Refrigeration Cycle Diagram - LG LBNK3660BL Service Manual

Ceiling duct air conditioner
Hide thumbs Also See for LBNK3660BL:
Table of Contents

Advertisement

Refrigeration Cycle Diagram

Heat Pump
ORIFICE
(Capillary only
for 60k Btu)
Orifice Number
Capacity
Orifice Number
30k
36k
42k
74/72
48k
86/90
72k
90k
100k
104
Pipe Size (Diam-
eter: Ø)
Capacity
inch
Standard
Gas
Liquid
30k Btu/h
5/8"
3/8"
36k Btu/h
5/8"
3/8"
42k Btu/h
3/4''
3/8"
48k Btu/h
3/4''
3/8"
60k Btu/h
3/4''
3/8"
72k Btu/h
1''
1/2"
90k Btu/h
9/8''
5/8"
100k Btu/h
9/8''
5/8"
• If 60K Model is installed at a distance of 15m, 525g of refrigerant should be added
(15-7.5) x 70g = 525g
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
63
62
98
84
Piping Length
Elevation B(m)
A(m)
Standard
Max.
Max.
7.5
30
5
15
7.5
30
5
15
7.5
30
5
15
7.5
30
5
15
7.5
30
5
15
7.5
25
5
20
7.5
30
5
20
7.5
30
5
20
HP
ORIFICE
(Only for
60k Btu)
* Additional
Refrigerant
(g/m)
70
50
70
70
70
70
90
100
- 11 -