Intake Air Connection - A.O. Smith BTX 100 Service Handbook

Series 120 & 121 commercial / residential gas water heater
Hide thumbs Also See for BTX 100:
Table of Contents

Advertisement

faCtory supplied/installed fittings
Factory supplied vent and intake air terminations and factory installed fittings on the water heater are not
factored in to the vent and intake air pipe equivalent feet calculations. The intake air connection fitting and
exhaust elbow (vent connection) are factory installed fittings, see Figure 1 below and Figure 3 on page 8.

intaKe air ConneCtion

The intake air connection has a screen and a hose barb installed at the factory, see Figure 1 below.
The intake air connection screen is installed to prevent debris from entering the Combustion Blower and/or
Burner. This screen is left in place when the water heater is installed in a Power Vent configuration but must
be removed before connecting the intake air piping on direct Vent installations. once the intake air pipe is
installed the screen, if not removed, would be hidden from view and may become clogged with debris over
time. This can cause poor combustion and Blocked Air Intake fault conditions and Control System lock outs.
Ensure this screen has been removed on all direct Vent installations if experiencing Blocked Air Intake fault
conditions.
The hose barb is installed on the intake air connection to connect the Blocked Intake Air switch sensing tube.
The intake air connection is factory installed so that the hose barb is at approximately a 115° angle when
viewed from the end. Ensure the hose barb is not oriented any lower than 115° as this will allow water from
condensate or snow being drawn inside the intake air piping on direct Vent installations to fill the Blocked
Intake Air switch sensing tube. If water does enter the Blocked Intake Air switch sensing tube it will damage
the switch and cause Blocked Air Intake fault conditions and Control System lock outs. Ensure this hose
barb is properly oriented when experiencing Blocked Air Intake fault conditions. Angles between 90° and
115° are acceptable. If necessary loosen the hose clamp on the intake air connection elbow and rotate the
intake air connection fitting to adjust the angle properly as shown in Figure 1 below.
INTAKE AIR
CONNECTION
SCREEN MUST
BE REMOVED
ON DIRECT VENT
INSTALLATIONS
HOSE BARB
ANGLED
BETWEEN
90° AND 115°
Service Notes:
• Plastic debris left on the edges of intake air pipe sections after cutting must be removed on direct Vent
installations. These debris can collect inside and clog the Burner which can cause poor combustion,
sooting, rough starting, rough operation and Ignition Failure fault conditions and Control System lock
outs. The Burner is a radial design that can trap debris, see Figure 5 on page 9.
• Exceeding the equivalent length limitations for the vent piping will cause Blocked Exhaust fault
conditions and Control System lock outs.
• Exceeding the equivalent length limitations for the intake air piping will cause Blocked Air Intake fault
conditions and Control System lock outs.
• Exceeding the maximum number of elbows allowed for the intake air and/or vent piping will also cause
Blocked Air Intake and Blocked Exhaust fault conditions and Control System lock outs.
• using smaller intake air and/or vent pipe than required for the installed equivalent length will also cause
Blocked Air Intake and Blocked Exhaust fault conditions and Control System lock outs.
INTAKE AIR CONNECTION
INTAKE AIR
CONNECTION ELBOW
INTAKE AIR
CONNECTION
HOSE BARB FITTING FOR
BLOCKED INTAKE AIR
SWITCH SENSING TUBE
Figure 1
Servicing should only be performed by a Qualified Service Agent
COMBUSTION BLOWER
24 VOLT
GAS VALVE
5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gdhe 50

Table of Contents