Five Seasons FS-GM20AS-A Owner's Manual

Return grille mount electronic air cleaner

Advertisement

Quick Links

OWNER'S MANUAL
MODEL FS-GM20AS-A
RETURN GRILLE MOUNT
ELECTRONIC AIR CLEANER
IMPORTANT: PLEASE READ MANUAL BEFORE OPERATING UNIT
Features
Lifetime Filter System never needs replacing
Electronically removes dust, mites, pollen, pet dander, tobacco smoke, cooking smoke
and grease, mold, fungi, bacteria, and more down to 0.01 micron
Light Weight Aluminum Collecting Cells are durable and easy to maintain
Plastic Intake Grille is easy to wipe clean
Hinged, Swing Out Door allows easy access to filters
Automatic interlock switch disconnects power when unit is opened
Durable Scratch-Resistant powder coat paint finish resists abrasion
Electronic Air Proving Switch allows for quick wiring, and cycles air cleaner on/off with system fan
Indicator Light shows Air Cleaner is working properly at a glance
Easily installs on the wall or ceiling in the main return duct of a central forced air heating/
cooling system

Advertisement

Table of Contents
loading

Summary of Contents for Five Seasons FS-GM20AS-A

  • Page 1 OWNER’S MANUAL MODEL FS-GM20AS-A RETURN GRILLE MOUNT ELECTRONIC AIR CLEANER IMPORTANT: PLEASE READ MANUAL BEFORE OPERATING UNIT Features Lifetime Filter System never needs replacing Electronically removes dust, mites, pollen, pet dander, tobacco smoke, cooking smoke and grease, mold, fungi, bacteria, and more down to 0.01 micron...
  • Page 2: Table Of Contents

    When working on air cleaning equipment, observe IMPORTANT: Please read entire instructions before precautions in the manual, labels attached to the unit, installing the Electronic Air Cleaner. and other safety precautions that may apply. Follow CONTENTS all safety codes. Wear safety glasses and work gloves.
  • Page 3: Major Components

    Cleaner opening as closely as possible. The opening MAJOR COMPONENTS should be framed to provide adequate support for the Air Cabinet Cleaner. Before mounting the Air Cleaner, cover the The cabinet is constructed of 18 gauge steel, painted framing and close the opening to within 1/4 in. (.63 cm) of with a tough powder-coated, scratch-resistant finish.
  • Page 4: White Dust

    WHITE DUST After installation of the Air Cleaner, you may notice some white dust on tabletops and shelves. Most large particles such as lint, are too heavy to remain airborne Fig. 2 — DAX Detergent and tend to settle quickly, never reaching the air cleaner. is available from your installer This white visible dust is normally referred to as “clean or dealer.
  • Page 5: Testing For High Voltage At Power Board

    3. Install new APS on plastic spacers. Ensure sensor 2. Disconnect wiring from the LED, HV1, HV2 and 24 V protrudes into the airstream. terminals. 4. Connect wiring to terminals on APS. Wiring from 3. Remove the hex nut from the power board. power source is connected to terminals 2 and 3.
  • Page 6: Testing Voltage Of Power Board

    Ionizer (K VDC) side of the cell. The reading should be close to 0 ohms. If not, bend the contact to touch the plate. FS-GM20AS-A 4.6 - 4.8 (HV1) 7.0 - 7.3 (HV2) 5. With an ohmmeter, check continuity between the top, Testing Voltage At Cell center disc contact and one of the ionizing wires.
  • Page 7 Spring Table 2 — Specifications MODEL FS-GM20AS-A HOUSE SIZE Ionizing Bar AIR FLOW up to 2000 cfm DUCT SIZE 22 x 29.1 in Wire CABINET 31.4 x 24.4 x 7 DIMENSIONS WEIGHT 38 lbs Fig. 3 — Replacing An Ionizing Wire...
  • Page 8 Fig. 5 — Dimensions Fig. 6 — Exploded View...
  • Page 9: Troubleshooting Guide

    Table 3 — TROUBLESHOOTING GUIDE PROBLEM PROBABLE CAUSE REMEDY System fan is not on. Turn system fan on. Unit does not function correctly. Power Wiring improperly connected. Check wiring. switch on and Defective power switch. Check power switch for continuity with multimeter. Replace if defective. performance indicator light is off.
  • Page 10: Warranty

    ELECTRONIC AIR CLEANER LIMITED FIVE (5) YEAR WARRANTY FIVE YEAR WARRANTY - This FIVE SEASONS product is warranted to be free from electrical and mechanical defects in material and workmanship, under normal use and maintenance within its listed capacity, for a period of FIVE (5) years from the date of original installation.

Table of Contents