Eco Air EAP-10.5XS Installation And Operating Instructions Manual

Air to water heat pump

Advertisement

Quick Links

INSTALLATION/OPERATING/ MAINTENANCE
INSTRUCTIONS
Air to Water Heat Pump
EAP-10.5XS EAP-13XS EAP-18DS
www.ecoairpump.co.uk
Support Line: 08444 930099
Email: Info@ecoairpump.co.uk
Air Source Heat Pump EAP range user manual - www.ecoairpump.co.uk

Advertisement

Table of Contents
loading

Summary of Contents for Eco Air EAP-10.5XS

  • Page 1 INSTALLATION/OPERATING/ MAINTENANCE INSTRUCTIONS Air to Water Heat Pump EAP-10.5XS EAP-13XS EAP-18DS www.ecoairpump.co.uk Support Line: 08444 930099 Email: Info@ecoairpump.co.uk Air Source Heat Pump EAP range user manual - www.ecoairpump.co.uk...
  • Page 2: Read Immediately

    1. READ IMMEDIATELY 1.1. Important Information Prior to opening the unit it must be ensured that all electrical circuits are disconnected from the power supply. During transport, the heat pump must not be tilted more than 45 (in either direction). The intake and outlet openings must not be restricted nor obstructed.
  • Page 3: Scope Of Delivery

    the air outlet, depending on the weather. 3. SCOPE OF DELIVERY 3.1. Baseline Unit The heat pump is delivered as a compact unit containing the components listed below. Copeland Scroll Compressor Condenser ( 316 stainless steel brazed plate heat exchanger) Evaporator Alco Expansion Valve Accumulator...
  • Page 4: Cleaning & Care

    6.1. General Information The following connections need to be made on the heat pump: - supply/return lines of the heating system - condensate drain - control lead to the heat pump controller - power supply 6.2. Heating-Side Connection The connections on the heating side of the heat pump are provided with 1"external thread. The hoses to be connected exit the unit through its side plate.
  • Page 5: Cleaning Of Heating Side

    Do not use any cleaning agents containing sand, soda, acid or chloride as these may damage the surface. To prevent malfunctions in the heat exchanger of the heat pump caused by dirt deposits, care must be taken that the heat exchanger in the heating installation cannot become contaminated.
  • Page 6 Evaporator Coil Temperature 1 1) The evaporator coil temperature sensor replace the sensor Sensor 1 is damaged Malfunction Evaporator Coil Temperature 2 1) The evaporator coil temperature sensor replace the sensor Sensor 2 is damaged Malfunction 1) Loop wire terminals 1 and 2 (no matter whether water flow switch is installed) to Replace mainboard see if E6 still shows up.
  • Page 7 Vaccumize the system and fill the gas. B. if the readings are above 0.9Mpa, 2) The low pressure switch is damaged probably the 0.02~10.15Mpa low pressure switch is defected. Replace the switch. 1) Defrost cut-in temperature is set Set the defrost cut-in temperature as incorrectly.
  • Page 8: Dimensioned Drawings

    Check what kind of protection it is and 7) The system is in protection. remedy it. 8) Damaged mainboard or damaged Replace the mainboard or sensor temperature sensor. 10. DIMENSIONED DRAWINGS 10.1. Dimensioned Drawing .. EAP-10.5XS EAP-13XS Air Source Heat Pump EAP range user manual - www.ecoairpump.co.uk...
  • Page 9: Equipment Data

    11. EQUIPMENT DATA Model EAP10.5-XS EAP-13XP EAP-18DS Outlet Water Rated Temp.(℃ ) Outlet Water Max. Temp(℃ ) Heating Capacity 10.3 11.9 18.5 (KW) A7/W35 EN14511 Heating Capacity 10.3 15.9 (KW) A2/W35 EN14511 Heating Capacity 13.6 (KW) A-2/W35 EN14511 Heating Capacity 12.2 (KW) A-7/W35 EN14511...
  • Page 10: Wiring Diagrams

    12. WIRING DIAGRAMS Air Source Heat Pump EAP range user manual - www.ecoairpump.co.uk...
  • Page 11 13. Schematics of Installation 13.1. Schematics of Space Heating Air Source Heat Pump EAP range user manual - www.ecoairpump.co.uk...
  • Page 12 13.2. Schematics of Space Heating/Hot Water Heating Air Source Heat Pump EAP range user manual - www.ecoairpump.co.uk...
  • Page 13 14. Controller Controller type: 15 This controller is applicable to both single compressor and dual compressors units. This controller includes three parts: mainboard, control panel and connecting wires. 14.1. Mainboard Layout Air Source Heat Pump EAP range user manual - www.ecoairpump.co.uk...
  • Page 14: Jumper Settings

    COMP1: Compressor 1 COMP2: Compressor 2 4WV1: 4-way Reversing Valve 1 4WV2: 4-way Reversing Valve 2 FAN1: Fan Motor, Low Speed FAN2: Fan Motor, High Speed PUMP: Water Pump HOT: Backup Electricity Heater A-HOT: Crankcase Heater P-W: Solenoid for Hot Water S-F: Solenoid for Defrost Heating Cable ERR:...
  • Page 15: Control Panel

    Jumpers 5, 6,7 and 8 are used to set Duty/Assist Unit No. Unit No. 1 ( Duty) No. 2 (Assist) No. 3 (Assist) No. 4 (Assist) No. 5 (Assist) No. 6 (Assist) No. 7 (Assist) No. 8 (Assist) No. 9 (Assist) No.
  • Page 16 Heating Mode: the unit will heat the water till the water temperature reached the set point. Auto Mode: the unit will cool the water till the water temperature reaches the set point, and automatically heat the water till the water temperature reaches the set point. Note: Hot water heating mode can only be activated in parameter setting.
  • Page 17: Screen Symbols

    14.4. Running Parameter Checkup Duty Unit Item Parameter Name Unit ℃ Inlet Water Temp ℃ Outlet Water Temp ℃ Ambient Air Temp ℃ Evaporator Coil Temp 1 ℃ Evaporator Coil Temp 2 ℃ Hot Water Temp ℃ Discharge Gas Temp Compressor 1 ℃...
  • Page 18 Item Parameter Name Unit Default Remarks ℃ Hot Water Temp Only valid when P25 value is set as 1. Defrost Cut-in Time Defrost Cut-out Time ℃ Defrost Cut-in Temp ℃ Defrost Cut-out Temp Defrost Heating Cable Cut-in Only valid when defrost heating cable ℃...
  • Page 19 Water Temperature In Cooling Switch on the control panel and then ℃ Mode press Up or Down button to change Water Temperature In Heating the set water temperature in cooling, ℃ Mode heating and auto mode. The range of Water Temperature in Auto water temperatures is different in ℃...
  • Page 20: Function Description

    15. Function Description 15.1. Automatic Mode The unit will select heating or cooling mode automatically depending on the current inlet water temperature. When Ti ≥ Ts + P15, the unit enters cooling mode; When Ti ≤Ts – P16, the unit enters heating mode; Where Ti is inlet water temperature read by CN3, Ts is the set water temperature, P15 is the parameter value set in P15, and P16 is the parameter value set in P16.
  • Page 21 The fan motor has three speeds, with low speed in yellow color, medium speed in blue color and high speed in black color. A factory set unit has blue wire connected to FAN1 and black wire connected to FAN2. It is not recommended to change high speed to low speed manually because insufficient air volume in low air temperatures could damage the unit.
  • Page 22 Set Jumpers No. 5 to No. 8 on the mainboard of each unit accordingly. Connect the unit one by one through CN12. Ambient Coefficient Compensation Set Water Temperature Temperature (Ta) (P21) Temperature (P20) =P20+P21*0.1*(P20-Ta) Air Source Heat Pump EAP range user manual - www.ecoairpump.co.uk...
  • Page 23: Unit Protection

    Auto Set Water Temp Table Coefficient Compensation Temp (deg C) Auto Set Water Temp ( deg Ambient Temp ( deg C) Weather compensation settings will only be valid in heating mode and will not affect the manually set water temperature in hot water heating mode and cooling mode.
  • Page 24 outputs. Note: Water Pump control in antifreeze protection will never be blocked. 16.6. Insufficient Water Flow Protection All outputs will be closed if water flow is insufficient or the water flow switch is malfunctioning. System uses two approaches to check whether the water flow is insufficient. Water Flow Switch System will check the state of Water Flow Switch one minute after the water pump is on.
  • Page 25 Shutdown Compressor Compressor 2 Overload Turn backup Winter Anti Freeze electricity heating Protection element heating mode Shutdown Compressor Outlet Water Temp Too and Backup Electricity High in Heating Heater Turn compressor, Outlet Water Temp Too turn pump Low in Cooling backup electricity heater Discharge Temp...