Eleven settings: 0.7, 1, 1.4, 2, 2.7, 3.5, 5, 7, 10, 12 and 15 Vdc ±1% max. One variable setting : 0.2 to The Model 2350 Rack Adapter accepts up to ten 2310B 7 Vdc Amplifiers for mounting in a standard 19-in (483-mm) rack;...
The operating procedure is 115 or 230 Vac switch selected in amplifiers, 50/60 covered in Section 4.0. Hz, 40 Watts max. 3.1 2310B FRONT PANEL SIZE & WEIGHT: CAL Switches: Toggle switches to place shunt- 9.06 H x 7.20 W x 18.90 D in calibration resistors across arms of the input bridge.
±1.414V (1 Vrms for sine waves). INPUT Receptacle: A 15-pin quarter-turn connector to connect the input circuit to the 2310B. Quarter, half, and full bridges, potentiometers, or voltage inputs can be accepted simply by using the appropriate pins; see 4.2 Gage Input Connections for details.
4.2 GAGE INPUT CONNECTIONS recommended; neither of these circuits requires It is suggested that the 2310B be turned on (press the red additional wiring from that shown in Figure 2. POWER button) and allowed to stabilize while...
(and insulated against accidental groundings) at the gage end. The 2310B Amplifier can accept dc inputs, such as Normally the guard shield is used inside a conventionally thermocouples, provided two requirements are observed: grounded shield, as shown in Figure 2C.
The 2310B Amplifier has two simultaneous non- interacting outputs; any one or all may be used in a particular test. Both outputs are accessible at the rear of the 2310B utilizing coaxial (BNC) connectors.
To select the outputs to be filtered, open the right side- semifloating. Unless some ground exists in the input cover of the 2310B and note the two toggles on the red circuit, the supply automatically centers itself about FILTER switch (near the top of the p.c. board) marked circuit common (e.g., when set at 5B, P+ will read...
POWER is turned off (or there is a failure in the ac RESET position, and release. In 1 to 3 seconds (8 mains) since the 2310B has a keep-alive supply (a small seconds under the most extreme conditions) the battery) to power this circuit at all times.
Note that this equation assumes one active gage; 4.13 FILTER additional active gages will increase the output. The standard 2310B is equipped with a 6-pole low-pass Equation 6 can be rearranged as: active filter which, depending on which FILTER button...
To use the playback mode, move the PLAYBACK coupling is selected, there is a maximum permissible switch on the rear panel of the 2310B to ON (up). differential dc input which must not be exceeded (to Connect the output from the tape recorder to the INPUT avoid saturation of the preamplifier);...
+15V supply may be used, as shown in Figure be at REMOTE, and 8A. When more than one 2310B is to be operated with a single set of switches (or external relays), an external 5 The EXCITATION selector switch must be set at Vdc power supply is required (250 mA for each 10 half the desired bridge excitation.
+ or -. (If both necessary for the shunting effect of the resistance switches are operated simultaneously the values are balance circuit, since the 2310B does not use the shunt algebraically additive.) method for bridge balance.) With Option Y additional relays are installed in the Gage factor (K´) in equation 10 may be the actual...
CKT 1: Shunt Internal Half Bridge Excitation SENSE: LOCAL USE: Quarter and half bridge (full bridge Cal Selector Switches: with reduced accuracy). #1 closed (P+ at INT) #3 closed (P- at INT) ADVANTAGES: Same resistors for any #5 closed (S+ at INT) active gage resistance.
Page 18
M installed inside the 2310B. In other cases the pins of the 2310B INPUT plug, the other from the may be one normal input lead and one normal output transducer negative output pin to pin N of the lead.
5.5 STANDARD CALIBRATION RESISTORS simultaneously shunting two opposite legs of the bridge. To calculate the resistor value, use the The 2310B is intended to be ready for use as received, following equation: with bridge completion resistors, dummy gages and shunt calibration resistors installed.
6.1 FILTER CHARACTERISTICS Should there be an instantaneous step input, the The standard 2310B is supplied with an active 6- Butterworth filter will produce 5 to 8% overshoot pole filter with Butterworth characteristics having...
IC and adjustments where: is the cut-off frequency (-3dB) in Hz. that are used to calibrate the 2310B. Also shown are the All multipole filters introduce a significant time delay relays used for shunt cal and zero functions. Schematic near and above the cut-off frequency.
Page 22
It is should be set 0.1% (if possible) after — 15 minutes warmup. *Press AC button IN, reading shift <5mV Adjustments D and E are set to make the 2310B METER LEADS READING ADJUST output (after “balancing” the bridge) independent of...
Remote cal plug (for 2350/2360) routinely two years after installation. — 12X300533 (Cinch-Jones S-308-CCT) The batteries used in the 2310B are widely used and Line cord (for 2350 and 2360) — 21X300126 are available at most electronic supply stores. Eagle (Belden 17742) Picher PT-2150 (Lithium 3.6Volt, 1/2AA) or equal is...
APPENDIX – 1000-OHM BRIDGE COMPLETION The 2310B Signal Conditioning Amplifiers provides the capability of 1000-ohm quarter bridge operation. For this mode, the 120-ohm dummy terminal (pin B of input plug) is converted to a 1000-ohm dummy terminal by removing a solder shunt from a factory-installed precision resistor in series with the internal 120-ohm dummy gage.
Vishay Micro-Measurements reserves the right to make any changes in the design or construction of its instruments at any time, without incurring any obligation to make any change whatever in units previously delivered.
Need help?
Do you have a question about the 2310B and is the answer not in the manual?
Questions and answers