Battery Replacement Procedure
5.3 Storage
To store the UPS, cover it and store it with the battery fully charged. During extended
storage, it is suggested to connect the utility power to the UPS to recharge the battery every
three months to ensure battery life.
A
T
PPENDIX A
ROUBLESHOOTING
Problems
Possible Cause
Full-time Bypass
Circuit breaker button popped up as
Protection outlets
a result of overload.
stop providing
power to the
equipment
UPS doesn't
Battery undercharged or depleted
perform to its
due to frequent power outages.
expected runtime.
The power required by your
equipment slightly exceeds the
capacity of the UPS.
The battery is slightly worn-out.
UPS cannot be
UPS has a circuit breaker designed
turned on.
to prevent damage.
The battery is worn-out.
Mechanical problem.
Solution
Unplug at least one piece of
equipment from the Full-time
Surge Protection outlets,
switch off the UPS, wait for 5
seconds and reset the circuit
breaker (press down breaker
button, then switch on UPS).
Recharge the battery by leaving
the UPS plugged in and switched
on.
Unplug at least one piece of
equipment from the UPS outlets.
Consider replacing the battery.
Switch UPS off, wait for 5
seconds, and then switch UPS
on.
Consider replacing the battery.
Contact your sales
representative.
- 7 -
A
S
PPENDIX B
PECIFICATIONS
Part No.
Model
UPS Capacity
Total Capacity
(Protection)
No. of sockets
Output
Voltage (on battery)
Frequency(on battery)
Transfer Time
Voltage (single phase)
Input
Frequency
Unit Input
Protection
Overload Protection
Short Circuit
Surge Protection
Type
Typical Recharge Time
Battery
Back-up Time
Protection
Net weight Kg (lbs)
Physical
Dimension (W x D x H)
Interface
USB
Battery Back-Up
Battery Low
Alarm
Charge Abnormal
Overload
Ambient operation
Environment
Audible Noise
ULT33063
RCD-UPS700
700VA
1200VA
Style A UPSx3, Bypassx3
Simulated sine wave at 120V +/- 5%
50 or 60Hz +/- 0.3Hz
2-4 milliseconds, including detection time
120V +15%/-20% at line input
50 or 60Hz +/- 10% (auto sensing)
Circuit breaker for overload & short circuit
protection
AC Mode: If load exceeds 110% of nominal,
Buzzer beeps continuously. If load exceeds
120% of nominal for 30 seconds, 130% for 3
seconds, UPS shuts down automatically.
Back up Mode: If load exceeds 105% of
nominal for 20 seconds, 120% for 10 seconds,
130% for 3 seconds, UPS shuts down
automatically.
UPS output shuts off immediately
1140 Joules, 2ms
Sealed, maintenance-free lead acid battery,
with 3-6 years typical lifetime
6 hours (to 90% of full capacity)
9-11 minutes (a PC with 15" CRT monitor)
17-19 minutes (a PC with 15" LCD monitor)
Automatic self-test, Over discharge
protection, short circuit protection by fuse
2.58(5.67)
104 x 316 x 85 (4.1" x 12.4" x 3.3")
Battery low detecting, USB on/off scheduling
AC input/output power status display.
Slow beeping sound every 4 seconds
Rapid beeping sound every second
AC Mode: Rapid beeping sound every 0.5
second
Continuous beeping sound
3,500 meters max. elevation, 0-95% humidity
non-condensing, 0-40℃
<40dBA (1 meter from surface)