Digital non-programmable universal radiant floor heating thermostat 29001

Advertisement

Steps
Procedures
Step 1
To start setting, press the SET key for 3 seconds to access the setpoint mode. The LCD
will display the current setpoint (flashing). Then press either the Up key to increase or
the Down key to decrease the setpoint to the desired setting. An example of LCD
display in AF mode is shown.
Step 2
Press SET key again to access the differential mode. The LCD will display the current
differential (blinking). Then press either the Up key to increase or the Down key to
decrease the differential to the desired setting. Selection value: 0.5, 1.0, 1.5, 2.0
Step 3
Press SET key again to access the Outdoor sensor. LCD will display the current
(A mode only,
setting: Off (blinking) Then press either the Up key or Down key to toggle between
otherwise, skip
On and Off.
this step)
Step 4
Press SET key again to access the Maximum Floor limit. The LCD will display the
current setting (blinking). Then press either the Up key to increase or the Down key
(AF mode only,
otherwise skip
to decrease the limit to the desired setting.
this step)
Step 5
Press SET key again to access the Minimum Floor limit. The LCD will display the
(AF mode only,
current setting (blinking). Then press either the Up key to increase or the Down key
otherwise skip
to decrease the limit to the desired setting.
this step)
Step 6
Press SET key again to access the System Mode. LCD will display the current
mode: Heat (blinking) Then press either the Up key or Down key to toggle between
Heat and Off.
Step 7
Press SET key again to access the backlit mode. LCD will display the current mode,
Auto (blinking). Then press either the Up key or the Down key to toggle etween the
Auto, On, Off designation. Press SET key again to go back to normal operating
mode. Note: In Auto Mode, backlit is turned on for 60 seconds when any key is
pressed.
View
Setting
Mode:
Press both Up and Down keys at the same time to review the current control
settings. "VIEW MODE" appears on the upper left corner of the LCD. Then
Press
Down
(or Up ) key to scroll through the settings in the same order as
Setting Mode (Setpoint, Differential, Heat/Off, Backlit etc.). To exit to normal
mode, press
Down key
one more time from the last setting (e.g. Backlit) or
press both Up and
Down keys
cannot be changed.
Turning On and
the Heating System
In the heat mode, the relay is operated to maintain the temperature of the zone.
The control output will turn on when the sensor temperature falls to the setpoint
temperature minus half the differential amount. The control output will turn off as
the temperature rises to the setpoint plus half the differential amount.
During the normal operating mode:
To disable or enable the relay output, press the power button once(eg. 1
second). LCD indicates a flashing "Heat" or "Off" under the "System"
heading. Press the power button again to toggle between "Heat" to enable
and "Off" to disable the relay output. After 30 seconds, the system returns to
normal operating mode.
To completely power off the thermostat, press the power button for three
seconds. Press the power button again to turn back on the thermostat.
Keypad Lock:
Keypad can be locked to prevent tempering by unauthorized personnel. This is
done by pressing SET , Up and Down keys at the same time for three seconds.
A lock symbol appears on the lower LCD screen which indicates that the
keypad is locked. Then input from the keypad is disabled. Press SET , Up and
Down keys at the same time again for another three seconds to unlock the
keypad. The lock symbol disappears from the screen.
Factory setting: unlock
Error Messages
Sensor Error
Internal sensor is open or short circuit. Replace the
Er1
thermostat
Sensor Error
External sensor is open or short circuit. Replace
Er2
the external sensor.
In A mode, if outdoor sensor is set to ON and no
sensor is connected.
at the same time. In this mode, the settings
:
Description
Setpoint Temperature
Default setting: 70 F(21 C)
for A or AF mode, 82 F(28 C)
for F mode.
Differential Temperature
Default setting: 1 F(1 C)
Outdoor sensor: On or Off
Floor maximum limit
Default setting:
82 F(28 C)
°
Floor minimum limit
Default setting: 40 F(5 C)
System Mode: Heat or Off
Default setting: Heat
Backlit mode: Auto, On or
b
Off
Default setting: Auto
Sensor Error
EEPROM (memory) data has been corrupted.
Er3
Replace the thermostat.
HHH
The measured temperature is above the upper
display range.
LLL
The measured temperature is below the lower
display range.
SPECIFICATIONS:
Display Format: Liquid Crystal Display(LCD) with backlit
Power Input : 24VAC
±10%
, 50/60Hz, 0.5VA
Contact Rating: 2A 24VAC
Selectable display in °F or °C
Setpoint Range (ambient):
34-100°F(1-38°C)
Floor Temperature Control Range: 34-122°F(1-50°C)
Default setting:
82 F (28 C)
°
°
Maximum Floor Temperature Limit(AF Mode): 35-122°F(2-50°C)
Default: 82°F(28°C)
Minimum Floor Temperature Limit(AF Mode): 34-121°F(1-49°C)
Default: 40°F(5°C).
Temperature Display Range: -22 to 131°F(-30 to 55°C)
Switching Differential: A/F/AF Mode: 0.5/1.0/1.5/2°F(
Sensor Probe: P-01 10k thermistors, 10" lead, 3/8"(9.5mm) OD x
?
13/16"(20.6mm) length
Operating Temperature: 32 - 122°F (0 - 50°C)
Dimension: 3.62"W x 2.99"H x 0.91"D(92 x 76 x 23mm)
Weight: 0.32 lb. (145 g)
Storage: -4 to 120°F (-20 to 50°C)
Material: Flame retardant plastic
Lockout mode to prevent tempering by unauthorized personnel
EEPROM memory retains control settings in the event of a power
failure.
For more product information, please visit:
www
P.O. Box 4945, 503 Gregg Dr., Buena Vista, Co 81211
Ph: 800 608-0562 Fax: 719-395-3555
Email: info@infloor.com
LCD Display
SET MODE
SET MODE
°
°
70
Room
°
°
SET MODE
8if
SET MODE
1
°
°
SET MODE
SET MODE
OutDoor
Sensor
SET MODE
SET MODE
Floor Max
82
°
SET MODE
SET MODE
Floor
Floor
Min
40
°
°
SET MODE
SET MODE
SYSTEM
Heat
SET MODE
SET MODE
Backlit:
. Default setting: 70 F (21 C)
°C)
, Default: 1°F/1°C.
°F
AF
°F
On
A
°F
AF
°F
AF
Auto
°
°