Serial Number _E_1007 User Manual May 2009 February 25, 2014 – Revision Polygard® is a registered trademark of MSR SPC3-11XX US Customer Services (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice.
Single Point Gas Controller SPC3 must not be used in potentially explosive atmospheres. The SPC3 may only be used within ambient conditions described in the Technical Data. Polygard® is a registered trademark of MSR SPC3-11XX US Customer Services (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 &...
Push the cursor onto the position segment, which is to be changed. Change the setup / set point. Save the changed value. Finish. Polygard® is a registered trademark of MSR SPC3-11XX US Customer Services (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 &...
See from point 3.6 System Setup Display and change of the system setups See from point 3.7 Polygard® is a registered trademark of MSR SPC3-11XX US Customer Services (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice.
In the error memory the last 15 faults are listed for the service technician even if they were already acknowledged in the menu “System Error“. The deletion of each individual message is effected in the same way as the reset of a fault. Polygard® is a registered trademark of MSR SPC3-11XX US Customer Services (858) 578-7887 &...
A2 = Alarm 2 ON Stage Status A3 = Alarm 3 ON A4 = Alarm 4 ON Polygard® is a registered trademark of MSR SPC3-11XX US Customer Services (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice.
= Reset of a latching mode. Take over the unction Manual OFF Polygard® is a registered trademark of MSR SPC3-11XX US Customer Services (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice.
See 3.5.6 Delay OFF Time Set delay time OFF See 3.5.6 Polygard® is a registered trademark of MSR SPC3-11XX US Customer Services (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice.
Status Relay Latching Relay 2 Reset in the Menu Status Relay Polygard® is a registered trademark of MSR SPC3-11XX US Customer Services (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice.
Time Time Relay 3 Acknowledging- signal Polygard® is a registered trademark of MSR SPC3-11XX US Customer Services (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice. INTEC Controls, 12700 Stowe Dr., Suite 110, Poway, CA 92064 www.inteccontrols.com...
SP Signal Adjust signal form of the transmitter linear See 3.6.4 Polygard® is a registered trademark of MSR SPC3-11XX US Customer Services (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice.
Page 14
01; 02; 03; 04 Analog Output Assign SP signal to analog output See 3.6.10 Polygard® is a registered trademark of MSR SPC3-11XX US Customer Services (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice.
Toxic gas 0 - XX Recommendation without obligation Decreasing signal at oxygen measurement! Polygard® is a registered trademark of MSR SPC3-11XX US Customer Services (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice.
Gas concentration < Stage/Set Point: Alarm is only deactivated at Delay Time OFF 0 the end of the fixed time (sec.). 0 sec. = No Delay Polygard® is a registered trademark of MSR SPC3-11XX US Customer Services (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 &...
Selection of SP No. 0 = SP Signal not assigned to analog output 1 = SP Signal assigned to analog output 1 Polygard® is a registered trademark of MSR SPC3-11XX US Customer Services (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice.
Change **** Failure Relay See 3.7.8 Power On Time See 3.7.9 Polygard® is a registered trademark of MSR SPC3-11XX US Customer Services (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice.
1800 s AV Time 1800 s sec. = Time for the calculation of the average value Polygard® is a registered trademark of MSR SPC3-11XX US Customer Services (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice.
Function Status Fault Relay R0X = Define the fault relay Polygard® is a registered trademark of MSR SPC3-11XX US Customer Services (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice.
30 s Power On Time 30 s XX = Define the power on time (sec.) Polygard® is a registered trademark of MSR SPC3-11XX US Customer Services (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice.
The recommendation does not consider local conditions such as fire protection etc. For the exact position of the terminals see the following connection diagram. Polygard® is a registered trademark of MSR SPC3-11XX US Customer Services (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 &...
R3/R4: Open Collector, 30 VDC, 50 mA * The analog input function is determined by the hardware. Each PCB has got a label with the specific type. Polygard® is a registered trademark of MSR SPC3-11XX US Customer Services (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 &...
The standard setups can be taken from the following configuration and setup card. We recommend registering the individual setups and set points into the list. We recommend checking the setups and set points according to the following check list. Polygard® is a registered trademark of MSR SPC3-11XX US Customer Services (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 &...
Assigned alarm <> alarm relay Assig. SP sig. <> analog output SP 01 = On Board Sensor, SP 02 = external Transmitter Polygard® is a registered trademark of MSR SPC3-11XX US Customer Services (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice.
Screw type terminals min. 0.25 to 2.5 mm -Wire connection (14 to 30 AWG) Polygard® is a registered trademark of MSR SPC3-11XX US Customer Services (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice.
Page 28
Ambient temperature -20°C (-4°F) Power consumption 0.5 A; 12 VA Polygard® is a registered trademark of MSR SPC3-11XX US Customer Services (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice.
The sensor has to be replaced. Remove calibration adapter carefully by turning lightly. Check the sensor for correct mounting! Polygard® is a registered trademark of MSR SPC3-11XX US Customer Services (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 &...
Take the new sensor out of the original packing. Plug in the sensor element into the PCB at X3/X7. Calibrate according to section 8. Polygard® is a registered trademark of MSR SPC3-11XX US Customer Services (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 &...
Hydrogen, H Calibration adapter Fig. 6 CONKIT-E/CH-LC Type: Polygard® is a registered trademark of MSR SPC3-11XX US Customer Services (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice. INTEC Controls, 12700 Stowe Dr., Suite 110, Poway, CA 92064 www.inteccontrols.com...
Notes and General Information ® It is important to read this user manual carefully in order to understand the information and instructions. The PolyGard SPC3 gas monitoring, control and alarm system may only be used for applications in accordance to the intended use.