HITACHI SPLIT-UNIT AIR CONDITIONER
INSTALLATION MANUAL
Indoor Unit
Outdoor Unit
RAS-10CE9S
RAC-10CE9

SAFETY PRECAUTION

G
Read the safety precautions carefully before operating the unit.
G
The contents of this section are vital to ensure safety. Please pay special attention to the following sign.
!
WARNING ........ Incorrect methods of installation may cause death or serious injury.
!
CAUTION ......... Improper installation may result in serious consequence.
Be sure that the unit operates in proper condition after installation. Explain to customer the proper way of operating
the unit as described in the user's guide.
WARNING
!
G
Please request your sales agent or qualified technician to install your unit. Water leakage, short circuit or fire may
occur if you do the installation work yourself.
G
Please observe the instructions stated in the installation manual during the process of installation. Improper
installation may cause water leakage, electric shock and fire.
G
Make sure that the units are mounted at locations which are able to provide full support to the weight of the units.
If not, the units may collapse and impose danger.
G
Observe the rules and regulations of the electrical installation and the methods described in the installation manual
when dealing with the electrical work. Use wire which is specified for the air conditioner. A short circuit and fire
may occur due to the use of low quality wire or improper work.
G
Be sure to use the specified wire for connecting the indoor and outdoor units. Please ensure that the connections
are tight after the conductors of the wire are inserted into the terminals. Improper insertion and loose contact may
cause over-heating and fire.
G
Please use the specified components for installation work. Otherwise, the units may collapse or water leakage,
electric shock and fire may occur.
G
Do not mix any coolant other than R-22 into the cooling circulation path when mounting or shifting the unit. If it
is mixed with air, the high pressure in the circulation path will rise and this may result in broken copper pipes or
faults.
!
G
Be sure to use the earth line. Do not place earth line near gas or water pipes, lightning conductor
and the earth line of telephone. Improper earthing may cause electric shocks.
G
A circuit breaker should be installed depending on the mounting size of the unit. Without a circuit breaker, the
danger of electric shock exists.
G
Do not install the unit near a location where there is flammable gas. The outdoor unit may
catch fire if flammable gas leaks around it.
G
Please ensure smooth flow of water when installing the drain hose.
1
Installation of Mounting Plate, Wall Penetration and Installation of Protection Pipe
CAUTION
!
G
The draining of the water container inside the indoor unit can be done from the left.
Therefore the mounting plate must be fixed horizontally or slightly tilted towards the
side of drain hose. Otherwise, condensed water may overflow the water container.
Direct Mounting On The Wall
G
Please use hidden beams in the wall to hold the mounting plate.
External dimension of
indoor unit
180mm
200mm
80mm
180mm
1030mm
Drain Hose
Mounting
Plate
Screw for Mounting plate
Please use more
than 4 screws.
Procedures of Installation and Precautions
G
Procedures to fix the mounting plate.
1. Drill holes on wall.
2.Fix the mounting plate on
(As shown below)
wall with 4.1 x 32 screw
(As shown in figure below)
Procedures to fix the holder of remote control.
G
1. Drill holes on wall.
(As shown below)
Wall Penetration and Installation of Protection Pipe
G
Drill a ø 65mm hole on wall
which is slightly tilted
Indoor
towards the outdoor side.
Drill the wall at a small angle.
G
Cut the protection pipe
according
to
the
wall
thickness.
Empty gap in the sleeve of
G
WALL
protection pipe should be
Sleeve of
Protection
protection
completely sealed with putty
pipe
pipe
to avoid dripping of rain
water into the room.
<
>
I957: A
INS RAS/RAC 10CE9S-EN(1)
1
G
Carefully read through the procedures of proper
installation before starting installation work.
G
The sales agent should inform customers regarding
the correct operation of installation.
Tools Needed For Installation Work
G
+ – Screwdriver
G
Measuring Tape
G
Saw
G
ø 65mm Power Drill
G
Allen Key (
G
Wrench (14, 17, 19, 22mm)
G
Gas Leakage Detector
G
Pipe Cutter
G
Plastic Tape
G
Pliers
G
Flare Tool
CAUTION
2
Installation of the Indoor Unit
VERTICALLY DOWNWARD PIPING
Preparation
Connect power cord.
G
G
Pull out the pipe, power cord and drain hose.
Installation
G
The upper part of the indoor unit is hanged
on the mounting plate.
The projection at the lower part of the indoor
G
unit is hooked onto the mounting plate.
Mounting Plate
Coolant pipe
Protection
Pipe
Drain Hose
Power Cord
Level
HORIZONTAL PIPING
Preparation
Change of Drain Hose and Installation Procedures.
Exchange the location of drain hose and drain cap during horizontal piping as shown
G
Line
Hole for
in figure below. Be sure to plug in the drain hose until the insulating material folds upon
Mark
pipe
itself.
G
Please use pliers to pull out the drain cap.
(This is an easier way to remove the drain cap).
Drain cap
G
Remove the cap for drain hose installation
Drain cap
Please insert
until here
CAUTION
!
HORIZONTAL & DOWNWARD PIPING – MAKING OPENINGS
Outdoor
!
CAUTION
G
During horizontal or downward piping, use a knife to cut
2~5mm
openings as shown in figure. Then smoothen the edges
Be sure that the wire is not
of openings with a file.
in contact with any metal
in the wall. Please use the
Pipe
protection pipe as wire
Seal with
support
putty
passing through the hollow
part of the wall so as to
prevent the possibility of
Pull up the pipe after
bending downward
damaged by mouse.
THE CHOICE OF MOUNTING SITE
WARNING
!
G
The unit should be mounted at stable, non-vibratory location which
can provide full support to the unit.
CAUTION
!
G
No nearby heat source and no obstruction near the air outlet is
allowed.
G
Knife
G
The clearance distances from top, right and left are specified in
4mm)
figure below.
G
The location must be convenient for water drainage and pipe
connection with the Outdoor unit.
G
To avoid interference from noise please place the unit and its
remote controller at least 1m from the radio, television and inverter
type fluorescent lamp.
G
To avoid any error in signal transmission from the remote controller,
please put the controller far away from high-frequency machines
and high-power wireless systems.
G
The installation height of indoor unit must be 2.3m or more in a
non public area.
Names of Indoor Components
The Length of Indoor Unit
No.
Component's Name
Qty
Mounting Plate
about
1
1
0.9m
Do not alter the power cord.
Screw for Mounting Plate
6
2
( 4 . 1 x 3 2 )
Holder for Remote
Controller
Cut away shaded
1
3
portion, and finish
the edge of the
opening so that
there is no burr.
AAA Size Battery
2
4
Screw for holder of
Remote Controller
2
5
( 3 . 1 x 1 6 )
There
Remote Controller
allowed, namely, horizontally
6
1
perpendicular to the unit,
vertically down from right,
horizontally out from right and
horizontally out to left.
Purifying Filter
Don't
1
7
downward at the left of the unit.
Dimension of Mounting Stand
(unit : mm)
Power line, pipe and
drain hose must be
tied together with
plastic tape.
!
CAUTION
Please pull the lower part
of
the
indoor
unit
Mounting
Lift the body
Plate
outwards to check if the
of the unit
unit is hooked onto the
upwards and
Projection
then force
mounting plate. Improper
it downwards.
installation may cause
vibration and noise.
Hook
Drain cap
Drain hose
Drain hose
Drain hose
Please insert
until here
Condensed water may leak out if not inserted properly.
Openings
G
Transform the piping while holding down the lower portion
of pipe-support by hand.
18/11/05, 6:29 PM
(Please note the following matters and obtain permission from customer before installation).
WARNING
!
G
The outdoor unit must be mounted at a location which can sup-
port heavy weight. Otherwise, noise and vibration will increase.
CAUTION
!
G
Do not expose the unit under direct sunshine or rain. Besides,
ventilation must be good and clear of obstruction.
G
The air blown out of the unit should not point directly to animals
or plants.
G
The clearances of the unit from top, left, right and front are specified
in figure below. At least three of the above sides must be open
air.
G
Be sure that the hot air blown out of the unit and noise do not
disturb the neighbourhood.
G
Do not install at a location where there is flammable gas, steam,
oil and smoke.
G
The location must be convenient for water drainage.
G
Place the outdoor unit and its connection wire at least 1m away
from the antenna or signal line of television, radio or telephone.
This is to avoid noise interference.
Power Cord
about 1.6m
Figure showing the Installation
of Indoor and Outdoor Unit.
!
CAUTION
In case the pipe length is more than 8m, add refrigerant R22 at
15 gram per every meter exceeds. However, pipe length shall
not exceed 15m.
20
Direction of Piping
Be sure to
completely
Horizontally
seal any
perpendicular
to the unit
gap with
putty.
Connection
are
4
directions
form
the
piping
of the outdoor unit
35
mounting stand
12
35
500
100
INSTALLATION OF COOLANT PIPES AFTER CONNECTION
The coolant pipes should be adjusted to fit into the
G
hole on the wall and then ready for further connection.
G
The terminals of 2 connected pipes must be covered
with insulator used for terminal connection.
G
Connect the power cord.
G
After adjustment, fit the power cord and pipes into
the space available under the indoor unit.
Pipe
THE CONNECTION OF COOLANT PIPE DURING THE
INSTALLATION OF INDOOR UNIT
Preparation To Install Coolant Pipes
Coolant pipes and power cord must be tied together.
G
The front part of the coolant pipes are at locations
G
marked with "
" symbol.
Please bend at a small
0.85m
radius to form an arc
Installation
Hang the indoor unit onto the mounting plate. Use the temporary
stand at the back of the indoor unit to push its lower part 15cm
forwards.
G
Place the drain hose through the hole on the wall.
G
Insulate the connecting portion of coolant pipe with insulator.
G
Connect the power cord.
G
After adjustment, the power cord and coolant pipes are placed
into the space available under the indoor unit.
G
The projection of indoor unit must hook to the mounting
plate.
Heat insulation
pipe
Pull this to the front
during the connection
Coolant pipes
of coolant pipes to
Power cord
ease task.
3
Installation of Drain Hose
Stagment
Drain
water
Bending
Stagment
upwards
water
You are free to choose the side (left or right) for the installation of drain
!
hose. Please ensure the smooth flow of condensed water of the indoor
CAUTION
unit during installation. (Carelessness may result in water leakage.)
2,300mm or more
G
The difference in height
between the indoor and
outdoor unit should be
kept below 5m.
G
The connecting pipe, no
matter big or small,
should all be insulated
with insulation pipe and
then wrapped with plastic
tape. (The insulator will
deteriorate if it is not
wrapped with tape).
The connection of insulated
drain hose.
Please use insulated drain
hose for the indoor piping
(commercial product).
Drain hose
Pipe
Power cord
!
CAUTION
G
The rubber strap used for
fixing the insulator should
not be tied with great force.
Otherwise, this will damage
heat insulation and causes
water condensation.
Pipe
Rubber strap tied with great force
CAUTION
!
Please fix in the plastic
G
core after flaring to avoid
plastic chips entering the
pipes.
below
5mm
Temporary stand
Projection
Hook
about 15cm
Protection
pipe
Drain
Connected
hose
terminals
Power cord
of coolant
pipes
CAUTION
!
Be sure that the
drain hose is not
loosely connected
or bent.

Advertisement

loading

Summary of Contents for Hitachi RAS-10CE9S

  • Page 1: Safety Precaution

    The outdoor unit must be mounted at a location which can sup- the correct operation of installation. can provide full support to the unit. port heavy weight. Otherwise, noise and vibration will increase. HITACHI SPLIT-UNIT AIR CONDITIONER CAUTION CAUTION INSTALLATION MANUAL...
  • Page 2 Please mount the outdoor unit on stable ground Preparation of Pipe Removal Of Air From The Pipe And Gas Leakage Inspection to prevent vibration and increase of noise level. Decide the location for piping after sorting out Use a pipe cutter to cut the copper pipe. Procedures of using Vacuum Pump for Air Removal the different types of pipe available.

This manual is also suitable for:

Rac-10ce9Ras-10c9Rac-10c9Ras-5111cRac-5111cRas-10ce9