NCR 4072 Installation And Operation Manual

500-1400 va

Advertisement

NCR 4072
500–1400 VA
Uninterruptible Power Systems (UPS)
Site Preparation,
Installation, and Operation Manual

Advertisement

Table of Contents
loading

Summary of Contents for NCR 4072

  • Page 1 NCR 4072 500–1400 VA Uninterruptible Power Systems (UPS) Site Preparation, Installation, and Operation Manual...
  • Page 2 Cet appareil numérique de la classe B respecte toutes les exigences du Reglement sur le matériel brouilleur du Canada. ECopyright 2001–2005 NCR Corporation, Dayton, Ohio. All rights reserved. No part of this document may be reproduced in any way without the express written approval of NCR Corporation.
  • Page 3 Requesting a Declaration of Conformity Units that are labeled with a CE mark comply with the following harmonized standards and EU directives: Harmonized Standards: IEC 62040-1-1 and IEC 62040-2; IEC 60950 Third Edition EU Directives: 73/23/EEC, Council Directive on equipment designed for use within certain voltage limits 93/68/EEC, Amending Directive 73/23/EEC 89/336/EEC, Council Directive relating to electromagnetic compatibility...
  • Page 4: Special Symbols

    Special Symbols The following are examples of symbols used on the UPS to alert you to important information: CAUTION Risk of Electric Shock Do Not Open Cover CAUTION To reduce the risk of electric shock, Do not remove cover (or back) No user-serviceable parts inside Refer servicing to the factory RISK OF ELECTRIC SHOCK...
  • Page 5: Table Of Contents

    ..........NCR 4072 UPS Site Preparation, Installation, and Operation Manual...
  • Page 6 ........... . . NCR 4072 UPS Site Preparation, Installation, and Operation Manual...
  • Page 7: Ncr 4072 - One Of The Best

    — causing hours of lost productivity and expensive repairs. With the NCR 4072 UPS, you can safely eliminate the effects of power disturbances and guard the integrity of your equipment. The NCR 4072 UPS’s flexibility to handle an array of network devices makes it the...
  • Page 8 Low voltage models can also protect modems, fax machines, or other telecommunications equipment. The NCR 4072 UPS is backed by worldwide agency approvals. NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 9: Safety Warnings

    To comply with international standards and wiring regulations, the total equipment connected to the output of this UPS must not have an earth leakage current greater than 1.5 milliamperes. NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 10 Never open or mutilate batteries. Released electrolyte is harmful to the skin and eyes, and may be extremely toxic. Replace batteries with the same number and type of batteries as originally installed in the UPS. NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 11 Skaf dig aldrig af med batterierne ved at brænde dem. Batterierne kan eksplodere ved åben ild. Batterierne bør aldrig åbnes eller skilles ad. Udløst elektrolyt er skadeligt for hud og øjne og kan være yderst giftigt. NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 12: Belangrijke Veiligheidsinstructies

    Nooit batterijen in het vuur gooien. De batterijen kunnen ontploffen. Nooit batterijen openen of verminken. Vrijkomend elektrolyt is schadelijk voor de huid en ogen, en kan uiterst giftig zijn. NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 13 Älä koskaan heitä akkuja tuleen. Ne voivat räjähtää. Älä avaa tai riko akkua. Paljastunut elektrolyytti on vahingollinen iholle ja silmille ja voi olla erittäin myrkyllistä. NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 14 Ne jamais ouvrir ou mutiler des batteries. L’électrolyte qui s’en échappe est nuisible à la peau et aux yeux et peut s’avérer extrêmement toxique. NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 15 Öffnen oder beschädigen Sie nicht die Batterien, ausfließendes Elektrolyt ist schädlich für Haut und Augen. Falls Sie die Batterien austauschen, verwenden Sie bitte ausschließlich die gleiche Anzahl und die Batterietypen. NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 16 Áðáéôåßôáé óùóôÞ äéÜèåóç ôùí óõóóùñåõôþí. Äåßôå ôïõò ôïðéêïýò êáíïíéóìïýò ðïõ áöïñïýí ôéò áðáéôÞóåéò äéÜèåóÞò ôïõò. ÐïôÝ ìçí ðåôÜôå ôïõò óõóóùñåõôÝò óôç öùôéÜ, ãéáôß ìðïñåß íá åêñáãïýí. NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 17: Avvisi Di Sicurezza

    Osservare le apposite istruzioni. Le batterie devono essere smaltite in modo corretto. Per i requisiti di smaltimento fare riferimento alle disposizioni locali. NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 18: Viktig Sikkerhetsinformasion

    Kast aldri batterier i flammer, da de kan eksplodere, hvis de utsettes for åpen ild. Batterier må aldri åpnes eller ødelegges. Frigjorte elektrolytter er skadelige for hud og øyne og kan være ekstremt giftige. NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 19 Nunca jogue as baterias no fogo, porque há risco de explosão. Nunca abra ou danifique as baterias. O eletrólito liberado é prejudicial à pele e aos olhos e pode ser extremamente tóxico. NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 20 Необходимо соблюдать правила утилизации аккумуляторов. Обратитесь к местным нормативным актам за информацией о требованиях к утилизации. Никогда не бросайте аккумуляторы в огонь. Аккумуляторы могут взорваться под воздействием огня. NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 21: Advertencias De Seguridad

    Nunca abra o mutile las baterías. El electrolito liberado es peligroso para la piel y los ojos, y puede ser extremadamente tóxico. NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 22 Använda batterier får aldrig brännas upp. De kan explodera. Öppna aldrig batterierna eller ta isär dem. Utsläppt elektrolyt är skadlig för hud och ögon och kan vara mycket giftig. NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 23: Installation

    Check the battery recharge date on the shipping carton label. If the date has expired and the batteries were never recharged, do not use the UPS. Contact Customer Service. NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 24: Ups Internal Battery Connection

    Remove the UPS front panel. Figure 2. Removing the Front Panel Slide up and remove the metal battery cover. 500–1000 VA 1400 VA Figure 3. Removing the Battery Cover NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 25 This is normal and does not damage the unit or present any safety concern. Figure 5. Connecting the Red Wire Reinstall the metal battery cover. Figure 6. Reinstalling the Battery Cover NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 26: Installing The Ups

    “Voltage Configuration” on page 29 before installing the UPS. On 230V models, plug the detachable power cord into the input connector on the UPS rear panel. NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 27 The batteries charge to 90% capacity in approximately 3 hours. However, it is recommended that the batteries charge for 6 to 24 hours after installation or long-term storage. NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 28: Ups Rear Panels

    Installation UPS Rear Panels This section shows the rear panels of the NCR 4072 UPS models. DIP Switches USB Port Site Wiring Fault Indicator Network Transient Protector Communication Port Four 5-15 Receptacles Input Overcurrent Protector 6-ft Power Cord with 5-15 Plug Figure 9.
  • Page 29 Site Wiring Fault Network Transient Indicator Protector Six 5-15 Receptacles Input Overcurrent Protector 6-ft Power Cord with 5-15 Plug Figure 12. 1400 VA, 120V Rear Panel NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 30 Figure 13. 500 VA, 230V Rear Panel DIP Switches USB Port Communication Port Network Transient Protector Four 10A, IEC-320 Receptacles 10A, IEC-320 Input Connector Figure 14. 750 VA, 230V Rear Panel NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 31 Figure 15. 1000 VA, 230V Rear Panel DIP Switches USB Port Communication Port Network Transient Protector Six 10A, IEC-320 Receptacles 10A, IEC-320 Input Connector Figure 16. 1400 VA, 230V Rear Panel NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 32 Installation NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 33: Operation

    To turn off the UPS, press and hold the button for two seconds and then unplug the UPS from the power outlet. If you do not unplug the UPS, it remains in Standby mode. NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 34: Standby Mode

    If the UPS finds a problem, an LED indicates where the problem is. For more information, see “Troubleshooting” on page 43. NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 35: Additional Ups Features

    Press and hold the button until you hear the UPS beep (approximately two seconds) to turn the UPS on. UPS Rear Panel Figure 18. DIP Switches NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 36: Communication Options

    Connect the other end of the USB cable to the USB port on your computer. USB Port Figure 19. The USB Port Install the power management software. NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 37: Db-9 Communication Port

    To external device (tied to Pin 4) — No Connection — AC Fail AC Fail relay contact; 20 mA, 30 Vdc contact rating Power Source +V (8 to 24 volts DC power) NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 38: Network Transient Protector

    IN. Connect the network or telephone cable (low voltage models only) to the jack labeled OUT. NETWORK TRANSIENT PROTECTOR Figure 21. Network Transient Protector NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 39: Ups Maintenance

    Check the battery recharge date on the shipping carton label. If the date has expired and the batteries were never recharged, do not use the UPS. Contact Customer Service. NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 40: Replacing Batteries

    Pull the battery out onto a flat, stable surface. The battery is unsupported when you pull it out of the UPS. Use the following steps to replace the batteries: 1. Remove the UPS front panel. NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 41 Disconnect the red battery cable and then 500 VA models. disconnect the black battery cable. Pull the battery out onto a flat, stable surface. 500 VA NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 42 Remove the battery tie around the black cable set and disconnect the black battery cable to the UPS as shown. 1400 VA NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 43: Testing New Batteries

    + --- illuminates and the indicator flashes. Check the battery connections and be sure the battery is fully charged. Call Customer Service if the problem persists. NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 44: Recycling The Used Battery

    Do not discard the UPS or the UPS batteries in the trash. This product contains sealed, lead-acid batteries and must be disposed of properly. For more information, contact your local recycling or hazardous waste center. NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 45: Specifications

    Chapter 7 Specifications This section provides the following specifications for the NCR 4072 UPS models: Dimensions and weights Electrical input and output Environmental and safety Battery Table 3. Model List and Mechanical 120V Models 230V Models UPS Models 4072-0500-7194 4072-0500-7494...
  • Page 46 EN 50091-1-1 and IEC 60950 Safety Markings UL, cUL UL, cUL, CE, TÜV, C-Tick EMC (Class B) FCC Part 15, ICES-003 EN 50091-2, FCC Part 15, ICES-003 NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 47 UPS Models by VA Ratings Load (VA) Watts 1000 1400 1000 1200 1400 Battery times are approximate and may vary depending on the load configuration and battery charge. NOTE NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 48 Specifications NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 49: Troubleshooting

    On/Off Button Unlit Test/Alarm Reset Button Flashing Power On Indicator (Green) On Battery Indicator (Yellow) Overload Indicator (Red) Service Indicator (Red) Figure 22. UPS Front Panel NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 50: Silencing An Audible Alarm

    34 to replace the battery. During extended power outages, turn off the UPS after saving your work and shutting down your computer to conserve battery power. NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 51 If the indicator still flashes, see “Replacing Batteries” on page 34 to replace the battery. Call Customer Service if the problem persists. NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 52 Save your work and turn off your equipment. beep. below or above the limit Turn off the UPS. Contact Customer Service. while the UPS is on battery. NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...
  • Page 53: Service And Support

    Troubleshooting Service and Support If you have any questions or problems with the UPS, call NCR at 1-800-262-7782 and ask for a UPS technical representative. Please have the following information ready when you call Customer Service: Model number Serial number...
  • Page 54 What We Will Do If your NCR product becomes defective within 3 years of the date of purchase, we will repair it or, at our option, replace it at no charge to you. You may call the number listed below for dispatch of an NCR service representative for on-site repair or replacement.
  • Page 55 United States, fire, floods, acts of God. If your NCR product is not covered by our warranty, call us toll free at the number below for advice as to whether we will repair your NCR product and other repair information, including charges.
  • Page 56 Troubleshooting NCR 4072 UPS Site Preparation, Installation, and Operation Manual 05147374 Rev C Uncontrolled Copy...

Table of Contents