CONTROL PANEL TEMPERATURE AND ERROR CODES DISPLAY ON / OFF POWER BUTTON WATER DEFICIENCY INDICATOR HEATING TEMPERATURE ADJUSTMENT KNOB WATER PRESSURE LEVEL 1 BAR INDICATOR DOMESTIC HOT WATER TEMPERATURE ADJUSTMENT KNOB WATER PRESSURE LEVEL 1.5 BAR INDICATOR MODE SELECTION PAD (SUMMER ONLY / WINTER ONLY / SUMMER AND WINTER) GENERAL LOCK-OUT WITH FLASHING ERROR CODE ON DISPLAY...
Page 5
SM 20015 DIAGNOCODE ELECTRONIC PRINTED CIRCUIT BOARD cod. 76655LA TECHNICAL SPECIFICATION New generation printed circuit board with easy settings of boiler parameters. Special features: : • Heating temperature adjustment from 30 to 80 °C Exclusively for technicians settings • Standard / reduced heating temperature •...
IT BRINGS THE HOT WATER TEMPERATURE OF THE STORAGE CYLINDER UP TO 60°C WHATEVER TEMPERATURE VALUE IS SET FOR HOT WATER. NOT COMPATIBLE THIS CODE IS DISPLAYED WHEN THE REMOTE CONTROL OR OUTSIDE REMOTE CONTROL. TEMPERATURE SENSOR CONNECTED ARE NOT ORIGINAL RADIANT PARTS. P.C.B. SM 20015 – boiler settings...
PARAMETERS TABLE PARAMETER PARAMETER TYPE OF OPERATION FUNCTION NUMBER VALUE WALL MOUNTED OR FLOOR STANDING BOILER TYPE SELECTION OIL FLOOR STANDING UNIT INSTANTANEOUS WITH STORAGE CYLINDER BOILER TYPE SELECTION WITH STORAGE CYLINDER-COMFORT (+ 7°C) NATURAL GAS GAS TYPE SELECTION L.P.G. HEATING TEMPERATURE STANDARD: from 30 to 80°C SETTING...
Page 8
Parameter setting: BOILER TYPE SELECTION To modify the Parameter value: a. Put ON/OFF button in OFF position ( b. Push pad simultaneously and keep them pressed; c. Put ON/OFF button in ON position ( and wait until the display shows d.
Page 9
Parameter setting: HEATING TEMPERATURE SETTING To modify the Parameter value: a. Put ON/OFF button in OFF position ( b. Push pad simultaneously and keep them pressed; c. Put ON/OFF button in ON position ( and wait until the display shows d.
Page 10
Parameter setting: WATER-HAMMER PREVENTION SETTING To modify the Parameter value: a. Put ON/OFF button in OFF position ( b. Push pad simultaneously and keep them pressed; c. Put ON/OFF button in ON position ( and wait until the display shows d.
Parameter setting: PUMP OVERRUN - HEATING CIRCUIT adjustable from 0 to 7.5 minutes. Factory calibrated at 3 minutes STANDBY. (N.B. DO NOT set the overrun time under 3 minutes) To modify the Parameter value: a. Put ON/OFF button in OFF position ( b.
Page 12
: Mechanical minimum gas pressure setting The mechanical minimum gas pressure is factory calibrated on all boilers at 17/18 mmH20. When replacing the gas valve adjust the mechanical minimum pressure as follows: : • Using a single cut screwdriver turn D screw (fig.1 ) clockwise and tight it ; To adjust the mechanical minimum, turn D screw (fig.1) counter-clockwise for •...
Page 13
Parameter setting: MAXIMUM GAS PRESSURE SETTING - MAXIMUM HEATING OUTPUT SETTING To check or modify the existing pressure value: a. Insert a manometer into the gas valve pressure point B (fig.1); b. Put ON / OFF button in OFF position ( c.
Page 14
Parameter setting: MAXIMUM HEATING OUTPUT SETTING To check or modify the existing pressure value: a. Insert a manometer into the gas valve pressure point B (fig.1); b. Put ON/OFF button in OFF position ( c. Push pad simultaneously and keep them pressed; d.
MAXIMUM HEATING OUTPUT GAS PRESSURE DIAGRAM mod. For 32 kW output boilers RBA 35 E (G20 - G30/31) METANO G.P.L. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 Pressione gas in mbar mod.
Page 17
WIRING DIAGRAMS – OPEN COMBUSTION CHAMBER BOILERS PRINTED CIRCUIT BOARD CVI-M SM20015 (cod. 76655LA) DISPLAY DIGITAL BOARD 2000 SKO6206 (COD. 76654LA) - LINE - NEUTRAL - FLUE SAFETY THERMOSTAT TF-RS - WATER PRESSURE SWITCH - ELECTRONIC FLOWSWITCH - MAIN SWITCH - D.H.
Page 18
WIRING DIAGRAMS - ROOM SEALED BOILERS PRINTED CIRCUIT BOARD CVI-M SM20015 (cod. 76655LA) DISPLAY DIGITAL BOARD 2000 SKO6206 (COD. 76654LA) - LINE - NEUTRAL - AIR PRESSURE SWITCH - WATER PRESSURE SWITCH - ELECTRONIC FLOWSWITCH - MAIN SWITCH - D.H. WATER SENSOR ELECTRONIC IGNITION BOARD - HEATING SENSOR 1,5bar...
Page 19
WIRING DIAGRAM FOR REMOTE CONTROL INSTALLATION (no zone valves) Fig. 3 Interfaccia grey orange Fig. 2 P.B.C. INTERFACE REMOTE Fig. 4 EXTERNAL SENSOR M1 1 REMOTO Fig. 5 Fig. 1 Fit the interface (fig. 2) on the circuit board (fig. 1) into the holes A and B provided (see fig. 1). Connect plug M1 on the interface circuit board (fig.
Page 20