Download Print this page

t.a.c. TS-8101 General Instructions

Electronic room temperature sensors

Advertisement

Quick Links

APPLICATION
Electronic sensing of room temperature at wall locations.

SPECIFICATIONS

Sensing Element: Temperature sensitive Balco resistance.
TS-8101 Series, 1000 ohms ±0.1% at 70°F (21°C);
changes 2.2 ohms per 1°F (0.5°C at 70°F (21°C).
TS-811 Series, 1000 ohms when control dial is set to
sensed temperature.
Control Dial Range: See Table 1.
Environment:
Ambient Temperature Limits,
Shipping and Storage -40 to 160°F (-40 to 71°C).
Operating 40 to 140°F (4 to 60°C).
Humidity, 5 to 95% RH, non-condensing.
Locations, NEMA Type 1 indoor only.
Connections: Coded screw terminals.
Cover: Beige plastic.
Mounting: Wall.
Dimensions: 4-3/8" high x 2-3/4" wide x 1-5/8" deep
(111 mm x 70 mm x 43 mm).
STANDARD
TS-8111 °F
TS-8111-116 °C
TS-8111-770 °F only
OPTIONS (TS-8111 & TS-8111-116 only)
(for quantities of 24 or more of each part number)
Add "dash-number" (-XXX) suffix to base part no. for desired option.
Table-1 Specifications.
Part
Company
Number
Identification
TS-8101
TAC
TS-8101-770
Robertshaw
TS-8111
TAC
TS-8111-116
TS-8111-770
Robertshaw
Printed in U.S.A. 8-08
Control
Cover
Dial Range
Configuration
-
Blank
55-85°F
Standard cover
and two inserts
(see Options
13 to 29°C
also)
Standard cover
55-85°F
and two inserts
© Copyright 2008 TAC All Rights Reserved.
TS-8101, TS-8101-770
TS-8111, TS-8111-116
Electronic Room Temperature Sensors
ACCESSORIES
AT-61 Series
Brushed bronze cover plates
AT-70 Series
Brushed bronze cover plates (TS-81XX-770)
AT-82 Series
Digital thermometer cover kit
AT-82-770
Digital thermometer cover kit (TS-81XX-770)
AT-101
Lock cover kit
AT-104
Dial stop pins
AT-504
Plaster hole cover kit (small)
AT-505
Surface mounting base
AT-546
Auxiliary mounting plate
AT-602
Selector switch sub-base DP4T
AT-1103
Wire guard
AT-1104
Cast aluminum guard
AT-1105
Plastic guard
AT-1155
Plastic guard
AT-1165
Plastic guard
PKG-1093
Digital thermometer battery replacement kit
Figure-1 Sensor Wiring.
TS-8111-770
General Instructions
F-22633-5

Advertisement

loading

Summary of Contents for t.a.c. TS-8101

  • Page 1: Specifications

    Electronic sensing of room temperature at wall locations. SPECIFICATIONS Sensing Element: Temperature sensitive Balco resistance. TS-8101 Series, 1000 ohms ±0.1% at 70°F (21°C); changes 2.2 ohms per 1°F (0.5°C at 70°F (21°C). TS-811 Series, 1000 ohms when control dial is set to sensed temperature.
  • Page 2 Required Installation Items • Wiring diagrams • Tools (not provided): DVM (digital volt-ohm meter) Figure-3 TS-8101 Series Mounting (Cover Removed) and Appropriate screwdriver for mounting screws and termi- Part Identification. nal connections • Appropriate accessories • Mounting screws, two (2) provided for securing to a 2 x 4...
  • Page 3 CHECKOUT Measure the resistance between terminals 7 and 8 (see Figure 1). TS-8101 Series: 100 ohms ±0.1% at 70°F (21°C); changes 2.2 ohms per 1°F (0.5°C) at 70°F (21°C). TS-8111 Series (see Figure 5): 1000 ohms when control dial is set to sensed temperature.
  • Page 4 FIELD REPAIR These sensors are not field repairable. Replace a defective sensor with a functional unit. Copyright 2008, TAC All brand names, trademarks and registered 1354 Clifford Avenue trademarks are the property of their respective P.O.