Summary of Contents for Symphony REF4-ADA
Page 1
Following installation, please forward this manual to the appropriate operations person. 801 Church Lane • PO Box D, Easton, PA 18044, USA Toll free (800) 523-9361 • (888) 2-FOLLETT Cool Ideas For Ice Management (610) 252-7301 • Fax (610) 250-0696 • www.follettice.com ®...
Page 2
A return authorization number has been issued by customer service. Follett receives the equipment at the factory in Easton, PA within 30 days of the issue of the return authorization number. The equipment must be returned in Follett packaging. If the packaging has been damaged or discarded, Follett will forward, at the customer’s expense, new packaging.
Before you begin After uncrating and removing all packing material, inspect the equipment for concealed shipping damage. If damage is found, notify the shipper immediately and contact Follett Corporation so that we can help in the filing of a claim, if necessary.
Installation Fig. 1 Stabilizer adjustment Leveling the unit is important to the proper operation of the refrigeration system. After the refrigerator is positioned in the desired mounting location, remove the lower front panel to access the stabilizer legs on the base of the unit.
Changing the temperature set point Follett sets the temperature controller to a 38˚F set point. This set point may not deliver the temperature range desired for your specific application. For example, some medicine manufactures suggest a storage temperature range of 36˚ to 46˚F. Therefore, we have provided you with the ability to easily change the set point to meet your specific needs.
Removal of dust and other particulates from air intake areas and the condenser is important to the proper operation of your Follett equipment. Some environments with large amounts of dust may require more frequent cleaning. 1. Disconnect power to unit by turning switch on the lower front panel to the OFF position, switching circuit breaker to OFF position, and removing power cord from receptacle.
Fig. 6 Slide-out compressor tray A few of the most important benefits of Follett equipment are unsurpassed accessibility and ease of service. REF Series refrigerators continue this commitment with the ability to partially slide the condensing unit out of the base of the refrigerator to access service components without cutting refrigeration lines.
This change can adversely affect the performance of your refrigerator. Therefore, Follett recommends that if hoses are ever connected to the refrigeration system for service, the refrigerant should be recovered, the system evacuated, and recharged by weighing in the correct refrigerant charge.
6. Recover, evacuate and weigh in correct charge. 7. Plugged capillary tube. 7. Replace capillary tube. 8. Inefficient compressor. 8. Consult technical service. If problems persist after following this basic troubleshooting guide, call Follett’s technical service group at (800) 523-9361, (888) 2-FOLLETT or (610) 252-7301.
Accessories Temperature alarm Fig. 1 Before installing alarm 1. Remove supplied 9-volt back-up battery from packing box. 2. Remove 2 screws from module face and remove faceplate. 3. Locate DIP switches on the back of the faceplate (Fig. 1). 4. Verify that the DIP switch settings meet the needs of your facility (Fig.
7. The controller contains a SPDT 1 amp 24V AC Fig. 4 resistive output for wiring alarm to central monitoring or central alarm system (Fig. 4). Power Black White Sensor Output Setting alarm temperatures Fig. 5 1. After the installation is complete allow 30 minutes for the system to stabilize to ambient temperature.
Replacement parts Condensing unit - Reference #11 Evaporator - Reference #5 Refrigeration Reference # Description Part # Fan motor, evaporator 00104919 Bracket, fan motor 00104927 Fan blade 00104935 Fan guard 00104943 Evaporator (includes parts above) 00104885 Filter drier & capillary tube 00103267 Compressor 00104950...
Page 14
Description Part # Door, REF5 (includes gasket – 21 5/8" x 21 5/8") 00105015 Not shown Door, REF4-ADA (includes gasket – 18 5/8" x 21 5/8") 00113910 Latch & striker (includes screws) 00105023 Latch screws (each – 3 per latch) 00103507 Striker screws (each –...
Page 15
Temperature alarm accessory Reference # Description Part # Not shown Bottle kit (includes bottle, bracket and gasket) 00113779 Not shown Controller kit (includes battery, probe and power supply) 00108175 Not shown Gasket, bottle 00112029 Not shown Bracket, bottle 00112011 Not shown Bottle 00112037 Not shown...
Page 16
801 Church Lane • PO Box D, Easton, PA 18044, USA 00104109R06 Toll free (800) 523-9361 • (888) 2-FOLLETT Cool Ideas For Ice Management 01/04 (610) 252-7301 • Fax (610) 250-0696 • www.follettice.com ® ®...