Display Features; User Interface - Greenheck Vari-Green Control 475573 Installation, Operation And Maintenance Manual

Indoor air quality–temp/humidity
Table of Contents

Advertisement

Wiring
All wiring for the Greenheck Temperature and
Humidity Controller is Class II low-voltage control
wiring. See the Wiring Diagram on Page 7 for the
wiring overview.
Control box to factory mounted
transformer control input.
Controller
Terminal
J15-FAN
J15-GND
J15-24V
Optional Remote Override
Connect a normally-open switch between terminals
J17-OVR and J15-GND on the controller. Closing
this switch will activate the remote override feature.
Opening the switch will de-activate the override.
Optional Output Reference
A 0 to 10VDC signal is available from J15-REF to
J15-GND. The signal is 15° to 130° F (-10° to 55°C)
or 0 to 100% Relative Humidity depending on the
value of parameter P10 (see pg 6).

User Interface

A scroll button protrudes through the case. The
programming switches and programming jumper are
inside the case.
4
Transformer
Control Terminal
0 to 10V
COM
24V
Scroll
Button
Programming
Switches
Programming
Jumper in
RUN Mode
Main Display 0.76
inch 4-digit Numeric
Dot

Display Features

The minor display is used to describe the units
displayed and the main display shows the numeric
value. The fan icon is illuminated whenever the fan
output voltage is at or above the minimum specified
in parameter P8, Minimum % Fan Speed. The Cool
and Heat Icons are illuminated in each control mode
respectively. The dot in the lower left is used to
signal fan cut-out mode.
Normal Operation (J19 = RUN)
The Greenheck Indoor Air Quality – Temperature/
Humidity Controller ships with the following factory
setting: Cooling Control, Temperature Setpoint 72°F,
Fan Control output at 2 to 10 Volts and Cut-Out
Disabled. Pressing the scroll button at any time
shows the Temperature setpoint, a second push
shows the fan speed in percent.
The scroll button will change the display momentarily
to view other information such as setpoints and fan
speed. These are for reference only, and cannot
be adjusted. The exact sequence will depend on
the settings of parameters P0, P1, P2 and P4. For
examples, see the two figures below.
Scroll Button
Sequence,
Temperature
Control
Cooling Mode,
Scroll Button Sequence,
°F Temperature
Temperature & Humidity Control
and Display in
Cooling Mode, °F Temperature
run.
and Display in run.
Minor Display
0.34 inch 3-digit
Alpha-Numeric
Heat Control
Icon
Cool Control
Icon
Fan ON Icon