Mitsubishi Electric Mr.SLIM PLA-RP35BA Service Manual page 40

Pla series mr. slim
Hide thumbs Also See for Mr.SLIM PLA-RP35BA:
Table of Contents

Advertisement

(2) Setting method of each function by wired remote controller
1. Stop operation( ).
2. Press the
button ( ) for 3 seconds so that [Maintenance mode] appears on the screen ( ).
TEST
After a while, [00] appears in the refrigerant address number display area. (at
3. Press the
button ( ) for 3 seconds to switch to [Maintenance monitor].
CHECK
Note) It is not possible to switch to [Maintenance monitor] during data request in maintenance mode
(i.e., while "----" is blinking) since no buttons are operative.
[----] appears on the screen ( ) when [Maintenance monitor] is activated.
(The display ( ) now allows you to set a request code No.)
4. Press the [TEMP (
[ScreenB]
5. Press the [CLOCK (
6. Press the
button ( ) to perform function setting.
FILTER
If above setting operations are done correctly, "Request code number will appear in data display area.( )
[Example: When the "311" of "Request code number" is set, [311] appears on the screen.( )]
[Refererence]
You can check current "request code number" setting by setting the "request code number" ("310" or "320") and
pressing the
button.( )
FILTER
[Example: When the current setting is "Setting No.2 (Request code 311)", [311] appears on the screen.( )]
7. To return to normal mode, press the
and
)] buttons ( ) to select the desired refrigerant address.
and
)] buttons ( ) to set the desired request code No. ("311~318", "321~324")
button ( ).
ON/OFF
B: Refrigerant address
C: Data display area
D: Request code display area
)