Speakman AL-2 Installation, Maintenance And Operation Instructions

Speakman al-2 alarm system - installation, maintenance and operation instructions

Advertisement

Quick Links

AL-2 Installation, Maintenance & Operation Instructions

DESCRIPTION

Electrical alarm for use with emergency safety equipment. Unit is supplied with an electric horn and flashing light
that are activated by a vapor proof flow switch when connected to an emergency shower or eyewash.

SPECIFICATIONS

FLOW SWITCH: ¾" Vapor Proof Flow Switch(Dwyer #V6EPSSS60).
HORN: Edwards #876-N5 electric. 103dB @ 10 Ft.
LIGHT: 40 Watt Bulb, 120V.
SHIPPING WEIGHT: 21 lb.

ELECTRICAL DATA:

ELECTRICAL SUPPLY: 120 VAC, 60 Cycle, Single Phase.
ELECTRICAL RATING: 7.5 Amps @ 120 VAC.
COMPLIANCE: Unit For Use In Non-Hazardous Locations. Suitable for outdoor / wet locations.
*Power supply to be in compliance with (N.E.C.) National Electric Code.

OPTIONS

DPDT
(Double Pole, Double Throw Flow Switch For Remote Locations)
BLUE GLOBE
RED GLOBE
CLEAR GLOBE
BELL
(97dB @ 10 Ft.)

INSTALLATION

To avoid electric shock make sure power supply is shut off before doing any electrical maintenance to this unit.
Power supply requirement is 120 VAC, 60 cycle, single phase. Ground-fault protection should be GFPD with a
nominal 30 milliampere trip level to prevent nuisance tripping. Minimum 15 AMP breaker is required. Make sure
power supply is in compliance with National Electric Code (N.E.C.).
Use thread sealant on all joints.

OPERATION

Horn sounds and light flashes automatically when emergency equipment is activated and water flow triggers the
flow switch. Horn will sound and light will flash until emergency equipment is deactivated.

TESTING PROGRAM

The American National Standards Institute (ANSI) states that all safety emergency equipment shall be activated on
a weekly basis to flush the line and verify proper operation. Speakman Company furnishes a testing record tag
(91-0635) with each unit. On this tag the date of inspection and the inspectors initials should be noted.
SPEAKMAN COMPANY

ALARM SYSTEM

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AL-2 and is the answer not in the manual?

Questions and answers

Summary of Contents for Speakman AL-2

  • Page 1: Alarm System

    The American National Standards Institute (ANSI) states that all safety emergency equipment shall be activated on a weekly basis to flush the line and verify proper operation. Speakman Company furnishes a testing record tag (91-0635) with each unit. On this tag the date of inspection and the inspectors initials should be noted.
  • Page 2 Be sure water supply is shut off if flow switch is being repaired. WARNING: Use only genuine Speakman parts when repairing or replacing components. To order parts call 1-800-537-2107.