INSTALLATION: CLEARANCES
The Indoor boiler must be installed with these minimum clearances from NON-COMBUSTIBLE surface:
Front = 30"/ Back = 30" / Sides = 12"
The Indoor boiler must be installed with these minimum clearances from any COMBUSTIBLE surface:
Front = 48"/ Back = 30" / Smoke pipe / Sides = 18"
Recommended maintenance clearances = 18"
Back 30 / one side 36

CONTENTS

– INDOOR MODELS
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE
SERVING ANOTHER APPLIANCE.
CHIMNEY TYPE: CLASS "A" ALL FUEL CHIMNEY 8" DIAMETER
CLEARANCES:
FLOOR PROTECTION: FOR INSTALLATION ON NON-COMBUSTIBLE FLOOR ONLY.
MAXIMUM DRAFT: 0.06 IN WATER COLUMN.
ELECTRICAL RATING: 120 V., 0.5 AMP, 60 HZ.
OPERATION/MAINTENANCE
FUEL: BURN SOLID WOOD OR COAL ONLY. LOAD FUEL CAREFULLY OR DAMAGE
MAY RESULT. DO NOT STORE FUEL OR COMBUSTIBLES NEAR UNIT.
DO NOT USE CHEMICALS OR FLUIDS TO START FIRE, DO NOT BURN GARBAGE,
GASOLINE, NAPTHA OR ENGINE OIL. FOR SAFETY, KEEP FUEL AND ASH DOORS
TIGHTLY CLOSED. CLEAN HEAT EXCHANGER. FUEL PIPE AND CHIMNEY
FREQUENTLY TO PREVENT ACCUMULATION OF SOOT. THE APPLIANCE AND
FLUE PIPE MUST BE IN GOOD CONDITION. IN THE EVENT OF A RUN-AWAY FIRE,
STOP SUPPLY OF COMBUSTION AIR TO FIRE. SECURE FUEL AND ASH DOORS.
REFER TO OWNER'S MANUAL.
DO NOT OPERATE DURING POWER FAILURE.
September 2012
UNIT TO BACKWALL
30"
UNIT TO SIDEWALL
18"
FLUE TO BACKWALL
18"
FLUE TO SIDEWALL
30'