Hood Exhaust - GE JVM1630 Installation Instructions Manual

Above the cooktop microwave oven
Hide thumbs Also See for JVM1630:
Table of Contents

Advertisement

HOOD EXHAUST

NOTE: Read these next two pages only if you plan to vent your exhaust to the outside. If you plan to recirculate the air
back into the room, proceed to page 6. Below are examples of Outside Top Exhaust and Outside Back Exhaust duct system
layouts. Note the position of the microwave oven relative to the duct system.
OUTSIDE TOP EXHAUST (EXAMPLE ONLY)
The following chart describes an example of one possible
ductwork installation.
* IMPORTANT: If a rectangular-to-round transition adaptor is used, the bottom corners of the damper will
have to be cut to fit, using the tin snips, in order to allow free movement of the damper.
OUTSIDE BACK EXHAUST (EXAMPLE ONLY)
The following chart describes an example of one possible
ductwork installation.
NOTE: For back exhaust, care should be taken to align exhaust with space between studs, or wall should be prepared
at the time it is constructed by leaving enough space between the wall studs to accommodate exhaust.
Installation Instructions
DUCT PIECES
Roof Cap
12 Ft. Straight Duct
(6" Round)
Rectangular-to-Round
Transition Adaptor*
Equivalent lengths of duct pieces are based on actual tests and
reflect requirements for good venting performance with any vent hood.
DUCT PIECES
Wall Cap
3 Ft. Straight Duct
(3
" x 10" Rectangular)
1
4
90° Elbow
Equivalent lengths of duct pieces are based on actual tests and
reflect requirements for good venting performance with any vent hood.
EQUIVALENT
LENGTH x
24 Ft.
x
12 Ft.
x
5 Ft.
x
Total Length
EQUIVALENT
LENGTH*
40 Ft.
x
3 Ft.
x
10 Ft.
x
Total Length
5
NUMBER
EQUIVALENT
USED
=
LENGTH
(1)
=
24 Ft.
(1)
=
12 Ft.
(1)
=
5 Ft.
=
41 Ft.
NUMBER
EQUIVALENT
x
USED
=
LENGTH
(1)
=
40 Ft.
(1)
=
3 Ft.
(2)
=
20 Ft.
=
63 Ft.
1" = 2.5 cm; 1' = 0.3 m

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Jvm1635

Table of Contents