Air Source Swimming pool Heat Pump
‐ Installation and Operation Manual ‐
DSP‐ 85HA
DSP‐100HA
DSP‐120HA

Advertisement

loading

Summary of Contents for Daishiba DSP? 85HA

  • Page 1 Air Source Swimming pool Heat Pump ‐ Installation and Operation Manual ‐ DSP‐ 85HA DSP‐100HA DSP‐120HA...
  • Page 2: Table Of Contents

    Content Safety Precautions ………………………………….……….…………………………………… 2 Technical data.....................3 Unit dimension………………………………………………………….......4 Installation………………………………………………………………........5 Sound pressure level…………………………………………….………………………..…..….8 Electric connection………………………………………………………………………..……….9 Controller instruction ………………………………..………………………………………….11 Maintenance & Troubleshooting………………………….……………………………..…15 - 1 -...
  • Page 3: Safety Precautions

    Safety Precautions Note! It is required to read the Safety precautions in details before operation. The precautions listed below are all-important for safety. Please follow the instructions strictly. General Make sure that the fixed ground wire in the building is securely connected to earth. Wiring tasks should be carried out by qualified electricians only, in addition, they should check the safety conditions of power utilization, for example, check if the cable capacity is adequate, and check if the power cable is damaged.
  • Page 4: Technical Data

    Transport and storage The machine must be transported and stored vertically. Technical data Model DSP‐85HA DSP‐100HA DSP‐120HA Heating Capacity(kW) 5.02 4.95 4.92 Cooling Capacity(kW) 3.59 3.59 Rated Input(kW) 1.69 2.02 2.44 Rated Current(A) 11.1 Max Current(A) 12.4 14.5 18.7 Power Supply(V/Ph/Hz) 220‐240/1/50 Setting Temp.
  • Page 5: Unit Dimension

    Unit dimensions Model A(mm) B(mm) C(mm) D(mm) E(mm) DSP‐85 HA DSP‐100 HA 1140 DSP‐120HA - 4 -...
  • Page 6: Installation

    Installation Select installation position Note! Installation must be carried out by professional 1. If the unit is to be installed on the floor, its undercarriage should be heightened, to avoid ingression of accumulated water in rainy season. In snowy areas, it is important to prevent accumulated snow from blocking up the air‐out.
  • Page 7 Installation in exceptional circumstances (unit: mm) No obstacle in front of the unit Obstacle above the unit Several units in a row Obstacle in front of the unit - 6 -...
  • Page 8 Installation diagram Installation diagram for combination - 7 -...
  • Page 9: Sound Pressure Level

    Sound pressure level Air to water heat pump is usually placed next to a house wall, which gives a directed sound distribution that should be considered. Accordingly, you should always attempt to find a place on the side that faces the least sound sensitive neighbor area. The sound pressure levels are further affected by walls, bricks, differences in ground level, etc and should therefore only be seen as guide values.
  • Page 10: Electric Connection

    Electric connection Note! Electrical installation and service must be carried out under the supervision of a qualified electrician. Electrical installation and wiring must be carried out in accordance with the stipulations in force. A heat pump must not be connected without the permission of the electricity supplier and must be connected under the supervision of a qualified electrician.
  • Page 11 Circuit drawing - 10 -...
  • Page 12: Controller Instruction

    Control instruction Operation panel 1. button instruction ◆ ON / OFF Switch button ◆ Cyclic me When the timer on / timer off are set, press this button, the unit will start or stop according to the set time everyday. Press again to cancel it.
  • Page 13 ◆ Up / Down Up / Down buttons are used to raise or reduce set water temperature, adjust the time of the clock and the timer, reset part of parameter in the management level The outlet water temp adjustment range from 25 ℃~60℃; ◆...
  • Page 14 Press the “Inquiry” button 10 seconds, enter into the parameter setting state of the administrative class Parameter Instruction Range Default Mark Back temp adjustment 1 ‐ 15℃ 3℃ Temp precision adjustment ‐5 ‐ 15℃ 0℃ Heating water flow insufficient temp. 5‐...
  • Page 15 Parameter Instruction Range Default Mark Function selecting of low pressure 0[No] 1[Yes] protection function Function selecting of high pressure 0[No] 1[Yes] protection function Adjust Function selecting of exhaust temp. 0[No] 1[Yes] through protection “up/down Water flow switch 0[No] 1[Yes] ” button 1[open constantly] Water pump open constantly option...
  • Page 16: Maintenance & Troubleshooting

    Maintenance & Troubleshooting Maintenance Check water supply device and release often. You should avoid the condition of no water ● or air entering into system, as this will influence unit’s performance and reliability. You should clear the pool/spa filter regularly to avoid damage to the unit as a result of the dirty of clogged filter.
  • Page 17 Trouble shouting guide Code Fault Return water temp. Coil temp. Water flow switch High pressure protection Low pressure protection Outlet water temp. Water flow insufficient Communication failure Compressor exhaust temp. Outlet water overcooling protection in the cooling mode Outlet water overheating protection in the heating mode Note: Failures related with temperature could restore automatically;...