INSTALLATION Transformer Inputs: TO OPEN COVER TO OPEN LAMP ================= BLACK - 120V WHITE - Common RED - 277V IMPORTANT NOTE: REMOVE THE INPUT POWER IMMEDIATELY IF ALL RED LED’S ON THE OP-PANEL FLASH: This indicates that the input power is incorrectly wired, and needs to be corrected.
Normal Power-Up Sequence APPLY INPUT IMPORTANT NOTE: POWER REMOVE THE INPUT POWER IMMEDIATELY IF ALL RED LED’S ON ~0/sec THE OP-PANEL FLASH. This indicates that the input power is incorrectly wired, and needs to be corrected. IF 277 is applied to the 120 tap for more than 7/sec, then the fusable-link may open requiring the transformer ARE ALL to be replaced.
NORMAL OPERATION / MANUAL TESTS OP-PANEL INDICATORS / OPERATION: GREEN - Status: Solid indicates system normal and charging current from the input source is available. NOTE: To reset/cancel a test, simply press the button once during any test. 1 Press: performs a 5/sec brief test, all lamps operating from battery only. 2 Presses: performs a 1/min test, all lamps operating from battery only.