Department Of Energy Compliance; Operation- Spark-Ignited Pilot Boilers - Weil-McLain CGA 2 Series Installation And Maintenance Manual

Gas-fired water boilers
Hide thumbs Also See for CGA 2 Series:
Table of Contents

Advertisement

COa Series 2 Gas-Fired Water Boiler -
Boiler Manual
8
Department of Energy - Compliance
This
boiler is equipped with a control system that
automatically
adjusts a time
delay
period to
turn
on the boiler
during
a call for
heat. This
is accomplished
by
circulating
available hot water in
the system while
measuring
water boiler water
temperature changes. The
control calculates
a
suitable
delay
based on temperature
measure-
ments and turns the boiler on only after it determines that the demand for heat cannot be satisfied with the
available
hot water,
Due to the wide variety of controls used in boiler
installations,
this
control
is also equipped with an adjustment
for
the
calculated time delay period
(ECONOMY
ADJUST). In the MIN position, the time delay
is
zero and the
IMPORTANT
notice below must be observed:
IMPORTANT
In
accordance
with
Section 325 (f)
(3)
of
the Energy Policy
and Conservation
Act,
this boiler
is equipped
with
a feature
that
saves energy by
reducing the
boiler
water temperature
as
the heating
load
decreases. This
feature
is
equipped
with
an override which
is
provided primarily
to
permit the
use
of an e:cternal energy
management
system
that
serves the same
function.
THIS OVERRIDE MUST
NOT
BE USED
UNLESS
iiT LEAST ONE OF THE FOLLOWING CONDITIONS IS TRUE:
An external energy
management
system
is installed that
reduces the boiler water
temperature
as
the
heating
load
decreases.
This boiler
is
part of a modular or multiple boiler
system
having a
total
input
of
300,000
BTU/hr or greater.
This boiler is
equipped with
a
tanlde<..s coil.
9 a
Operation - spark-ignited pilot boilers
NOTICE
Follow
all
procedures given
in
this
manual
and
operating
instructions
when operating
the
boiler.
Failure
to
do so
could result
in severe
personal injury,
death
or substantial
property
damage.
I.
Standby: With
no
call
for
heat,
the vent
damper
and circulator
are de-energized.
No
gas flows to
pilot
or
main gas valve.
2.
Call
for heat
(thermostat circuit closes):
34
a. While attempting
to
satisfy
the
heat
demand,
the
control
module monitors
the boiler
temperature
changes via
the
temperature
sensor
and determines
whether or
not
the
available hot
water will satisfy
the
demand,
only running
the circulator. If
additional heat
is
needed, the
sequence
continues. When DHW
(if
used) calls for
heat,
sequence
above
is
bypassed.
b. Vent damper
and circulator energized if
pilot
status
ac-
ceptable.
Vent damper drives
open.
When vent damper
end
switch
makes
circuit,
ignition
control begins
pilot
ignition
attempt.
c.
Ignition
control
checks for
false
flame
signal: If
ignition
control
senses pilot
signal
when no pilot gas
should
be
present, control will
lockout, requiring reset
procedure as
given
in
Figure
24.
3.
Pilot ignition:
Control
module sparks the pilot and opens pilot
valve in main gas valve.
a. If pilot does
light
and control module senses flame
current, spark generator
is
turned off and
main
valve
opens.
b.
Natural
Gas
-
If pilot
does
not
light within
IS
seconds,
pilot valve
is
closed and spark generator is
turned
off. Control
module
waits
5
minutes, then
attempts
to
ignite pilot
again.
This
cycle
will
continue
indefinitely if
pilot
ignition
control
does not sense pilot flame.
Part
Number
550-142-779/0712