Els) - Johnson Controls GG9S*MP Installation Manual

Residential gas furnace 95.5% afue single stage multi-position
Hide thumbs Also See for GG9S*MP:
Table of Contents

Advertisement

NOTES:
1.
Refer to the condensate management and drain hose
plumbing for different configurations in this document. No
hose clamps are needed for the condensate pan hook up.
2.
Drip leg in the gas line must be installed.
3.
The furnace controls require correct polarity on the power
supply and a proper ground.
4.
Y & G must be connected to the control board for cooling
operation.
5.
To measure total static pressure add supply duct pressure to
the return duct pressure, add pressure drop across the 'A'
coil, and add pressure drop across the filter. Ignore negative
signs on the readings.
6.
Inlet gas pressure for natural gas should be 7" and that for
propane should be 11" w.c. Nominal manifold gas pressure
is 3.5" for natural gas and 10" w.c. for propane.
Airflow CFM (Bottom Return without Filters)
Models
0.5" ESP (Nominal)
Low
Med-Lo
(T,G)G9S040A08MP11
581
653
(T,G)G9S060A10MP11
769
917
(T,G)G9S060B12MP11
713
872
(T,G)G9S080B12MP11
854
1008
(T,G)G9S080C16MP11
838
1250
(T,G)G9S080C22MP11
1285
1586
(T,G)G9S100C16MP11
819
1224
(T,G)G9S100C20MP11
1183
1430
(T,G)G9S120D16MP11
876
1254
(T,G)G9S120D20MP11
1190
1430
(T,G)G9S130D20MP11
1198
1459
Maximum
1
Models
Vent Equivalent
2"
3"
(T,G)G9S040A08MP11
65'
90'
(T,G)G9S060A10MP11
65'
90'
(T,G)G9S060B12MP11
65'
90'
(T,G)G9S080B12MP11
65'
90'
(T,G)G9S080C16MP11
65'
90'
(T,G)G9S080C22MP11
65'
90'
(T,G)G9S100C16MP11
30'
90'
(T,G)G9S100C20MP11
30'
90'
(T,G)G9S120D16MP11
30'
90'
(T,G)G9S120D20MP11
30'
90'
(T,G)G9S130D20MP11
N/A
85'
1. For venting purposes, one 90° sweep elbow is equal to 5 Ft. of venting length, one 90° standard elbow is equal to 10 equiva-
lent feet of vent length. Vent termination elbows are not included in these calculations, minimum required vent length is 15 ft.
2. Must be changed if not in rise range.
Subject to change without notice. Printed in U.S.A.
Copyright © 2008 by Johnson Controls, Inc. All rights reserved.
Johnson Controls Unitary Products
Norman, OK 73069
7.
If thermoplastic evaporator 'A' coil drain pans are to be
installed in the up-flow/horizontal configuration, then extra 2"
minimum spacing may be needed to ensure against drain
pan distortion.
8.
External filters required on all configurations.
9.
Electrical entry is available on both sides of the casing.
10. All 33", 95% furnaces are approved for single-pipe and 2-
pipe systems. For single pipe systems it is recommended to
install the combustion air coupling provided and install
approximately 18" of PVC pipe on the furnace.
11. Do not install an external condensate trap on these fur-
naces, as it will prevent the unit from operating correctly.
Minimum Wire
Total Unit
Size awg @ 75'
Amps
One-Way
Med-Hi
High
818
950
14
8.0
1038
1103
14
10.0
1082
1243
14
10.0
1179
1370
14
10.0
1465
1671
14
11.5
1937
2162
12
17.0
1477
1706
14
11.5
1712
1934
12
17.0
1495
1805
14
11.5
1739
1977
12
17.0
1786
2047
12
17.0
Time For 1 ft
Factory Heating
Temperature
(1030 Btu/Ft
2
Rise Range
Speed Setting
Seconds On (Rate)
Med-Hi
30°F-60°F
High
30°F-60°F
Med-Hi
30°F-60°F
High
35°F-65°F
High
35°F-65°F
Med-Hi
35°F-65°F
High
35°F-65°F
Med-Hi
35°F-65°F
High
40°F-70°F
Med-Hi
35°F-65°F
High
45°F-75°F
401260-URG-C-0808
*401260*
Supersedes: 401260-URG-B-0708
5005 York Drive
This document does not replace the installation instructions, which must be referred to for
detailed information.
SUPPLY END
.56"
23.8"
Combustion
B
Air Inlet
.56"
.56"
20"
Combustion Air Inlet
Condensate Drain
Maximum
(Downflow)
Over Current
Protection
Vent Connection
Outlet
15
15
15
15
15
20
15
20
15
20
20
LEFT SIDE
3
Natural Gas
3
Follow all national, local codes and standards in addition to this document. The installation
)
must comply with regulations of the serving gas supplier, local building, heating, plumbing,
and other codes. In absence of local codes, the installation must comply with the national
93
codes and all authorities having jurisdiction.
62
62
CLEARANCES
46
46
Application
46
Top
37
Vent
37
Rear
30
Side
30
Front*
28
Floor
Combustible
Closet
Line Contact
1. For combustible floors only when used with special
sub-base.
* 24" clearance in front and 18" on side recommended for
service access.
All furnaces approved for alcove and attic installation.
QUICK REFERENCE GUIDE
95.5% SINGLE STAGE MULTI-POSITION
RESIDENTAL GAS FURNACES (33" TALL)
RETURN END
2" Diameter
3"
Vent Connection
Outlet
24.25"
Combustion Air Inlet
Gas Pipe
Condensate Drain
Entry
(Downflow)
Electrical
Entry
Vent Connection
Outlet
Condensate
Drain
23"
Thermostat
Wiring
Optional Return Air
Cutout (Either side)
28.5"
29.5"
RIGHT SIDE
DIMENSIONS
Upflow
Downflow
Horizontal
1"
0"
0"
All 'A' Cabinet Furnaces
0"
0"
0"
All 'B' Cabinet Furnaces
0"
0"
0"
All 'C' Cabinet Furnaces
0"
0"
1"
All 'D' Cabinet Furnaces
0"
0"
0"
1
Combustible
Combustible
Slow Green Flash
Yes
Yes
Yes
• Normal operation
No
No
Yes
Slow Amber Flash
• Normal operation with call for heat
Any Red Flash = Fault condition
Any Rapid 4 Flash = Potential fault codes / conditions
DURING INSTALLATION,
DOORS MUST REMAIN ON
FURNACE WHEN MOVING
B
OR LIFING.
Clips can be flipped
into the up position
for coil cabinet or
plenum attachment
A-COIL
14"
1"
33"
1.5"
A
FRONT
Cabinet Size
A (in)
B (in)
14-1/2"
13-3/8"
17-1/2"
16-3/8"
21"
19-7/8"
24-1/2"
23-3/8"
LED INDICATOR

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents