The function works by integrating the error signal at fixed intervals. These intervals are TABLE OF CONTENTS expressed in repeats/minute. The acceptable range for the TC-136 is 0.01 to 10 repeats /minute. Start with a setting determined by the following formula.
REMOTE USER SET TEMPERATURE POTENTIOMETER • • • • • The bandwidth range of the TC-136 is 1°C to 100°C. The units are shipped with a default setting 0 V TO 5 V ADJUSTABLE RANGE • • • • •...
.100 center connector. TECHNICAL DESCRIPTION Model TC-136 is capable of operating from an input supply voltage of 12 through 28 VDC, common to many available thermoelectric modules. The self-contained MOSFET output devices deliver load currents from 0.1 to 25 amperes (NOTE: consult appropriate installation instructions for power...
Page 6
35. If you have entered values in the CALIBRATE box and they are the desired settings, select the Send Box Values power may be shut down. button to download these constants to the controller. 36. Initial set-up of your Model TC-136 controller is complete.
13. Now, click on the CONTROL TYPE menu key and select which type is appropriate for your application. The DEADBAND CONTROL is an on/off control and PID CONTROL is a proportional/integral/derivative control. The COMPUTER CONTROL acts like an electronic variac in that a fixed percentage of power may be applied to the load. 14.
SHLD 4. Insert the TC-136 software disk into the computer A:\ drive. To install the software from the floppy disk, select “START”, “RUN” from your Windows Desktop and then enter A:\Oi362.exe and OK. This will load the PC interface into your computer’s RAM.