table 1: Alarm Response Time Versus Range – 20/20MI-1 Sensitivity Range – ft (m) 33 (10) 65 (20)
Spectrex Inc. - SharpEye Mini IR3 Flame Detector Manual – TM 787100, Rev. D April 2011 Other fuels The detector will react to other types of fires as follows: Pan Fire Size: 1ft (0.1m Maximum Wind Speed: 6.5 ft/sec (2 m/sec)
Spectrex Inc. - SharpEye Mini IR3 Flame Detector Manual – TM 787100, Rev. D April 2011 3.2 Cone Of Vision Horizontal: 100° Vertical: 100° Figure 4: Horizontal and Vertical Fields of View...
Incandescent frosted glass light, 100 W Incandescent clear glass light, rough service, 100 W Fluorescent light with white enamel reflector, standard office or shop, 40 W (or two 20 W) Electric arc [12mm (15/32 in) gap at 4000 V alternating current, 60 Hz] Arc welding [4 mm (5/32 in) rod;...
Spectrex Inc. - SharpEye Mini IR3 Flame Detector Manual – TM 787100, Rev. D April 2011 Table 6: Welding Immunity Distance – 20/20MI-1 Sensitivity Detection Range Immunity Distance 33 ft (10m) >10 ft (3m) 65 ft (20m) >15 ft (5m) 100 ft (30m) >20 ft (7m)
Spectrex Inc. - SharpEye Mini IR3 Flame Detector Manual – TM 787100, Rev. D April 2011 4. Operation 4.1 Visual Indications One 3-color LED-indication is located in the detector front window: Detector Status LED color LED mode Fault, BIT Fault...
The detector controls the following outputs: • Alarm relay (this output is not available in the ATEX certified model 20/20MI-XX-X-C) • Fault relay (this output is not available in the ATEX certified model 20/20MI- XX-X-C) • 4-20mA current output • RS-485 communication The detector can be in one of the following states.
4.3 Detector Mode Setup 4.3.1 Detector setting See Section 4.3.3 for default factory settings The 20/20 MI incorporates several functions that can be set by the customer using: Spectrex Host software, which will be supplied for each detector shipment, refer to manual TM 784050 for programming instructions. The Host software enables you to change functions as described in 4.3.2.
The Time delay for fire alarm in this mode is from 2.5 to 15 seconds (mostly less than 10 seconds). Table 10: Time Delay Delay (seconds) *A – anti-flare * Default Note: The FM approval does not allow use of 20, and 30 second setting delay...
Spectrex Inc. - SharpEye Mini IR3 Flame Detector Manual – TM 787100, Rev. D April 2011 c. Function Setup The user can select the desired mode of operation by means of host. Table 11: Function Setup Name Alarm Latch Alarm latching enable...
• FAULT relay remains CLOSED. • ALARM relay is activated for 3 sec (only when Function Alarm BIT at YES) • 4-20 mA OUTPUT current will be 15mA (only when Function Alarm BIT at YES). • The LED will illuminate at red for 3 sec.
The contact will be open at Fault condition or low voltage. • The relay outputs are not available in the intrinsically safe model 20/20MI-XX-X-C. • 4-20mA Current Output: The 4-20mA is isolated sink option. The maximum permitted load resistor is 600Ohm.
EEx ia IIC T4 (Ta = -40ºC to +85ºC) EEx ia IIC T5 (Ta = -40ºC to +60ºC) C. Functional Test FM functional test Per 3620 for 20/20 MI-3 and 20/20MI-1 D. Water and dust tight NEMA 250 type 6p. IP 66 and IP 67 per EN 60529 E.
6. Installation Instructions 6.1 Scope The SharpEye Model 20/20MI is a self-contained Optical Flame Detector designed to operate as a stand-alone unit directly connected to alarm systems or automatic fire extinguishing systems. The detector can be a part of a more complex system where many detectors and other devices are integrated through a common control unit.
4 For wiring, use color-coded conductors or suitable wire markings or labels. 12 to 20 AWG (0.5 mm² to 3.5 mm²) wires may be used for site wiring. The selection of wire gauge should be based on the number of detectors used on the same line and the distance from the control unit, in compliance with specifications.
Manual – TM 787100, Rev. D April 2011 6.4 Certification Instructions This section refers only for intrinsically safe installation on model 20/20MI-XX-X-C. The following instructions apply to equipment covered by certificate numbers Sira 04 ATEX 2010 and Sira 04 ATEX 2011X:...
Spectrex Inc. - SharpEye Mini IR3 Flame Detector Manual – TM 787100, Rev. D April 2011 6.5 Conduit Installation The detector can be mounted directly on the wall through 7-mm hole (item 7, Fig. 6) or preferably with the optional Tilt Mount, Model 787640 (item 1, Fig. 6).
PIN No. 6 or light blue wire The contact is normally energised closed when the detector is in its normal operational condition. This output is not available in the intrinsically safe model 20/20MI-XX-X-C. Alarm Relay The Alarm output is a N.O. SPST contact relay.
Alarm Delay: An Alarm Delay may be required for certain applications. The detector has an Alarm Delay that permits time delays from 0, anti-flare, 3, 5, 10, 15, 20 and 30 seconds respectively. The delay can be defined by the RS-485.
Spectrex Inc. - SharpEye Mini IR3 Flame Detector Manual – TM 787100, Rev. D April 2011 7. Operating Instructions 7.1 Scope The following instructions are designed to obtain optimal performance from the detector over its life cycle. 7.2 Power-Up 1 Apply power and wait approximately 60 seconds for the automatic self-test of the detector.
The LED flash (1 Hz) at green. If the detector is on, skip this step. Aim the Spectrex Fire Simulator Model 20/20-310 at the target point of the detector (see Fig. 15), in a way that the radiation emitted by it is facing directly towards the detector.
Spectrex Inc. - SharpEye Mini IR3 Flame Detector Manual – TM 787100, Rev. D April 2011 7.5 Safety Precautions After Powering-up, the detector requires hardly any attention in order to function properly, but the following should be noted: 1 Follow the instructions in the manual and refer to the drawings and specifications issued by the manufacturer.
Spectrex Inc. - SharpEye Mini IR3 Flame Detector Manual – TM 787100, Rev. D April 2011 8. Maintenance Instructions 8.1 Scope This Section deals with preventive maintenance, describes possible faults in detector operation and indicates corrective measures. Ignoring these instructions may cause problems with the detector and may invalidate the warranty.
Spectrex Inc. - SharpEye Mini IR3 Flame Detector Manual – TM 787100, Rev. D April 2011 unit is sent to the manufacturer or distributor for service, a copy of the Maintenance records should accompany it. 8.6 Troubleshooting 8.6.1 Fault Indication 1 Check power supply for correct voltage, polarity and wiring.
Page 44
Spectrex Inc. - SharpEye Mini IR3 Flame Detector Manual – TM 787100, Rev. D April 2011...
Manual – TM 787100, Rev. D April 2011 Appendix A: Typical Wiring Configurations Important Note See Appendix B for Wiring for Intrinsically Safe installation Figure 8: Connector Interface Option Note In the intrinsically safe model 20/20MI-XX-X-C PINs 5,6,7,8 are not connected...
Spectrex Inc. - SharpEye Mini IR3 Flame Detector Manual – TM 787100, Rev. D April 2011 Figure 9: Cable Interface Option Note In the intrinsically safe model 20/20MI-XX-X-C wires brown, light blue, orange, violet are not connected...
Spectrex Inc. - SharpEye Mini IR3 Flame Detector Manual – TM 787100, Rev. D April 2011 RS-485 Communication Network Using the RS-485 network capability of the IR3 detector and control software, it is possible to connect up to 32 detectors in an addressable system with 4 wires only (2 for power and 2 for communication).
Spectrex Inc. - SharpEye Mini IR3 Flame Detector Manual – TM 787100, Rev. D April 2011 Figure 11: 4-20mA Wiring (Sink Option) Figure 12: 4-20mA Wiring (Source Option) Notes: The detectors are factory set to isolated 4-20mA-sink version. To work at non-isolated 4-20mA source version, connect PIN 3 or blue wire to PIN 1 or red wire.
Manual – TM 787100, Rev. D April 2011 Figure 13: Typical Wiring For 4 Wire Controllers Notes: In the intrinsically safe model 20/20MI-XX-X-C this wiring configuration is not relevant For EOL resistor value see Controller Manual The color wire refers to the color of the cable output option. The PIN No.
Page 50
Spectrex Inc. - SharpEye Mini IR3 Flame Detector Manual – TM 787100, Rev. D April 2011...
Appendix B: Intrinsically Safe Connection For 20/20MI-XX-X-C The 20/20MI-XX-X-C is intrinsically safe certified per ATEX Ex II 1GD, EEx ia IIC T4. This model does not include the relay outputs. In order to comply with the intrinsic safety requirements, barriers/ galvanic isolators must be incorporated.
Spectrex Inc. - SharpEye Mini IR3 Flame Detector Manual – TM 787100, Rev. D April 2011 Figure 14: 4-20 mA (sink) connection for Intrinsically Safe installation...
Spectrex Inc. - SharpEye Mini IR3 Flame Detector Manual – TM 787100, Rev. D April 2011 Figure 15: RS-485 connection for Intrinsically Safe installation...
Product Description The SharpEye IR3 Long Range Fire simulator 20/20-310 is designed specifically for use with SharpEye IR3 flame detectors. The Fire Simulator emits IR radiation in a unique sequential pattern corresponding to and recognizable by the IR3 detector as fire. This allows the IR3 detectors to be tested under simulated fire conditions without the associated risks of an open flame.
Follow these instructions to simulate a fire: 1. Aim the Fire Simulator towards the detector’s “Target Point”. 2. For testing keep a distance of at least 50cm (20 inches) from the detector. 3. Press the operation button once. Fire simulation will last for 20 seconds.
Page 56
6 x Rechargeable 1.2 VDC NiCad Batteries Current: 2.5A Avg. Charge: 400mA for 14 Hours Environmental Temperature Range: -4º F (-20º C) to 122º F (50º C) Vibration Protection: 1g (10-50hz) Water and Dust: IP 67 per EN 60529 Physical Dimension: 11.5 x 10.1 x 3.9 in (292 x 258 x 100 mm)
Baseline Sensitivity Test All four samples of the 20/20MI-3 – flame detector were subjected to a small-scale sensitivity test consisting of a 1.75 in. (4.5 cm.) diameter fire of n-Heptane at a distance of 3 ft.
Page 58
Field of View Test One sample of the Model 20/20 MI-1, which has an identical enclosure to the 20/20 MI-3 and is considered representative of the series, was exposed to the 12 in. x 12 in. (0.3 m. x 0.3 m.) N-heptane pan fire during which time the viewing angle was varied +/-50º...
Page 59
Manual – TM 787100, Rev. D April 2011 False Stimuli Response Test All four samples of the Model 20/20 MI-1with sensitivity setting 10, considered representative of the series, were tested in the presence of modulated and non- modulated artificial sources of light and other heated bodies, then, in the presence of each of the false stimuli, were exposed to the standard test consisting of a 12 in.
Page 60
Spectrex Inc. - SharpEye Mini IR3 Flame Detector Manual – TM 787100, Rev. D April 2011...
Spectrex Inc. - SharpEye Mini IR3 Flame Detector Manual – TM 787100, Rev. D April 2011 Appendix E: Ordering Information Please define the requested model according to 1.1.5 by filling in the appropriate squares below. The detector default set up:...
Page 62
Company Position Billing Address Address City State Country Shipping Address Address City State Country Phone Country Code Area Code Number Country Code Area Code Number E-mail For additional information about ordering 20/20MI, please call Spectrex Inc. at: +1 (973) 239-8398.
Spectrex Inc. - SharpEye Mini IR3 Flame Detector Manual – TM 787100, Rev. D April 2011 Technical Support For all technical assistance or support, contact: 218 Little Falls Road Cedar Grove, NJ 07009, USA Tel: +1 (973) 239 8398 Fax: +1 (973) 239 7614 Email: Spectrex@spectrex.net...