Aqua PRO PRO1100 Owner's Manual

Aqua PRO PRO1100 Owner's Manual

Heat pump pool heater
Table of Contents

Advertisement

Available languages

Available languages

HEAT PUMP POOL HEATER
BOMBA DE CALOR PARA PISCINAS
OWNER'S MANUAL
MANUAL DEL USUARIO
PRO1100, PRO1100e, PRO1300, PRO1300h/c, PRO1100e TCE, PRO1300 TCE, PRO1300h/c TCE
101 Production Drive, Harrison, OH 45030 877.278.2797 fax 877.289.2963
cs@aquaprosystems.com www.aquaprosystems.com

Advertisement

Chapters

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PRO1100 and is the answer not in the manual?

Questions and answers

Tony
April 8, 2025

The screen has a high pressure code

2 comments:
Tony
April 8, 2025

@Tony the y it is A1300

Mr. Anderson
April 9, 2025

A high pressure (HP) code on the Aqua PRO PRO1100 means there is either low water flow, high ambient temperature, or both. It may also indicate a clogged filter that is not allowing enough water to flow through the heater.

This answer is automatically generated

Tony
April 8, 2025

The unit is showing a high pressure code

1 comments:
Mr. Anderson
April 9, 2025

The context does not provide information about a high pressure code for the Aqua PRO PRO1100 unit.

This answer is automatically generated

Claude
July 27, 2025

Hi , I have aqua pro 1100E and need a new panel board ( AHRI reference number 3798332) Let me know the price . Thank you

Summary of Contents for Aqua PRO PRO1100

  • Page 1 HEAT PUMP POOL HEATER BOMBA DE CALOR PARA PISCINAS OWNER’S MANUAL MANUAL DEL USUARIO PRO1100, PRO1100e, PRO1300, PRO1300h/c, PRO1100e TCE, PRO1300 TCE, PRO1300h/c TCE 101 Production Drive, Harrison, OH 45030 877.278.2797 fax 877.289.2963 cs@aquaprosystems.com www.aquaprosystems.com...
  • Page 3: Table Of Contents

    SPECIFIC MODEL DETAILS serious injury. induce hyperthermia. Hyperthermia PRO1100 ..... 4 Caution occurs when the internal temperature Wiring Diagram ....4...
  • Page 4: Installation Procedures

    Operating Instructions Installation Procedures (continued) THE UNIT MUST BE TRANSPORTED IN THE UP-RIGHT POSITION AT ALL TIMES AND MUST NOT BE DROPPED OR TAILGATED. DAMAGE TO THE 5 feet 5' Minimum (minimum) UNIT DURING TRANSPORTATION IS NOT THE RESPONSIBILITY OF THE MANUFACTURER.
  • Page 5: Basic Heat Pump Operation

    PRO1300, PRO1100e, PRO1300h/c, PRO1100, PRO1300h/c TCE, PRO1300 TCE, PRO1100e TCE Basic Heat Pump Buttons 3. Set unit to the “POL” mode. Operation 4. Connect remote system with 2 wires (continued) Press the SET button to change to the P/S terminal on control board between modes and use the up and (see specific model wiring diagram).
  • Page 6: Pro1100

    Motor Temp White High Pressure Yellow Time Delay Black Orange Blue Black Pressure 240V-24V Thermostat Blue Transformer Nuet Hot In Out Gray Water Pressure Black Capacitor Compressor Green Gray Light Llight Figure 4 - PRO1100 wiring diagram www.aquaprosystems.com Phone: (877)-278-2797...
  • Page 7: Pro1300 & Pro1100E

    PRO1300, PRO1100e, PRO1300h/c, PRO1100, PRO1300h/c TCE, PRO1300 TCE, PRO1100e TCE MY-TECH PH-111A Brown PRO1100e Brown & White PRO1300 SPR1 SPR2 REVR JANDY Blue Black Gray Water Sensor Yellow 12 VAC Black Blue Blue Black Black Defrost Sensor Black To Remote System...
  • Page 8: Toggling Between Heat

    Operating Instructions This section allows you to run the heat however, since the unit is checking for PRO1300h/c pump at set intervals during the day. If and adding heat when needed, it you have a time clock, and would like to prevents long recovery times when Electronic Temp.
  • Page 9: Wiring Diagram

    PRO1300, PRO1100e, PRO1300h/c, PRO1100, PRO1300h/c TCE, PRO1300 TCE, PRO1100e TCE MY-TECH PH-111A Brown PRO1100e Brown & White PRO1300 SPR1 SPR2 REVR JANDY Blue Black Yellow Water Sensor Gray 12 VAC Black Blue Blue Black Black Defrost Sensor Black To Remote System...
  • Page 10: Pro1300H/C Tce

    Operating Instructions temperature and reversing operation This section allows you to run the heat PRO1300h/c TCE for 2 minutes to defrost the evaporator pump at set intervals during the day. If coil and will resume heating function you have a time clock, and would like to after defrosting the evaporator coil.
  • Page 11: Tce Operation

    PRO1300, PRO1100e, PRO1300h/c, PRO1100, PRO1300h/c TCE, PRO1300 TCE, PRO1100e TCE “down” arrows, you can select how Time Clock Eliminator the day and also provide the benefit of many total hours a day you want the checking if heat is needed every 4 hours.
  • Page 12: Application Guidelines

    50% - 60% in temperature is not the issue and the your heating bills. During the start of ALL MODELS (except PRO1100) heat pump continues to display “LP” or the swimming season and the end of “LP3”, please call AquaPRO...
  • Page 13 PRO1300, PRO1100e, PRO1300h/c, PRO1100, PRO1300h/c TCE, PRO1300 TCE, PRO1100e TCE Troubleshooting Unit is not running (All Models): Unit runs continuously: Guide (cont.) • Check the power light. Check to see if It may be running continuously because it the breaker is set.
  • Page 14: Warranty

    Operating Instructions LIMITED WARRANTY For two (2) years from the date of purchase, Wayne Water Systems, d/b/a AquaPRO ® Systems (“AquaPRO ® ”) will repair or replace, at its option, for the original owner any parts of its Heat Pumps (“Product”) which are found upon examination by AquaPRO ®...
  • Page 15 DETALLES DE MODELOS ESPECÍFICOS con antecedentes de enfermedades PRO1100 ......3 - 4 cardíacas, presión sanguínea alta - Digrama eléctrico .
  • Page 16: Importantes Instrucciones De Seguridad

    Manual de Instrucciones Importantes instrucciones de seguridad (Continuación) • Como la tolerancia de los dispositivos que regulan la temperatura del agua Mínimo 1,5 m 5 feet puede variar hasta ±3ºC (±5ºF), (minimum) (5 pies) debería medir la temperatura del agua en varios lugares usando un termómetro preciso antes de entrar a una piscina o tina.
  • Page 17: Funcionamiento Básico De La Bomba De Calor

    PRO1300, PRO1100e, PRO1300h/c, PRO1100, PRO1300h/c TCE, PRO1300 TCE, PRO1100e TCE corriente de la unidad, retiene el último Procedimientos de Botones punto de ajuste mostrado. instalación Presione la tecla SET para cambiar entre (Continuación) Conexión a un sistema los modos y use las flechas arriba (UP)
  • Page 18: Bloqueo Por Alta Temperatura

    Amarillo alta Temp. Retraso Negro Azul Anaranjado Presión Negro baja Transformador Termostato de 240V-24V Azul Rojo Nuet Cal. En. Sal. Rojo Gris Presión de agua Negro Condensador verde Compresor Gris roja Figura 4 - PRO1100 diagrama de cableado 4 Sp...
  • Page 19: Pro1300 & Pro1100E

    PRO1300, PRO1100e, PRO1300h/c, PRO1100, PRO1300h/c TCE, PRO1300 TCE, PRO1100e TCE MY-TECH PH-111A Castaño PRO1100e Castaño y Blanco VENTILADOR PRO1300 SPR1 SPR2 REVR JANDY ~8 ~12 Roja Azul Negro Amarillo Gris Sensor de agua 12V CA Negro Azul Azul Negro Sensor de...
  • Page 20: Cómo Alternar Entre Modo De Calefacción Y Modo De Enfriamiento

    Manual de Instrucciones Operación con del(los) tiempo(s) de funcionamiento PRO1300h/c siguiente(s). Note que en días fríos o de Eliminación del mucho viento, es posible que la unidad Temporizador (TCE) funcione por largo tiempo, para Controles electrónicos alcanzar y mantener la temperatura Por favor sírvase leer cuidadosamente de temperatura deseada de la piscina.
  • Page 21: Operación Tco (Con Limitación Del Temporizador)

    PRO1300, PRO1100e, PRO1300h/c, PRO1100, PRO1300h/c TCE, PRO1300 TCE, PRO1100e TCE MY-TECH PH-111A Marrón Marrón y blanco PRO1100e VENTILADOR PRO1300 SPR1 REVR SPR2 JANDY Rojo Azul Negro Sensor de agua Amarillo Gris 12V CA Negro Azul Azul Negro Negro Sensor de...
  • Page 22: Pro1300H/C Tce

    Manual de Instrucciones Operación con PRO1300h/c TCE el uso del servicio eléctrico fuera de Limitación del las horas pico. Por cualquier pregunta, Controles electrónicos sírvase contactar su empresa de Temporizador (TCO) servicio eléctrico. de temperatura (Continuación) Puesta en marcha y ajuste del Cómo alternar entre Modo tiempo de funcionamiento –...
  • Page 23: Ciclo De Descongelación

    PRO1300, PRO1100e, PRO1300h/c, PRO1100, PRO1300h/c TCE, PRO1300 TCE, PRO1100e TCE Controles electrónicos • La función de TCE se realiza por medio unidad funcione por largo tiempo, de temperatura de una secuencia de 6 períodos de para alcanzar y mantener la tiempo en las 24 horas.
  • Page 24: Operación Tco (Con Limitación Del Temporizador)

    Manual de Instrucciones recomienda que un especialista calor cada 4 horas. Eso lo logra Operación con licenciado en acondicionamiento de aire activando el sistema de bomba y Eliminación del realice el mantenimiento anual filtro por 15 minutos. Si se necesita Temporizador (TCE) programado de su calentador.
  • Page 25: Aberturas De La Piscina

    Diagnósticos DSd: Este código indica que hay una falla FS: Este código tiene la siguiente secuencia: del sensor de descongelación. Por favor Todos los modelos (excepto PRO1100) • Cuando aparece por primera vez, la llame a AquaPRO Systems para solicitar ®...
  • Page 26 Manual de Instrucciones Guía de diagnóstico y enfría en el modo “SPA”. sistema en busca de obstrucciones. resolución de La unidad no está funcionando La unidad funciona continuamente: problemas (Continuación) (todos los modelos): Puede que funcione sin parar porque • Verifique la luz de corriente. modo de calefacción.
  • Page 27: Garantía

    PRO1300, PRO1100e, PRO1300h/c, PRO1100, PRO1300h/c TCE, PRO1300 TCE, PRO1100e TCE GARANTÍA LIMITADA Durante 2 (dos) años a partir de la fecha de compra, Wayne Water Systems, cuyo nombre comercial es AquaPRO® Systems (“AquaPRO®”) reparará o cambiará, a su propio criterio, para el propietario original, cualquier pieza de sus bombas de calor (“Producto”) que AquaPRO®...
  • Page 28 Manual de Instrucciones Notes Notas...