2
Installation Of Drain Hose
!
CAUTION
Be sure that the drain
hose is not loosely
connected or bent.
Bending
Upwards
You are free to choose the side (left or right) for the installation of drain hose. Please ensure the
!
smooth flow of condensed water of the indoor unit during installation. (Carelessness may result in water
CAUTION
leakage.)
Please mount the Outdoor unit on stable ground to prevent vibration and increase of noise level.
G
Decide the location for piping after sorting out the different types of pipe available.
G
Please Remove The Cover For Wire Connection
Procedure to remove the cover of wiring terminals
Remove the screw (1 piece).
G
Hold the projected part at the lower left of the cover and push the cover
G
upwards to remove it.
To close the cover, insert the upper part of the cover into the body of outdoor
G
unit, then be sure that the hook below the cover is plugged in before screwing.
1
Removal Of Air From The Pipe And Gas Leakage
Procedures of using Vacuum Pump for Air Removal
As shown in figure on the right, remove
the cap of valve head and valve core
1
and then connect them to the vacuum
pump and sub-division valve.
Fully tighten the "Hi" shuttle of the sub-
division valve and completely unscrew
the "Lo" shuttle. Run the vacuum pump
2
for about 10–15 minutes, then completely
tighten the "Lo" shuttle and switch off
the vacuum pump.
Completely unscrew the spindle of the
service valve (at 2 places) in anti-
3
clockwise direction to allow the flow of
coolant (using Allen key).
Remove the connection pipe and tighten
4
the cap of valve head. The task is then
completed.
Gas Leakage Inspection
Please use gas leakage detector to check if leakage occurs at the
connection of Hexagon screw nut as shown on the right.
If gas leakage occurs, further tighten the connection to stop leakage.
<
>
I719: A
Ditch
Condensed Water
Pond
Condensed
Water Pond
Please Face This Side
(suction side) Of The
Unit To The Wall
When the meter reaches - 101KPa
(-76cmHg) during pumping, fully tighten
the shuttle.
Meter showing pressure
Closed
Lo
Hi
Charge hose
Manifold valve
Valve
Valve
Vacuum pump
Vacuum
pump
adapter
When pumping starts, slightly loosen the flare
nut to check of air sucked in. Then tighten the
flare nut.
The Body Of
Service Valve
Cap Of Valve
Core
Allen Key
Cap Of Valve Head
Cap Of Valve Head
1
Preparation of Pipe
Use a pipe cutter to cut the copper pipe.
G
Jagged edge will cause leakage.
G
Point the side to be trimmed downwards during trimming to prevent copper chips from entering the pipe.
G
Before flaring, please put on the hexagon screw cap.
G
Mould
Outer
Diameter (ø)
6.35 (1/4")
9.52 (3/8")
2
Pipe Connection
Please be careful when bending the copper pipe.
G
Applied frozen grease to the connection points and then screw in manually.
G
After that, use a torque wrench to tighten the connection.
Spanner
Hook
WARNING
!
Power supply shall be connected at the rated voltage, otherwise the unit will be broken or could not reach the
specified capacity.
Procedures of Wiring
Green & Yellow
The naked part of the wire core should be 14 mm and the insulated part of the wire must be push into
G
the terminal for 3 – 4 mm. Then try to pull the individual wire to check if the contact is tight. Improper
insertion may burn the terminal.
Be sure to use only wire specified for the use of air-conditioner.
G
Please refer to the installation manual for wire connection and the wiring technique should meet the
G
standards of electrical installation.
There is a AC voltage drop between the A, B terminals if the power is on. Therefore, be sure to remove
G
the plug from its socket.
Copper Pipe
CAUTION
!
A (mm)
Imperial flaring tool
Rigid flaring tool
0.8 – 1.5
0 – 0.5
1.0 – 1.8
0 – 0.5
Hexagon Screw Nut
of pipe (ø)
Small diameter side
Big diameter side
Torque Wrench
Valve head cap
Valve core cap
G
THIS APPLIANCE MUST BE EARTHED.
Line Cord
Indoor Unit
Brown (L)
Blue (N)
AC 220-240V
Connecting Cord
Thermistor Wire
Indoor Unit
GRN + YEL
Strip Wires
Outdoor Unit
GRN + YEL
Detail of cutting the connecting cord
To remove the connecting wires for the
indoor unit, please remove the low cover
panel in front of the unit.
WARNING
!
Trimming Tool
Mould
A
Copper Pipe
Outer
Torque N.m
diameter
(kgf
cm)
G
13.7 – 18.6 (140 – 190)
6.35 (1/4")
9.52 (3/8")
34.3 – 44.1 (350 – 450)
19.6 – 24.5 (200 – 250)
12.3 – 15.7 (125 – 160)
Outdoor Unit