15.2 Burner Compartment

The burner compartment is
a sealed compartment.
Following any work,
re-seal the compartment
with the gas pipe rubber
seal fully in place and all
screws fitted and tight.
NOTE: Flexible duct only applies
for model UHAS.
15.2.1 Burner Injectors
Ensure gas tight fitting of injectors.
Ensure correct alignment with burners.
Ensure all pipe joints are gas tight.
UHA[X][S]
MODEL
150
Orifice Quantity
7
Natural Gas (G20)
Orifice Marking
43
P/N
91930043
Propane (G31)
Orifice Marking
1.35 mm
P/N
91930135
Burner
Compartment
Cover
Flame Probe
Viewing port
for flame probe
Remove flexible
air duct from spigot
Ignition Electrode
Viewing port
for ignition electrode
Remove
access plate
Rubber Seal
Remove screws and
pull off burner
compartment cover
UHA[X][S]
UHA[X][S]
UHA[X][S]
175
200
8
9
43
2.25 mm
91930043
91930225
1.35 mm
54
91930135
91930054
UHA[X][S]
225
250
10
11
2.25 mm
2.25 mm
91930225
91930225
54
54
91930054
91930054
SECTION 15: R
EPLACEMENT
UHA[X][S]
UHA[X][S]
UHA[X][S]
300
350
12
14
40
40
91930040
91930040
91930040
1.45 mm
53
91930145
91930053
91930053
P
ARTS
400
14
40
53