Continuous Blower Mode; Heat Pump Mode - Carrier Series 100 Installation, Start-Up, And Operating Instructions Manual

Sizes 040-140, series 100 deluxe 4–way multipoise fixed-capacity condensing gas furnace
Hide thumbs Also See for Series 100:
Table of Contents

Advertisement

1. Heat pump MUST have a high pressure switch for dual fuel applications.
2. Refer to outdoor equipment Installation Instructions for additional information and setup procedure.
3. Select the "ZONE" position on the two-speed heat pump control.
4. Outdoor Air Temperature Sensor must be attached in all dual fuel applications.
5. Dip switch No. 1 on Thermidistat should be set in OFF position for air conditioner installations. This is factory default.
6. Dip switch No. 1 on Thermidistat should be set in ON position for heat pump installations.
7. Dip switch No. 2 on Thermidistat should be set in OFF position for single-speed compressor operation. This is factory default.
8. Dip switch No. 2 on Thermidistat should be set in ON position for two-speed compressor operation.
9. Configuration Option No. 10 "Dual Fuel Selection" must be turned ON in all dual fuel applications.
10. NO connection should be made to the furnace HUM terminal when using a Thermidistat.
11. The RVS Sensing terminal "L" should not be connected. This is internally used to sense defrost operation.
12. DO NOT SELECT the "FURNACE INTERFACE" or "BALANCE POINT" option on the two-speed heat pump control board. This is
controlled internally by the Thermidistat/Dual Fuel Thermostat.
13. Dip switch D on Dual Fuel Thermostat should be set in OFF position for single-speed compressor operation. This is factory default.
14. Dip switch D on Dual Fuel Thermostat should be set in ON position for two-speed compressor operation.
c. When the "call for cooling" is satisfied while there is a
demand for dehumidification, the cooling blower-off delay
is decreased from 90 seconds to 5 seconds.

CONTINUOUS BLOWER MODE

When the R to G circuit is closed by the thermostat, the blower
motor BLWM will operate on continuous-blower speed (can
be adjusted to FAN, HEAT, or COOL speed) at the thermo-
stat. Factory default is FAN speed. Terminal EAC-1 is
energized as long as the blower motor BLWM is energized.
During a call for heat, the blower BLWM will stop during
igniter warm-up (17 seconds), ignition (7 seconds), and
blower-ON delay (66 or 45 seconds for 040 through 120 sizes
or for 140 size), allowing the furnace heat exchangers to heat
up more quickly, then restarts at the end of the blower-ON
delay period at HEAT speed.
In heating, the furnace control CPU will hold the blower
motor BLWM at HEAT speed during the selected blower-OFF
delay period before reverting to continuous-blower speed.
When the thermostat "calls for low-cooling", the blower motor
BLWM will switch to operate at low-cool speed (same speed
as FAN). When the thermostat is satisfied, the blower motor
BLWM will operate an additional 90 seconds on low-cool
speed (same speed as FAN) before reverting back to
continuous-blower speed.
When the thermostat "calls for high-cooling", the blower
motor BLWM will operate at COOL speed. When the ther-
mostat is satisfied, the blower motor BLWM will operate an
additional 90 seconds on COOL speed before reverting back
to continuous-blower speed.
When the R to G circuit is opened, the blower motor BLWM
will continue operating for an additional 5 seconds, if no other
function requires blower motor BLWM operation.
Continuous Blower Speed Selection from Thermostat -To
select different continuous-blower speeds from the room
thermostat, momentarily turn off the FAN switch or push-
button on the room thermostat for 1-3 seconds after the blower
motor BLWM is operating. The furnace control CPU will shift
the continuous-blower speed from the factory setting of FAN
to HEAT speed. Momentarily turning off the FAN switch
again at the thermostat will shift the continuous-blower speed
from HEAT to COOL. Repeating the procedure will shift the
continuous-blower speed from COOL back to FAN speed.
Notes For Figure 48-54
The selection can be changed as many times as desired and is
stored in the memory to be automatically used following a
power interruption.

HEAT PUMP MODE

(See Fig. 52, 53, 54, and 55 for thermostat connections.)
When installed with a heat pump, the furnace control auto-
matically changes the blower timing sequence to avoid long
blower off times during demand defrost cycles. When the R to
W-and-Y1 or R to W-and-Y1-and-G circuits are energized the
furnace control CPU will switch to or turn on the blower
motor BLWM at HEAT speed, and begin a heating cycle. The
blower motor BLWM will remain on until the end of the
prepurge period, then shut off for 24 seconds then come back
on at HEAT speed. When the W input signal disappears, the
furnace control begins a normal inducer post-purge period and
the blower remains running at HEAT speed for the selected
blower-OFF delay period then switches to low-cool speed
(same speed as FAN). If the R to W-and-Y1-and-G signals
disappear at the same time, the blower motor BLWM will
remain on for the selected blower-OFF delay period. If the R
to W-and-Y1 signals disappear, leaving the G signal, the
blower motor BLWM will remain on for the selected blower-
OFF delay period then switch to continuous-blower speed.
When the R to W-and-Y/Y2, R to W-and-Y/Y2-and-G, R to
W-and-Y1-and-Y/Y2, or R to W-and-Y1-and-Y/Y2-and-G
circuits are energized the furnace control CPU will switch to
or turn on the blower motor BLWM at HEAT speed, and
begin a heating cycle. The blower motor BLWM will remain
on until the end of the prepurge period, then shut off for 24
seconds then come back on at HEAT speed. When the W input
signal disappears, the furnace control begins a normal inducer
post-purge period and the blower switches to COOL speed
after a 3-second delay. If the R to W-and-Y/Y2-and-G or R to
W-and-Y1-and-Y/Y2-and-G signals disappear at the same
time, the blower motor BLWM will remain on for the selected
blower-OFF delay period. If the R to W-and-Y/Y2 or R to
W-and-Y1-and-Y/Y2 signals disappear, leaving the G signal,
the blower motor BLWM will remain on for the selected
blower-OFF delay period then switch to continuous-blower
speed.
47