GRZ100
Optical Interface Unit G1IF1 (Option)
Ratings
Power supply:
Burden:
Interface
Communication interface:
Operative Range:
Wavelength:
Connector type:
Fibre type:
Atmospheric Environment
Temperature
Humidity
Enclosure Protection
Protocol Converter G1PR2 (Option)
Ratings
Power supply:
Burden:
Communication port
RS232C interface
Connector type
Cable type
RS485 interface
Connector
Cable type
Optical interface
Operative Range:
Wavelength:
Connector type:
Fibre type:
IRIG-B
Connector
Mechanical design
Enclosure Protection
Weight
Installation
Atmospheric Environment
Temperature
Humidity
110Vdc/125Vdc (Operative range: 88 - 150Vdc)
220Vdc/250Vdc (Operative range: 170 - 300Vdc)
48Vdc (Operative range: 38.4 - 72Vdc)
less than 8W
CCITT-G703-1.2.1
CCITT-G703-1.2.2 or 1.2.3
X.21
less than 1.2km with 62.5/125µm GI fibre (3dB/km)
820nm
ST
62.5/125µm glass fibre
IEC60068-2-1/2
Operating range: -10°C to +55°C.
Storage / Transit: -25°C to +70°C.
IEC60068-2-78
56 days at 40°C and 93% relative humidity.
IEC60529
IP40 (without outer-case, excluding terminal parts)
IP50 (with outer-case)
110Vdc/100Vac
Operative range:
220Vdc/200Vac
Operative range:
48Vdc
Operative range:
less than 20W
RS232C 9-pin D-subminiature connector female
Multi-core (straight)
Screw terminals (Phoenix Contact, FRONT type)
Twisted pair cable
less than 1.2km with 62.5/125µm GI fibre (3dB/km)
820nm
ST
62.5/125µm glass fibre
Screw terminals (Phoenix Contact, FRONT-MSTB type)
IEC60529, IP20
5 kg
Flush mounting
IEC60068-2-1/2
Operating range: -10°C to +55°C.
Storage / Transit: -25°C to +70°C.
IEC60068-2-78
56 days at 40°C and 93% relative humidity.
88 - 150Vdc of 110Vdc rated voltage
80 - 120Vac of 100Vac rated voltage
170 - 300Vdc of 220Vdc rated voltage
200 - 240Vac of 200Vac rated voltage
38.4 - 72Vdc
20