OPERATION All Frontier transmitters send input signals at specific intervals (typically 30 or 60 seconds) and are received by the Model RUT-G directly or through Frontier Model RR repeaters. They are then translated into the protocol desired, de- pending on the plug-in key card selected.
LON devices easy without special SNVT conversion. RS232, RS485 All Frontier points are represented with a transmitter module address ID and point number (1-4); four points per trans- mitter ID. The number of total points is limited by the transmitter interval time calculation shown below.
Page 6
POINT SET-UP CONFIGURATION LON point mapping and SNVT selection are done through a Frontier LNS plug-in. Each Frontier transmitter address and point number is mapped to one of 40 NVOs or NVIs per protocol key and selectable SNVTs. An XIF file and LNS plug-in is included with each LON key.
Page 7
INSTALLING A CONTROL MODULE LON KEY Each LON-KEY-◊ control module can support up to 40 network variables (NVs). The Frontier Gateway can support up to three control modules for 120 NVs. As the application expands, control modules can be field-installed to meet the demand.
Radio motherboard with communication CPU with three key docking ports* (three per RUT-G) 232-KEY-1* RS232 with open frontier protocol (refer to Table 7 for more key options) 485-KEY-1* RS485 with open frontier protocol (refer to Table 7 for more key options)
1. On the PC, open Internet Explorer. Enter the RUT-G’s default IP address. 2. The login screen will request a user name and password. Enter KELE for user name and FRONTIER for pass- word (all capital letters for both).
Page 11
ETHERNET ETHERNET CONNECTION / ACCESSING THE RUT-G (CONTINUED) 4. Within the "Web Server Setup" sub-window on the right, you may change the IP address, Netmask, and Gate- way settings by clicking the appropriate "change" link. 5. When the IP address, Netmask, and Gateway settings have been changed as desired, click the "Reset Server to Above Settings"...
Due to the large number of possible configurations (depending upon field Frontier devices and installed keys), the user is directed at this point to the individual I/O manuals for descriptions of the individual fields shown.
Page 13
ETHERNET DEVICE DETAIL SCREEN (EXAMPLE) Kele • RUT-G Manual 2005 • www.kele.com • USA 888-397-5353 • International 901-382-6084...
• All float type (4-byte) SNVTs supported types (twisted pair, free, or bus topology) • Fully configurable using the supplied Kele • "Switch SNVTs" type NVOs are used for Frontier Frontier plug-in (LNS) Radio Diagnostics • Support for Ethernet web server Field Transmitter Low Battery •...
LON INTERFACE KEY FRONTIER RUT-G GATEWAY WITH LON-KEY-◊ BLOCK DIAGRAM The Frontier Gateway is composed of three main modules: LON Control Module, Local Processor, and the RF Radio Transceiver. Serial links pass data between the modules (Figure 1). ��� �������...
Page 17
LON INTERFACE KEY NETWORK BUS CHANNEL WIRING OPTIONS One Frontier Gateway with 120 network variables using three nodes (LON-KEYS) on one LonWorks channel. Each node can have up to 40 network variables (Figure 2). �������� �������� ������� ���� � ���� �...
Page 18
LonWorks Control Module (Key) is the LonWorks network interface. Local Processor is the main Frontier Gateway control unit. This processor handles all data to and from the RF trans- ceiver radio. The local processor communicates directly with the LonWorks control module.
Page 19
DIP Switches – Refer to Table 4 on page 66 for more information on DIP Switch settings. Switches 1 through 4 are used to select Frontier transceiver channels A, B, C, D. Channel A is set at the factory. Note that the Frontier field de- vices must be programmed to match channels with the RUT-G Gateway.
LON INTERFACE KEY LON-FT-10 NETWORK WIRING OPTIONS (Refer to Echelon FTT-10A Free Topology Transceiver user’s manual, available at www.echelon.com, for configura- tions not specifically shown here.) Note that terminals REFx, RTSx, CTSx on the Gateway circuit card are not used for LON applications. �������...
Configuration Properties (CPs). It is for this reason that the Kele Gateway LNS plug-in was developed. The built-in support for the Ethernet web server will only allow changes to the CPs that affect the Frontier radios, and cannot access the LON-KEY-◊ side of the device. The web server will not support changeable SNVT types or SNVT format- ting.
Page 22
Frontier transmitter ID number, the transmitter or receiver’s point number on a Frontier unit, and the facility code. Transmitter ID can range from 1 to 65,000. A Frontier field receiver has no Tx ID but is programmed with a Tx ID ref- erence in order for it to respond to its related transmitters.
LON INTERFACE KEY INSTALLING THE KELE LNS PLUG-IN SOFTWARE AND LON SUPPORT FILES The supplied Kele Frontier Plug-in CD contains the plug-in and all support files for the Frontier Gateway. The follow- ing directories and files will be created: The Kele web site, at www.kele.com, has the latest versions of all required support files including the latest copy of this CD.
Page 24
DE-REGISTERING THE FRONTIER PLUG-IN If the Frontier Plug-in is no longer needed on the installed computer, it is very important to de-register the plug-in from the Windows registry before removing the file from the computer. If this is not done, a warning message may be displayed each time the network management tool is started.
Resource files for the Configuration Properties (CPs) are located in the plug-in directory under "Types." By default, this is "C:\Program Files\Frontier Plug-in\Types". The resource files have been created for use with LNS-based sys- tems and may not be compatible with all LON-based systems. In factory preprogrammed units, they may not be re- quired.
Page 26
LON INTERFACE KEY LNS FRONTIER PLUG-IN The Frontier Plug-in is designed using the LNS protocol. Identifies the Gateway plug- in device. Click on tabs for screen selection. Shown is an NVI screen. An NVO screen is similar. Figure 9 Kele • RUT-G Manual 2005 • www.kele.com • USA 888-397-5353 • International 901-382-6084...
LON INTERFACE KEY ENTERING DATA ON PLUG-IN SCREENS To enter data into a Plug-in screen: 1. Select the screen (NVI, NVO, etc.) to which the desired changes are to be made. 2. To change a value, click on the value window. 3.
Page 28
Figure 10 The NVI screen (Figure 10) is used to transmit the network variables to a Frontier field receiver point. All NVI screens set up the Frontier Gateway as a transmitter for Frontier field receivers (RO-4, RDO-2, etc.). The values on this screen must match the values in the field receiver.
Page 29
4. 3. Transmit Time Interval. A value of "30" has been entered. If the Frontier Gateway has not received an updated value from the network within this time period of 30 seconds, the Gateway will re-transmit the last known val- 4.
Page 30
Once the "Download" button is clicked, the Frontier Gateway will configure itself to use the new values for the Frontier field devices. At this time, the "Download" button will disappear (Figure 13). Note also that the log window continues in data flow.
Page 31
The NVO screen (Figure 14A) is used for output network variables (outputs to the network). The NV value is received by the Frontier Gateway from a Frontier field transmitter. The values entered on this screen must be related to the programmed targeted field transmitter.
Page 32
5. Transmitter Low Value Limit. This value is "5," which is what the Frontier Gateway expects to see as its low- est value from the Frontier field transmitter. Refer to Table 2 for more information on limits.
Page 33
LON INTERFACE KEY NVO SCREEN (CONTINUED) The Facility Code screen (Figure 15) is used to enter the Frontier facility code for the complete Frontier system. This code is global to all Frontier transmitters, receivers, repeaters, and the Gateway. All Frontier transmitters, receivers, repeaters, and the Gateway must have the same facility code or communication between devices will not take place.
(always 0.0) Figure 17 1. nviRequest: This is an NVI that allows the user to send a request to the selected Frontier Gateway NV. Refer to the user’s network manager documentation for information on this SNVT. Caution: Do not change the "nviRequest" unless user has experience with this particular SNVT. Doing so may disable, decommission, or set other conditions undesirable to the Gateway’s operation.
Page 35
NVI[x] SETUP REQUIRED. This is an NVI without a Frontier Tx ID. The indicated NVI will not be operational but will not affect any other NVIs.This is a common status if some Frontier NVs are not used (not set up).
The nvoStatus displays the object’s condition as ones and zeros with a "1" being active. No identifying text is included. The Kele Frontier LNS Plug-in aids in the language, deciphering objects, and of the ones and zeros of the nvoStatus as shown below.
The Frontier Gateway supports changeable SNVT types. Not all types are acceptable. Only those SNVT types shown in the "Select SNVT Type" window are supported by the Frontier Gateway. Refer to Table 1 for a listing of the supported SNVT types. With the exception of the SNVT switch, no structured-type SNVTs are supported. SNVTs with a byte length of one to four bytes are used (character, integer, and float).
Page 38
If no selection is made, the default format will be used (typically the second format listed). Like the SNVT type selection, the format is not active at this time. Current SNVT Type: This field displays the current (active) SNVT type being used by the Frontier Gateway for the displayed NV.
LON INTERFACE KEY CHANGING SNVT TYPES AND FORMATS (CONTINUED) After clicking the "Apply" button the type and format is programmed into the node. In addition, the log window is up- dated to display the changes (Figure 21). Figure 21 HELP SCREENS Help screens are available for each type of screen: NVI, NVO, Facility Code, Status, and SNVT Type.
NV MONITOR SCREEN The NV (Network Variable) screen displays all of the node’s NV values at one time. The related Frontier radio ID and point number are also displayed to aid in identifying the NV. This screen is for monitoring only. Editing of values is not allowed.
Page 41
LON INTERFACE KEY NOTES Kele • RUT-G Manual 2005 • www.kele.com • USA 888-397-5353 • International 901-382-6084...
Page 43
Frontier Gateway network interface key. Each RS232/485 Key supports 150 I/O (refer to Table 7 for key types). The maximum I/O that the RUT-G Frontier Gateway can support is 150 I/O. Because of this, only one RS232/485 Key can be installed in a RUT-G Gateway with no other Key types installed. Multiple gateways can be on the same RS485 bus but there must be a unique address for each.
Page 44
Gateway terminal strip. The network interface key is a DTE. Refer to Figure 5 for jumper settings. IMPORTANT: If RTS/CTS is not used, jumper the RTS and CTS lines together on the Frontier network interface key. USER DEVICE RS232 Shields to Chassis Ground...
Page 45
Refer to Figure 5 for jumper settings. USER DEVICE RS485 Shields to Chassis Ground RS485 Ports Gateway NWK B NWK A FRONTIER Network Interface Key USER DEVICE COMMUNICATION WIRING RS485 Figure 2C Kele • RUT-G Manual 2005 • www.kele.com • USA 888-397-5353 • International 901-382-6084...
Refer to Figures 4 and 5. RS232 Communication Transmitting RS232 to User Device from Frontier Network Interface Key (User Device Receiving Data) The network interface key will control the RTS line and monitor the CTS line when transmitting data to the user de- vice.
RS485 Communication RS485 Master/Slave The RS485 Frontier Gateway network interface key software is designed for Master/Slave operation with the user’s device as the master. RS485 Addressing The Interface Key must be set with a unique address on the Node Address Dip Switch located on the network inter- face key.
Page 48
The address is compared to the dip switch setting and if a match is found, the data is processed. If no match is found, the data is discarded. When the user device is sending data to a Frontier field de- vice (RO-4, RDO-2, etc.) and if the ACK is enabled, the network interface key will send an ACK as outlined in Defi-...
Serial Key Interface Module is the Interface between the user’s device and the Gateway. Refer to Table 7 for key types. Local Processor is the main Frontier Gateway control unit. This processor handles all data to and from the RF transceiver radio. The local processor communicates directly with the LonWorks control module.
Page 50
DIP Switches - Refer to Table 4 for more information on Dip Switch settings. Switches 1 through 4 are used to select Frontier Transceiver Channels A, B, C, and D. Channel A is set at the factory. Note that devices, unless otherwise re- quested, are preset at the factory to Channel A.
RS232/485 INTERFACE KEY CONTROL MODULE JUMPER PLACEMENT RS485 Daughter Board. Not RS485 Termination supplied for RS232 Applications. Jumper Pins. Install Jumper if Network Termination Required. END VIEW Reserved Gateway Socket Pins. (Plugs into RUT-G Gateway) TOP VIEW Baud Rate **Clear all Program Memory CTS Jumper.
The End Character is a constant, not a data item. Facility Code is a value used to identify a single installation of a Frontier system. It is set in the Global Configuration Packet. Code can range from 1 to 65,000, and is global to all Frontier radios communicating with the Frontier Gate- way.
Page 53
RS232/485 INTERFACE KEY DEFINITIONS (CONTINUED) Local Processor is the main Frontier Gateway control unit. This processor handles all data to and from the RF trans- ceiver radio. The network interface key communicates directly with the local processor, making the processor trans- parent to the user.
Page 54
RXD is RS232/485 received data by the user’s device and Frontier Gateway network interface key. Signal Strength is sent to the user device in the output data packet. This value, in db, is the power of the Frontier transmitter signal transmitting to the Gateway. Typically the closer the Frontier transmitter is to the Gateway, the great- er the signal strength.
Page 55
Frontier transmitter ID number, the transmitter or receiver point number on a Frontier unit, and facility code. Transmit- ter ID can range from 1 to 65,000. The Frontier Tx ID and point number must be included in most data packets. The transmitter ID and the point number identify the Frontier field device and the data point on that device.
RS485. Refer to Table 6. Global Configuration Packet: Data Type 1. This configuration data is related to all Frontier transmitters and receiv- ers communicating with the Gateway. After changes to any of the three configuration packets, the network interface key must receive this configuration packet first, followed by the configuration packets 2 and 3, as outlined below.
Page 57
RS232/485 INTERFACE KEY PACKETS (CONTINUED) Input Data Packet: Data Type 4. This data packet value is transmitted to Frontier radio receivers and is an input from the user device to the network interface key. Data Item 1 = Key address (RS232 will always be 0)
RS232/485 INTERFACE KEY EXAMPLES Receive and Transmit Examples Note: AAA is the key address. RS232 will always be 0. RS485 can be 1 to 255. Byte Count can be one to three bytes. Global Configuration Packet. Packet Type = 1, Facility Code = 100, 25 inputs, 25 outputs, no Polling, no ACK. Total of seven data items.
Page 59
RS232/485 INTERFACE KEY EXAMPLES (CONTINUED) Output Data Packet. Packet Type = 5, Transmitter ID = 1600, Point Number = 2, Unit Type = 6, Data Value = 3650, Signal-to-Noise Ratio (SNR) = 15, Signal Strength = 33, Diagnostic = 1 (Low field transmitter SNR). Total of nine data items.
Page 60
RS232/485 INTERFACE KEY NOTES Kele • RUT-G Manual 2005 • www.kele.com • USA 888-397-5353 • International 901-382-6084...
RS232/485 INTERFACE KEY TABLE 5 HARDWARE SPECIFICATIONS RS232 RS485 Mode of Operation Single-Ended Differential Maximum Cable Length 50 ft 4000 ft Maximum Data Rate (40 ft - 4000 ft for RS485) 19,200 bps 19,200 bps Maximum Driver Output Voltage ±25V ±1.5V Driver Output Signal Level (Loaded Min) Loaded...
RS232/485 INTERFACE KEY ASSIGNMENT OF THE RS485 DEVICE ADDRESS - DIP SWITCH “NODE ADDRESS” The RS485 requires that each device on the network has a device address. To assign the device address for the Gate- way, use DIP Switch "Node Address" on top of the RS485 control module. Allowable addresses are from 1 to 255. Select an appropriate and available address for the network to which the Gateway will be installed (see Table 8).