Wiring Diagram - Mitsubishi Electric MXZ-18NV Service Manual

Inverter-controlled multi system split-type, heat pump air conditioners
Table of Contents

Advertisement

7

WIRING DIAGRAM

TB
POWER SUPPLY
N
220-240V
~/N
L
50Hz
CIRCUIT BREAKER
TB
DC24V
3
INDOOR
TO
N
UNIT (B)
INDOOR
UNIT
CONNECTING
DC24V
3
INDOOR
N
UNIT (A)
SYMBOL
NAME
SURGE ABSORBER
AR61
C61
POWER-FACTOR CAPACITOR
C63
CERAMIC CAPACITOR
C64
CERAMIC CAPACITOR
C65
OUTDOOR FAN CAPACITOR
SMOOTHING CAPACITOR
C67
CT61
CURRENT TRANSFORMER
DIODE MODULE
DS61,63
FUSE1
FUSE(1A)
FUSE2
FUSE(3.15A)
F62
FUSE(3.15A)
HPS
HIGH PRESSURE SWITCH
NOTE:1. For the outdoor electric wining refer to the outdoor unit electric wining diagram for servicing.
2. Use copper conductors only.(For field wining)
3. Symbols below indicate.
: Terminal block,
4. "
"shows the terminals with a lock mechanism,so they cannnot be removed when you pull
the lead wire.
Be sure to pull the wire by pushing the locking lever (project part) of the terminal with a finger.
MODELS MXZ-18NV-
GRN/YLW
2
NF62
4
BLU
3
BRN
BRN
1
RED
LD71
RED
C61
BLU
+
C63
-
+
LD72
C64
-
RED
~
~
BLU
~
BLU
DS61
GRN
CT61
X64
NR61
3
4
AR61
R64
RELAY P.C.BOARD
SYMBOL
L
REACTOR
LEV A,B
EXPANSION VALVE
L61
CMC COIL
MC
COMPRESSOR
MF
OUTDOOR FAN MOTOR(INNER THERMOSTAT)
NF61,62 NOISE FILTER
NR61
VARISTOR
RT61
DEFROST TEMPERATURETHERMISTOR
RT62
DISCHARGE TEMPERATURETHERMISTOR
RT63
FIN TEMPERATURETHERMISTOR
RT64
GAS PIPE TEMPERATUREB.THERMISTOR
RT65
GAS PIPE TEMPERATUREA.THERMISTOR
: Connector
MXZ-18NV-
E1
WHT
WHT
2
NF61
4
C67
+
-
3
1
BLK
LD73
L61
LD74
LD77
BLU
BRN
1
1
1 2
YLW
CN801
2
2
YLW
3
3
FUSE1
YLW
4
4
RED
1
BLU
2
3
RED
4
BLU
CN761
CN771
5
1
2
3
4
5
1
2
3
4
6
LEV A
LEV B
NAME
E2
V
L
MC
WHT
U
DS63
~
+
RED
~
-
RED
R65
BLK
BLU
BuP
BvP
BwP
RED
EuP
EvP
P
U
V
N
BuN
BvN
BwN
EuN
EvN
21S4
1 2
1
2
4 3 2 1
CN61
CN621
CN731
C65
FUSE2
ELECTRONIC CONTROL
SSR61
P.C.BOARD
CN682
CN661
CN683
CN681
5
6
1
2
3
1 2
1 2 3 4
1 2 3 4
RT62
RT63
RT64
RT65
RT66
SYMBOL
RT66
SUCTION TEMPERATURETHERMISTOR
RT67
EVAPORATION TEMPERATURETHERMISTOR
R64
CURRENT-LIMITING RESISTOR
R65
CURRENT-DETECTING RESISTOR
SSR61
SOLID STATE RELAY
TB
TERMINAL BLOCK
TR
POWER TRANSISTOR MODULE
T801
TRANSFORMER
X60,67
FAN MOTOR RELAY
X64
RELAY
21S4
R.V.COIL
MF
W
BLK
BLK
1
WHT
WHT
2
RED
RED
3
TR
EwP
W
EwN
BRN
1
2 3 4 5
6
TAB91
8
RED
CN63
7
6
X67
ORN
5
YLW
4
X60
3
GRN
2
CN641
CN671
BLU
1
4
3
2
1
1 2
RT67
RT61
HPS
NAME
1.Slide the sleeve.
2.Pull the wire while
pushing the locking
lever.
13

Hide quick links: