Powered by
Specification
Cells Per Unit
Voltage Per Unit
Capacity
Weight
Maximum Discharge Current
Internal Resistance
Operating Temperature Range
Nominal Operating Temperature Range
Float Charging Voltage
Recommended Maximum Charging
Current Limit
Equalization and Cycle Service
Self Discharge
Terminal
Container Material
Dimensions :
Unit: mm (inch)
(http://www.csb-battery.com)
Constant Current Discharge Characteristics
F.V/Time
5MIN
10MIN
1.60V
80.2
1.67V
71.2
1.70V
67.4
1.75V
61.0
54.5
1.80V
48.0
1.85V
Constant Power Discharge Characteristics
F.V/Time
5MIN
10MIN
890
1.60V
790
1.67V
748
1.70V
1.75V
677
1.80V
605
1.85V
533
Ratings presented herein are subject to revision without notice. Please refer to www.csb-battery.com to confirm the latest version.
GP 12170
GP 12170 is a general purpose battery up to 5 years in standby
service or more than 260 cycles at 100% discharge in cycle
service. As with all CSB batteries, all are rechargeable, highly
efficient, leak proof and maintenance free.
6
12
17A h @ 20hr-rate to 1.75V per cell @25°C (77°F)
Approx. 5.5 kg(12.13 lbs)
230A(5sec)
Approx. 16 mΩ
Discharge:
Charge:
-15°C~40°C ( 5°F~104°F)
-15°C~40°C ( 5°F~104°F)
Storage:
25°C±3°C (77°F±5°F)
13.5 to 13.8 VDC/unit Average at
5.1A
14.4 to 15.0 VDC/unit Average at
CSB Batteries can be stored for more than 6 months at
25°C (77°F).
higher temperatures the time interval will be shorter.
B1/B3-L terminal to accept M5 nut & bolt
ABS(UL 94-HB) & Flammability resistance of
(UL 94-V0) can be available upon request.
Overall Height (H)
167±2 (6.57±0.08)
The system of manufacturer was certified
by TUV CERT according to ISO 9001,ISO 14001.
15MIN
30MIN
50.9
38.5
23.4
47.5
36.5
22.9
45.8
35.6
22.7
43.1
34.1
22.3
40.2
32.7
21.8
37.3
31.0
21.2
15MIN
30MIN
583
449
281
544
423
275
527
413
272
493
395
267
460
377
261
427
361
254
12V 17Ah
-15°C~50°C ( 5°F~122°F)
25°C (77°F)
25°C (77°F)
Please charge batteries before using. For
Container height (h)
165.5±2 (6.51±0.08)
60MIN
90MIN
2HR
13.8
10.1
8.03
13.7
10.0
7.99
13.6
10.0
7.97
13.4
9.86
7.92
13.3
9.79
7.87
13.1
9.68
7.80
60MIN
90MIN
2HR
166
121
96.4
164
120
96.0
163
119
95.8
161
119
95.3
160
118
94.6
158
116
93.8
CSB-manufactured
VRLA
recognized components
under UL924 and UL1989.
CSB is also certified by
ISO 9001 and ISO 14001.
Length (L)
181±2 (7.13±0.08)
76.2±1 (3.0±0.04)
Unit:A (25°C,77°F)
3HR
5HR
8HR
5.72
3.63
2.37
5.69
3.61
2.35
5.67
3.61
2.35
5.64
3.59
2.32
5.61
3.58
2.30
5.56
3.56
2.27
Unit:W (25°C,77°F)
3HR
5HR
8HR
68.6
43.6
28.4
68.5
43.4
28.3
68.4
43.3
28.2
67.9
43.2
27.9
67.3
43.0
27.6
66.8
42.9
27.3
batteries are UL-
Width (W)
10HR
20HR
1.93
1.00
1.90
0.95
1.89
0.94
1.86
0.91
1.83
0.88
1.80
0.85
10HR
20HR
23.1
12.0
22.8
11.5
22.7
11.3
22.4
10.9
22.0
10.5
21.7
10.1
RA1210
Need help?
Do you have a question about the GP 12170 and is the answer not in the manual?