Electrical - Pentair SSJ Series Owner's Manual

Vertical jet pumps
Table of Contents

Advertisement

Electrical

Max. Load Branch Fuse*
Motor HP
Volts
1/2
115/230
12.4/6.2
3/4
115/230
14.8/7.4
1
115/230
19.2/9.6
* Time delay fuse or circuit breakers are recommended in any motor circuit.
wire before connecting power supply wires. Use the wire size (including
the ground wire) specified in the wiring chart. If possible, connect the pump
to a separate branch circuit with no other appliances on it.
WIRING CONNECTIONS
damage the motor and voids the warranty. The supply voltage must be within
±10% of the motor nameplate voltage.
NOTICE: Dual-voltage motors are factory wired for 230 volts. If necessary,
reconnect the motor for 115 volts, as shown. Do not alter the wiring in single
voltage motors.
Install, ground, wire, and maintain your pump in compliance with the
National Electrical Code (NEC) or the Canadian Electrical Code (CEC), as
applicable, and with all local codes and ordinances that apply. Consult your
local building inspector for code information.
Connection Procedure:
1. Connect the ground wire first as shown in Figure 7. The ground wire
must be a solid copper wire at least as large as the power supply wires.
2. There must be a solid metal connection between the pressure switch
and the motor for motor grounding protection. If the pressure switch
is not connected to the motor, connect the green ground screw in the
switch to the green ground screw under the motor end cover. Use a
solid copper wire at least as large as the power supply wires.
3. Connect the ground wire to a grounded lead in a service panel, to a
metal underground water pipe, to a metal well casing at least ten feet
(3M) long, or to a ground electrode provided by the power company or
the hydro authority.
4. Connect the power supply wires to the pressure switch as shown in
Figure 7.
Wiring Chart – Recommended Wire and Fuse Sizes
Amp
Rating Amp
15/15
12/14 (3/2)
20/15
12/14 (3/2)
25/15
10/14 (5.5/2)
Hazardous voltage. Can shock, burn, or kill. Connect ground
Explosion hazard. Do not ground to a gas supply line.
Fire hazard. Incorrect voltage can cause a fire or seriously
DISTANCE IN FEET(METERS) FROM MOTOR TO SUPPLY
0 - 100
101 - 200
(0 - 30)
(31 - 61)
AWG WIRE SIZE (mm
10/14 (5.5/2)
8/14 (8.4/2)
8/14 (8.4/2)
201 - 300
301 - 400
(62 - 91)
(92 - 122)
)
2
8/14 (8.4/2)
6/12 (14/3)
6/14 (14/2)
6/12 (14/3)
6/12 (14/3)
4/10 (21/5.5)
8
401 - 500
(123 - 152)
6/12 (14/3)
4/10 (21/5.5)
4/10 (21/5.5)