Sola 415 Instruction Manual

200 series 3 to 22.5kva

Advertisement

Quick Links

Invensys Energy Systems Pty Ltd
SERIES 200
POWER CONDITIONERS
Instruction Manual
(3 to 22.5kVA)
6M4522 Revision 3
Issue Date: 18/10/02
Made in Australia

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 415 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Sola 415

  • Page 1 Invensys Energy Systems Pty Ltd SERIES 200 POWER CONDITIONERS Instruction Manual (3 to 22.5kVA) 6M4522 Revision 3 Issue Date: 18/10/02 Made in Australia...
  • Page 2: Table Of Contents

    Series 200 Power Conditioners Instruction Manual INDEX Page No. SECTION ONE 1.1 Introduction ....................... 1 1.2 General Description ..................1 1.3 Principles of Operation..................1 1.4 Applicable Product Range ................2 SECTION TWO 2.1 Service Location ....................6 2.2 Connections ...................... 6 2.3 Selection of Input Circuit Breakers..............
  • Page 3: Introduction

    1.1. INTRODUCTION This manual is relevant to the SOLA 200 series of power conditioners. These units require no complicated commissioning or maintenance procedures and will provide many years of trouble- free operation. This manual provides descriptive information and operation and maintenance instructions.
  • Page 4: Applicable Product Range

    Series 200 Power Conditioners Instruction Manual Part Number Power 415 - 240V 400 - 230V 380 - 220V Phase 200-26-730 200-25-730 20-44-730 200-26-730-00 200-25-730-00 200-26-750 200-25-750 200-44-750 200-26-750-HO 200-25-750-HO 200-26-775 200-25-775 200-44-775 1 or 3 200-26-790 200-25-790 200-44-790 1 or 3...
  • Page 5: Typical Schematic Diagrams 3 - 18Kva

    Series 200 Power Conditioners Instruction Manual Fig 3. Typical Schematic Diagrams 3 - 18kVA - 3 -...
  • Page 6: Typical Schematic Diagram 22.5Kva

    Series 200 Power Conditioners Instruction Manual Fig 4 - Typical Schematic Diagram 22.5kVA - 4 -...
  • Page 7: Typical Rating Plate

    MAX. INPUT CURRENT OUTPUT VOLTAGE MAX. OUTPUT CURRENT FREQUENCY 50 Hz THIS PRODUCT COMPLIES WITH AS3100 FOR SERVICE ON THIS PRODUCT CALL: 1300 303 059 Invensys Energy Systems Fig 5. Typical Rating Plate for SOLA 200 PC - 5 -...
  • Page 8: Section Two

    Series 200 Power Conditioners Instruction Manual SECTION TWO SERVICE LOCATION The power conditioner must be installed in an environment free from conductive dust, water vapour and corrosive gases. Positioning the unit directly beneath a fire detector, sprinkler or air conditioning temperature sensor should be avoided. Sufficient clearance between power conditioner and walls and other objects must be allowed for unrestricted movement of cooling air, and for installation and service access.
  • Page 9: Selection Of Input Circuit Breakers

    Series 200 Power Conditioners Instruction Manual SELECTION OF INPUT CIRCUIT BREAKERS As with all transformer based equipment, ferroresonant transformers are characterised by an inrush current when switched on. For this reason it is recommended that delayed-trip type circuit breakers are used when switching power conditioner circuits. In Australia the Heinemann CF1 and CF3 (for 1 and 3 phase circuits respectively) breakers are appropriate.
  • Page 10: Section Three

    220V). The range for the 200-46-822 unit, which CAN ONLY be configured for a three phase input, is 329V to 450V phase to phase, i.e. -21%, +8% for 415/240V and for the 200-35-822 is - 17%, +13% for 400/230V. For the 200-24-XXX the range is -18%, +9% for 380/220V. Useable output voltage is available for limited periods on all units for input deviations as high as +/-40%.
  • Page 11: Routine Operation

    Series 200 Power Conditioners Instruction Manual ROUTINE OPERATION No complicated procedures are required - the following simple steps will optimise performance: POWER All load equipment switches in OFF position Power conditioner input circuit breaker to ON position. Switch ON load equipment in correct sequence - if possible do not power up more than one item of equipment simultaneously.
  • Page 12: Section Four

    SECTION FOUR SERVICING Since SOLA 200 Power Conditioners are simple, rugged devices without moving parts or printed circuit boards no adjustments, servicing or maintenance is required in the normal sense. If poor performance is suspected, the following should be carried out by a competent electrician or technician: Measure and record voltages and currents as described in Section 2.3 of this manual.
  • Page 13: Parts List

    Series 200 Power Conditioners Instruction Manual PARTS LIST The following replaceable parts are available (if your model is not listed below, contact Invensys): Power SOLA PART NUMBERS Conditioner QUANTITY OF CORE/COIL/CAP INDICATOR CIRCUIT OUTPUT MAINS SETS PER UNIT BREAKER SOCKETS...
  • Page 14 Series 200 Power Conditioners Instruction Manual Invensys Energy Systems Pty Ltd ABN 82 054 056 709 This Warranty is subject to Invensys Energy Systems Pty Ltd (IES) standard Conditions of Sale which govern all sales of products by Invensys Energy Systems Pty Ltd. IES products, in general, are warranted against failure due to faulty materials and/or workmanship for a period of two years from despatch date (ex IES store) as per invoice.
  • Page 15 Series 200 Power Conditioners Instruction Manual REPAIR If poor performance is confirmed (refer SERVICING information on Page 10 of this Manual) you should contact Invensys National Service operation. If the unit is to be returned to Invensys for any reason, please obtain a “Return Authorisation” (RA) number first, and mark it clearly on the packaging.