ENVIRONMENTAL PERFORMANCE

Test
Atmospheric Environment
Temperature
Humidity
Enclosure Protection
Mechanical Environment
Vibration
Shock and Bump
Seismic
Electrical Environment
Dielectric Withstand
High Voltage Impulse
Electromagnetic Environment
High Frequency
Disturbance / Damped
Oscillatory Wave
Electrostatic
Discharge
Radiated RF
Electromagnetic
Disturbance
Fast Transient
Disturbance
Surge Immunity
Conducted RF
Electromagnetic
Disturbance
Power Frequency
Disturbance
Conducted and
Radiated Emissions
European Commission Directives
Standards
IEC60068-2-1/2
IEC60068-2-78
IEC60529
IEC60255-21-1
IEC60255-21-2
IEC60255-21-3
IEC60255-5
IEC60255-5
IEC60255-22-1 Class 3,
IEC61000-4-12 / EN61000-
4-12
IEC60255-22-2 Class 3,
IEC61000-4-2 / EN61000-
4-2
IEC60255-22-3 Class 3,
IEC61000-4-3 / EN61000-
4-3
IEC60255-22-4, IEC61000-
4-4 / EN61000-4-4
IEC60255-22-5,
IEC61000-4-5 /
EN61000-4-5
IEC60255-22-6 Class 3,
IEC61000-4-6 /
EN61000-4-6
IEC60255-22-7 Class A,
IEC61000-4-16 /
EN61000-4-16
IEC60255-25,
EN55022 Class A,
IEC61000-6-4
CISPR22 Class A
89/336/EEC
73/23/EEC
Operating range: -10 C to +55 C.
Storage / Transit: -25 C to +70 C.
56 days at 40 C and 93% relative humidity.
IP51 (Rear: IP20)
Response - Class 1
Endurance - Class 1
Shock Response Class 1
Shock Withstand Class 1
Bump Class 1
Class 1
2kVrms for 1 minute between all terminals and earth.
2kVrms for 1 minute between independent circuits.
1kVrms for 1 minute across normally open contacts.
Three positive and three negative impulses of 5kV(peak),
1.2/50 s, 0.5J between all terminals and between all terminals
and earth.
1MHz 2.5kV applied to all ports in common mode.
1MHz 1.0kV applied to all ports in differential mode.
6kV contact discharge, 8kV air discharge.
Field strength 10V/m for frequency sweeps of 80MHz to 1GHz
and 1.4GHz to 2.7GHz. Additional spot tests at 80, 160, 450,
900, 1850 and 2150MHz.
4kV, 2.5kHz, 5/50ns applied to all inputs.
1.2/50 s surge in common/differential modes:
HV ports: 2kV/1kV
PSU and I/O ports: 2kV/1kV
RS485 port: 1kV/0.5kV
10Vrms applied over frequency range 150kHz to 100MHz.
Additional spot tests at 27 and 68MHz.
300V 50Hz for 10s applied to ports in common mode.
150V 50Hz for 10s applied to ports in differential mode.
Not applicable to AC inputs.
Conducted emissions:
0.15 to 0.50MHz: <79dB (peak) or <66dB (mean)
0.50 to 30MHz: <73dB (peak) or <60dB (mean)
Radiated emissions (at 10m):
30 to 230MHz: <40dB
230 to 1000MHz: <47dB
Compliance with the European Commission Electromagnetic
Compatibility Directive is demonstrated according to EN
61000-6-2 and EN 61000-6-4.
Compliance with the European Commission Low Voltage
Directive is demonstrated according to EN 50178 and EN
60255-5.